0% of detected issues resolved · open: 1380 errors, 234 warnings, 2 info · 0 confirmed awaiting correction · 0 marked not an issue · 0 data edit(s) applied · checked: 5085 junctions, 1354 components, 77 disconnected_parts, 952 crossings, 3754 pipes
The 60 highest-priority issues are numbered as in the list below; smaller dots are the rest. Red = error, amber = warning, blue = info, green = resolved. Dashed lines are inactive or closed pipes.
| Category | Error | Warning | Info | Found | Resolved | Remaining |
|---|---|---|---|---|---|---|
| Topology Connectivity of the pipe network: unconnected ends, missing junctions, disconnected parts, crossings | 1375 | 221 | 1 | 1597 | 0 | 1597 |
| Completeness Missing or placeholder attribute values (null, 0, 'unknown') | 1 | 8 | 1 | 10 | 0 | 10 |
| Plausibility Values that are out of range or inconsistent with each other or with the geometry | 5 | 5 | 0 | 5 | ||
| Geometry Shape of the features: zero length, duplicates, overlaps, multi-part or self-intersecting lines | 4 | 4 | 0 | 4 |
Layers and fields were recognised automatically from the uploaded data (no manual mapping).
| Layer | Recognised as | Field roles |
|---|---|---|
| Junction_Rev03 Point · 5085 | Junctions / nodes 100% confidence | id = Junc_ID, elevation = Elevation, demand = BaseDemand, x = X_Coord, y = Y_Coord |
| Pipe_Functional_Rev04 MultiLineString · 3754 | Pipes 100% confidence | id = Pipe_ID2, from = Starting_N, to = Ending_N, length = Length, material = Material, diameter = Size, outer_diameter = OD, inner_diameter = ID, roughness = HW_C, year = year, age = Age_yr, function = Function, pressure_class = PN_Class, status = Status |
| # | Severity | Check | Layer / asset | Finding & suggested action | Status |
|---|---|---|---|---|---|
| 1 | ERROR P100 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev0467 pipes near 56672-2 | 67 pipe(s), 952 m in total incl. 34 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 2 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev03116109 | Junction 116109 (degree 1) lies on pipe 77106 (DN 160, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (37 m). → Split pipe 77106 at junction 116109 so both are connected. | Open |
| 3 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev03116112 | Junction 116112 (degree 1) lies on pipe 77106 (DN 160, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 77106 at junction 116112 so both are connected. | Open |
| 4 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0312 | Junction 12 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56418-2 at junction 12 so both are connected. | Open |
| 5 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0313 | Junction 13 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56418-2 at junction 13 so both are connected. | Open |
| 6 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314 | Junction 14 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 56418-2 at junction 14 so both are connected. | Open |
| 7 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314571 | Junction 14571 (degree 1) lies on pipe 52847 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52847 at junction 14571 so both are connected. | Open |
| 8 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314573 | Junction 14573 (degree 1) lies on pipe 56493-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 17 pipe(s) (426 m). → Split pipe 56493-2 at junction 14573 so both are connected. | Open |
| 9 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314576 | Junction 14576 (degree 1) lies on pipe 52847 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 52847 at junction 14576 so both are connected. | Open |
| 10 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314628 | Junction 14628 (degree 1) lies on pipe 56493-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56493-2 at junction 14628 so both are connected. | Open |
| 11 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318657 | Junction 18657 (degree 2) lies on pipe 95312 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (56 m). → Split pipe 95312 at junction 18657 so both are connected. | Open |
| 12 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318660 | Junction 18660 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 95313 at junction 18660 so both are connected. | Open |
| 13 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318662 | Junction 18662 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 95313 at junction 18662 so both are connected. | Open |
| 14 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318664 | Junction 18664 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 95313 at junction 18664 so both are connected. | Open |
| 15 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318666 | Junction 18666 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 95313 at junction 18666 so both are connected. | Open |
| 16 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318668 | Junction 18668 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 95313 at junction 18668 so both are connected. | Open |
| 17 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318670 | Junction 18670 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 95313 at junction 18670 so both are connected. | Open |
| 18 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318672 | Junction 18672 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 95313 at junction 18672 so both are connected. | Open |
| 19 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318674 | Junction 18674 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18674 so both are connected. | Open |
| 20 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318676 | Junction 18676 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 95354 at junction 18676 so both are connected. | Open |
| 21 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318678 | Junction 18678 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 95354 at junction 18678 so both are connected. | Open |
| 22 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318680 | Junction 18680 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 95354 at junction 18680 so both are connected. | Open |
| 23 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318682 | Junction 18682 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 95354 at junction 18682 so both are connected. | Open |
| 24 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318684 | Junction 18684 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 95354 at junction 18684 so both are connected. | Open |
| 25 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318686 | Junction 18686 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95313 at junction 18686 so both are connected. | Open |
| 26 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318688 | Junction 18688 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95313 at junction 18688 so both are connected. | Open |
| 27 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318690 | Junction 18690 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18690 so both are connected. | Open |
| 28 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318692 | Junction 18692 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 95354 at junction 18692 so both are connected. | Open |
| 29 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318694 | Junction 18694 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18694 so both are connected. | Open |
| 30 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318696 | Junction 18696 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18696 so both are connected. | Open |
| 31 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318698 | Junction 18698 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18698 so both are connected. | Open |
| 32 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318700 | Junction 18700 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 95354 at junction 18700 so both are connected. | Open |
| 33 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318702 | Junction 18702 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 95354 at junction 18702 so both are connected. | Open |
| 34 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318704 | Junction 18704 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18704 so both are connected. | Open |
| 35 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318706 | Junction 18706 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18706 so both are connected. | Open |
| 36 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318708 | Junction 18708 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 95354 at junction 18708 so both are connected. | Open |
| 37 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318710 | Junction 18710 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18710 so both are connected. | Open |
| 38 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318712 | Junction 18712 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 95354 at junction 18712 so both are connected. | Open |
| 39 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318714 | Junction 18714 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18714 so both are connected. | Open |
| 40 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318716 | Junction 18716 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 95354 at junction 18716 so both are connected. | Open |
| 41 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318718 | Junction 18718 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95354 at junction 18718 so both are connected. | Open |
| 42 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318720 | Junction 18720 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 95354 at junction 18720 so both are connected. | Open |
| 43 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318767 | Junction 18767 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 95313 at junction 18767 so both are connected. | Open |
| 44 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318770 | Junction 18770 (degree 1) lies on pipe 95312 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 95312 at junction 18770 so both are connected. | Open |
| 45 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318771 | Junction 18771 (degree 1) lies on pipe 95312 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 95312 at junction 18771 so both are connected. | Open |
| 46 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318773 | Junction 18773 (degree 1) lies on pipe 95312 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 95312 at junction 18773 so both are connected. | Open |
| 47 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318775 | Junction 18775 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95313 at junction 18775 so both are connected. | Open |
| 48 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318777 | Junction 18777 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 95313 at junction 18777 so both are connected. | Open |
| 49 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318779 | Junction 18779 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 95313 at junction 18779 so both are connected. | Open |
| 50 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318781 | Junction 18781 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 95313 at junction 18781 so both are connected. | Open |
| 51 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318783 | Junction 18783 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 95313 at junction 18783 so both are connected. | Open |
| 52 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318785 | Junction 18785 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 95313 at junction 18785 so both are connected. | Open |
| 53 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318788 | Junction 18788 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 95313 at junction 18788 so both are connected. | Open |
| 54 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318789 | Junction 18789 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 95313 at junction 18789 so both are connected. | Open |
| 55 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318791 | Junction 18791 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 95313 at junction 18791 so both are connected. | Open |
| 56 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0318793 | Junction 18793 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 95313 at junction 18793 so both are connected. | Open |
| 57 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0319603 | Junction 19603 (degree 1) lies on pipe 93645 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 93645 at junction 19603 so both are connected. | Open |
| 58 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0319605 | Junction 19605 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 6 pipe(s) (2,996 m). → Split pipe 52817 at junction 19605 so both are connected. | Open |
| 59 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0319999 | Junction 19999 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95313 at junction 19999 so both are connected. | Open |
| 60 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0320001 | Junction 20001 (degree 1) lies on pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 95313 at junction 20001 so both are connected. | Open |
| 61 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0320003 | Junction 20003 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 95354 at junction 20003 so both are connected. | Open |
| 62 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0320005 | Junction 20005 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 95354 at junction 20005 so both are connected. | Open |
| 63 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0320007 | Junction 20007 (degree 1) lies on pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 95354 at junction 20007 so both are connected. | Open |
| 64 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0320389 | Junction 20389 (degree 1) lies on pipe 93643 (DN 355, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 93643 at junction 20389 so both are connected. | Open |
| 65 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0325080 | Junction 25080 (degree 1) lies on pipe 52859 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52859 at junction 25080 so both are connected. | Open |
| 66 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0325082 | Junction 25082 (degree 1) lies on pipe 56477 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 56477 at junction 25082 so both are connected. | Open |
| 67 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0333502 | Junction 33502 (degree 1) lies on pipe 102634-3 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 102634-3 at junction 33502 so both are connected. | Open |
| 68 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0366680 | Junction 66680 (degree 1) lies on pipe 56447 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56447 at junction 66680 so both are connected. | Open |
| 69 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0366816 | Junction 66816 (degree 1) lies on pipe 89522-2 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (128 m). → Split pipe 89522-2 at junction 66816 so both are connected. | Open |
| 70 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0372749 | Junction 72749 (degree 1) lies on pipe 56431 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (32 m). → Split pipe 56431 at junction 72749 so both are connected. | Open |
| 71 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0372858 | Junction 72858 (degree 1) lies on pipe 56633-19 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 179 pipe(s) (3,395 m). → Split pipe 56633-19 at junction 72858 so both are connected. | Open |
| 72 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0372862 | Junction 72862 (degree 2) lies on pipe 53745 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 53745 at junction 72862 so both are connected. | Open |
| 73 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0375888 | Junction 75888 (degree 1) lies on pipe 52910-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 7 pipe(s) (182 m). → Split pipe 52910-2 at junction 75888 so both are connected. | Open |
| 74 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0376015 | Junction 76015 (degree 1) lies on pipe 89498-4 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 22 pipe(s) (371 m). → Split pipe 89498-4 at junction 76015 so both are connected. | Open |
| 75 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0376022 | Junction 76022 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 22 pipe(s) (371 m). → Split pipe 52877 at junction 76022 so both are connected. | Open |
| 76 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0376028 | Junction 76028 (degree 1) lies on pipe 52821 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 31 pipe(s) (315 m). → Split pipe 52821 at junction 76028 so both are connected. | Open |
| 77 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0377957 | Junction 77957 (degree 1) lies on pipe 89469-12 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 89469-12 at junction 77957 so both are connected. | Open |
| 78 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0377963 | Junction 77963 (degree 1) lies on pipe 89511-19 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 89511-19 at junction 77963 so both are connected. | Open |
| 79 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0378258 | Junction 78258 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 89522-1 at junction 78258 so both are connected. | Open |
| 80 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0378639 | Junction 78639 (degree 1) lies on pipe 89498-2 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89498-2 at junction 78639 so both are connected. | Open |
| 81 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0381371 | Junction 81371 (degree 1) lies on pipe 56396 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (4 m). → Split pipe 56396 at junction 81371 so both are connected. | Open |
| 82 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038454 | Junction 8454 (degree 1) lies on pipe 52889 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 29 pipe(s) (207 m). → Split pipe 52889 at junction 8454 so both are connected. | Open |
| 83 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038462 | Junction 8462 (degree 1) lies on pipe 89469-9 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 89469-9 at junction 8462 so both are connected. | Open |
| 84 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038463 | Junction 8463 (degree 1) lies on pipe 89469-9 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 89469-9 at junction 8463 so both are connected. | Open |
| 85 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038469 | Junction 8469 (degree 1) lies on pipe 89469-5 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 89469-5 at junction 8469 so both are connected. | Open |
| 86 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038514 | Junction 8514 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 179 pipe(s) (3,395 m). → Split pipe 56384 at junction 8514 so both are connected. | Open |
| 87 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386430 | Junction 86430 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 53503 at junction 86430 so both are connected. | Open |
| 88 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386432 | Junction 86432 (degree 2) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (27 m). → Split pipe 53503 at junction 86432 so both are connected. | Open |
| 89 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386434 | Junction 86434 (degree 2) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (26 m). → Split pipe 53503 at junction 86434 so both are connected. | Open |
| 90 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386436 | Junction 86436 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53503 at junction 86436 so both are connected. | Open |
| 91 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386438 | Junction 86438 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 53503 at junction 86438 so both are connected. | Open |
| 92 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386440 | Junction 86440 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (26 m). → Split pipe 53503 at junction 86440 so both are connected. | Open |
| 93 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386442 | Junction 86442 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 53503 at junction 86442 so both are connected. | Open |
| 94 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386445 | Junction 86445 (degree 2) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (23 m). → Split pipe 53503 at junction 86445 so both are connected. | Open |
| 95 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386449 | Junction 86449 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53503 at junction 86449 so both are connected. | Open |
| 96 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386451 | Junction 86451 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53503 at junction 86451 so both are connected. | Open |
| 97 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386453 | Junction 86453 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53503 at junction 86453 so both are connected. | Open |
| 98 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386455 | Junction 86455 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53503 at junction 86455 so both are connected. | Open |
| 99 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386457 | Junction 86457 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 53503 at junction 86457 so both are connected. | Open |
| 100 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386459 | Junction 86459 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53503 at junction 86459 so both are connected. | Open |
| 101 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386461 | Junction 86461 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 53503 at junction 86461 so both are connected. | Open |
| 102 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386463 | Junction 86463 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53503 at junction 86463 so both are connected. | Open |
| 103 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386465 | Junction 86465 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 53503 at junction 86465 so both are connected. | Open |
| 104 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386467 | Junction 86467 (degree 1) lies on pipe 53505 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53505 at junction 86467 so both are connected. | Open |
| 105 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386717 | Junction 86717 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56418-2 at junction 86717 so both are connected. | Open |
| 106 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386721 | Junction 86721 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56418-2 at junction 86721 so both are connected. | Open |
| 107 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386729 | Junction 86729 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56418-2 at junction 86729 so both are connected. | Open |
| 108 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386731 | Junction 86731 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56418-2 at junction 86731 so both are connected. | Open |
| 109 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386733 | Junction 86733 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56418-2 at junction 86733 so both are connected. | Open |
| 110 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386737 | Junction 86737 (degree 1) lies on pipe 56418-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56418-2 at junction 86737 so both are connected. | Open |
| 111 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386771 | Junction 86771 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 56395 at junction 86771 so both are connected. | Open |
| 112 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386773 | Junction 86773 (degree 2) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 56395 at junction 86773 so both are connected. | Open |
| 113 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386775 | Junction 86775 (degree 2) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (22 m). → Split pipe 56395 at junction 86775 so both are connected. | Open |
| 114 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386777 | Junction 86777 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56395 at junction 86777 so both are connected. | Open |
| 115 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386779 | Junction 86779 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56395 at junction 86779 so both are connected. | Open |
| 116 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386781 | Junction 86781 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 56395 at junction 86781 so both are connected. | Open |
| 117 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386783 | Junction 86783 (degree 2) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (18 m). → Split pipe 53501 at junction 86783 so both are connected. | Open |
| 118 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386785 | Junction 86785 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56395 at junction 86785 so both are connected. | Open |
| 119 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386787 | Junction 86787 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56395 at junction 86787 so both are connected. | Open |
| 120 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386789 | Junction 86789 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56395 at junction 86789 so both are connected. | Open |
| 121 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386793 | Junction 86793 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56395 at junction 86793 so both are connected. | Open |
| 122 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386796 | Junction 86796 (degree 1) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53501 at junction 86796 so both are connected. | Open |
| 123 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386798 | Junction 86798 (degree 2) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (17 m). → Split pipe 53501 at junction 86798 so both are connected. | Open |
| 124 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386801 | Junction 86801 (degree 1) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53501 at junction 86801 so both are connected. | Open |
| 125 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386803 | Junction 86803 (degree 2) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 53501 at junction 86803 so both are connected. | Open |
| 126 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386805 | Junction 86805 (degree 1) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 53501 at junction 86805 so both are connected. | Open |
| 127 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386807 | Junction 86807 (degree 1) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (26 m). → Split pipe 53501 at junction 86807 so both are connected. | Open |
| 128 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386809 | Junction 86809 (degree 2) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (37 m). → Split pipe 53501 at junction 86809 so both are connected. | Open |
| 129 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386811 | Junction 86811 (degree 2) lies on pipe 53502 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 53502 at junction 86811 so both are connected. | Open |
| 130 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386814 | Junction 86814 (degree 1) lies on pipe 53501 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53501 at junction 86814 so both are connected. | Open |
| 131 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386818 | Junction 86818 (degree 1) lies on pipe 53502 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53502 at junction 86818 so both are connected. | Open |
| 132 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386820 | Junction 86820 (degree 1) lies on pipe 53502 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53502 at junction 86820 so both are connected. | Open |
| 133 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386822 | Junction 86822 (degree 1) lies on pipe 53502 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53502 at junction 86822 so both are connected. | Open |
| 134 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386824 | Junction 86824 (degree 1) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52881 at junction 86824 so both are connected. | Open |
| 135 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386826 | Junction 86826 (degree 2) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 52881 at junction 86826 so both are connected. | Open |
| 136 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386829 | Junction 86829 (degree 2) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (50 m). → Split pipe 52881 at junction 86829 so both are connected. | Open |
| 137 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386832 | Junction 86832 (degree 2) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (25 m). → Split pipe 52881 at junction 86832 so both are connected. | Open |
| 138 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386835 | Junction 86835 (degree 1) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52881 at junction 86835 so both are connected. | Open |
| 139 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386837 | Junction 86837 (degree 1) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52881 at junction 86837 so both are connected. | Open |
| 140 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386839 | Junction 86839 (degree 1) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52881 at junction 86839 so both are connected. | Open |
| 141 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386841 | Junction 86841 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52919 at junction 86841 so both are connected. | Open |
| 142 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386843 | Junction 86843 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52919 at junction 86843 so both are connected. | Open |
| 143 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386845 | Junction 86845 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52919 at junction 86845 so both are connected. | Open |
| 144 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386847 | Junction 86847 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52919 at junction 86847 so both are connected. | Open |
| 145 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386849 | Junction 86849 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52919 at junction 86849 so both are connected. | Open |
| 146 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386851 | Junction 86851 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52919 at junction 86851 so both are connected. | Open |
| 147 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386853 | Junction 86853 (degree 2) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (27 m). → Split pipe 52919 at junction 86853 so both are connected. | Open |
| 148 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386856 | Junction 86856 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52919 at junction 86856 so both are connected. | Open |
| 149 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386858 | Junction 86858 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 52919 at junction 86858 so both are connected. | Open |
| 150 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386859 | Junction 86859 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (105 m). → Split pipe 52919 at junction 86859 so both are connected. | Open |
| 151 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386862 | Junction 86862 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52877 at junction 86862 so both are connected. | Open |
| 152 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386864 | Junction 86864 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (33 m). → Split pipe 52919 at junction 86864 so both are connected. | Open |
| 153 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386868 | Junction 86868 (degree 1) lies on pipe 52919 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52919 at junction 86868 so both are connected. | Open |
| 154 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386873 | Junction 86873 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52877 at junction 86873 so both are connected. | Open |
| 155 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386875 | Junction 86875 (degree 1) lies on pipe 56501-2 (DN 20, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56501-2 at junction 86875 so both are connected. | Open |
| 156 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386877 | Junction 86877 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52877 at junction 86877 so both are connected. | Open |
| 157 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386879 | Junction 86879 (degree 1) lies on pipe 56501-2 (DN 20, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56501-2 at junction 86879 so both are connected. | Open |
| 158 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386881 | Junction 86881 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52877 at junction 86881 so both are connected. | Open |
| 159 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386883 | Junction 86883 (degree 1) lies on pipe 56501-1 (DN 20, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56501-1 at junction 86883 so both are connected. | Open |
| 160 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386885 | Junction 86885 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52877 at junction 86885 so both are connected. | Open |
| 161 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386887 | Junction 86887 (degree 1) lies on pipe 52878 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52878 at junction 86887 so both are connected. | Open |
| 162 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386889 | Junction 86889 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52877 at junction 86889 so both are connected. | Open |
| 163 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386891 | Junction 86891 (degree 1) lies on pipe 52878 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52878 at junction 86891 so both are connected. | Open |
| 164 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386893 | Junction 86893 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52877 at junction 86893 so both are connected. | Open |
| 165 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386895 | Junction 86895 (degree 1) lies on pipe 52878 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52878 at junction 86895 so both are connected. | Open |
| 166 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386897 | Junction 86897 (degree 1) lies on pipe 52878 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52878 at junction 86897 so both are connected. | Open |
| 167 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386899 | Junction 86899 (degree 1) lies on pipe 52878 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52878 at junction 86899 so both are connected. | Open |
| 168 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386901 | Junction 86901 (degree 1) lies on pipe 52878 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52878 at junction 86901 so both are connected. | Open |
| 169 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386903 | Junction 86903 (degree 1) lies on pipe 52878 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52878 at junction 86903 so both are connected. | Open |
| 170 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386905 | Junction 86905 (degree 1) lies on pipe 52878 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52878 at junction 86905 so both are connected. | Open |
| 171 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386907 | Junction 86907 (degree 1) lies on pipe 56502 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56502 at junction 86907 so both are connected. | Open |
| 172 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386909 | Junction 86909 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52877 at junction 86909 so both are connected. | Open |
| 173 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386911 | Junction 86911 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52877 at junction 86911 so both are connected. | Open |
| 174 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386913 | Junction 86913 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52877 at junction 86913 so both are connected. | Open |
| 175 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386915 | Junction 86915 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52877 at junction 86915 so both are connected. | Open |
| 176 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386917 | Junction 86917 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52877 at junction 86917 so both are connected. | Open |
| 177 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386919 | Junction 86919 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52877 at junction 86919 so both are connected. | Open |
| 178 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386921 | Junction 86921 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52899 at junction 86921 so both are connected. | Open |
| 179 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386923 | Junction 86923 (degree 1) lies on pipe 56500 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56500 at junction 86923 so both are connected. | Open |
| 180 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386925 | Junction 86925 (degree 1) lies on pipe 56500 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 56500 at junction 86925 so both are connected. | Open |
| 181 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386927 | Junction 86927 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53731 at junction 86927 so both are connected. | Open |
| 182 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386929 | Junction 86929 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 53731 at junction 86929 so both are connected. | Open |
| 183 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386931 | Junction 86931 (degree 2) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (25 m). → Split pipe 53731 at junction 86931 so both are connected. | Open |
| 184 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386934 | Junction 86934 (degree 2) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 53731 at junction 86934 so both are connected. | Open |
| 185 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386937 | Junction 86937 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53731 at junction 86937 so both are connected. | Open |
| 186 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386939 | Junction 86939 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53731 at junction 86939 so both are connected. | Open |
| 187 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386941 | Junction 86941 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 53731 at junction 86941 so both are connected. | Open |
| 188 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386943 | Junction 86943 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 53731 at junction 86943 so both are connected. | Open |
| 189 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386945 | Junction 86945 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53731 at junction 86945 so both are connected. | Open |
| 190 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386947 | Junction 86947 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53731 at junction 86947 so both are connected. | Open |
| 191 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386949 | Junction 86949 (degree 2) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 53731 at junction 86949 so both are connected. | Open |
| 192 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386951 | Junction 86951 (degree 2) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (18 m). → Split pipe 53731 at junction 86951 so both are connected. | Open |
| 193 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386953 | Junction 86953 (degree 1) lies on pipe 53730-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53730-2 at junction 86953 so both are connected. | Open |
| 194 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386958 | Junction 86958 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53730-1 at junction 86958 so both are connected. | Open |
| 195 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386962 | Junction 86962 (degree 2) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (22 m). → Split pipe 53730-1 at junction 86962 so both are connected. | Open |
| 196 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386965 | Junction 86965 (degree 2) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 53730-1 at junction 86965 so both are connected. | Open |
| 197 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386968 | Junction 86968 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 53730-1 at junction 86968 so both are connected. | Open |
| 198 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386970 | Junction 86970 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53730-1 at junction 86970 so both are connected. | Open |
| 199 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386972 | Junction 86972 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 53730-1 at junction 86972 so both are connected. | Open |
| 200 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386974 | Junction 86974 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53730-1 at junction 86974 so both are connected. | Open |
| 201 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386976 | Junction 86976 (degree 2) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (23 m). → Split pipe 53730-1 at junction 86976 so both are connected. | Open |
| 202 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386978 | Junction 86978 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53730-1 at junction 86978 so both are connected. | Open |
| 203 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386980 | Junction 86980 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53730-1 at junction 86980 so both are connected. | Open |
| 204 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386983 | Junction 86983 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53730-1 at junction 86983 so both are connected. | Open |
| 205 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386985 | Junction 86985 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53730-1 at junction 86985 so both are connected. | Open |
| 206 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386987 | Junction 86987 (degree 2) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 53730-1 at junction 86987 so both are connected. | Open |
| 207 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386989 | Junction 86989 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53730-1 at junction 86989 so both are connected. | Open |
| 208 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386992 | Junction 86992 (degree 2) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 53730-1 at junction 86992 so both are connected. | Open |
| 209 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386994 | Junction 86994 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53730-1 at junction 86994 so both are connected. | Open |
| 210 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386996 | Junction 86996 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 53730-1 at junction 86996 so both are connected. | Open |
| 211 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386998 | Junction 86998 (degree 1) lies on pipe 53704 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 53704 at junction 86998 so both are connected. | Open |
| 212 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387000 | Junction 87000 (degree 1) lies on pipe 53704 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 53704 at junction 87000 so both are connected. | Open |
| 213 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387002 | Junction 87002 (degree 1) lies on pipe 53704 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 53704 at junction 87002 so both are connected. | Open |
| 214 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387005 | Junction 87005 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53730-1 at junction 87005 so both are connected. | Open |
| 215 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387007 | Junction 87007 (degree 1) lies on pipe 53703-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 53703-1 at junction 87007 so both are connected. | Open |
| 216 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387009 | Junction 87009 (degree 2) lies on pipe 53703-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 53703-1 at junction 87009 so both are connected. | Open |
| 217 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387011 | Junction 87011 (degree 1) lies on pipe 53703-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 53703-1 at junction 87011 so both are connected. | Open |
| 218 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387013 | Junction 87013 (degree 1) lies on pipe 53703-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 53703-1 at junction 87013 so both are connected. | Open |
| 219 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387015 | Junction 87015 (degree 1) lies on pipe 53703-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53703-1 at junction 87015 so both are connected. | Open |
| 220 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387017 | Junction 87017 (degree 1) lies on pipe 53703-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 53703-1 at junction 87017 so both are connected. | Open |
| 221 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387021 | Junction 87021 (degree 1) lies on pipe 53705 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 53705 at junction 87021 so both are connected. | Open |
| 222 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387023 | Junction 87023 (degree 1) lies on pipe 53705 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53705 at junction 87023 so both are connected. | Open |
| 223 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387025 | Junction 87025 (degree 1) lies on pipe 53704 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53704 at junction 87025 so both are connected. | Open |
| 224 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387027 | Junction 87027 (degree 1) lies on pipe 53704 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53704 at junction 87027 so both are connected. | Open |
| 225 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387029 | Junction 87029 (degree 1) lies on pipe 53704 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53704 at junction 87029 so both are connected. | Open |
| 226 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387031 | Junction 87031 (degree 1) lies on pipe 53704 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53704 at junction 87031 so both are connected. | Open |
| 227 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387033 | Junction 87033 (degree 1) lies on pipe 53704 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 53704 at junction 87033 so both are connected. | Open |
| 228 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387035 | Junction 87035 (degree 1) lies on pipe 53508 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 53508 at junction 87035 so both are connected. | Open |
| 229 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387037 | Junction 87037 (degree 1) lies on pipe 53508 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 53508 at junction 87037 so both are connected. | Open |
| 230 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387039 | Junction 87039 (degree 1) lies on pipe 53508 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53508 at junction 87039 so both are connected. | Open |
| 231 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387041 | Junction 87041 (degree 1) lies on pipe 53508 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53508 at junction 87041 so both are connected. | Open |
| 232 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387043 | Junction 87043 (degree 1) lies on pipe 53508 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53508 at junction 87043 so both are connected. | Open |
| 233 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387045 | Junction 87045 (degree 1) lies on pipe 53508 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53508 at junction 87045 so both are connected. | Open |
| 234 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387047 | Junction 87047 (degree 1) lies on pipe 53508 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53508 at junction 87047 so both are connected. | Open |
| 235 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387075 | Junction 87075 (degree 1) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56430 at junction 87075 so both are connected. | Open |
| 236 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387077 | Junction 87077 (degree 2) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (14 m). → Split pipe 56430 at junction 87077 so both are connected. | Open |
| 237 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387079 | Junction 87079 (degree 1) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 56430 at junction 87079 so both are connected. | Open |
| 238 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387081 | Junction 87081 (degree 1) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56430 at junction 87081 so both are connected. | Open |
| 239 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387084 | Junction 87084 (degree 1) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56430 at junction 87084 so both are connected. | Open |
| 240 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387086 | Junction 87086 (degree 1) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56430 at junction 87086 so both are connected. | Open |
| 241 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387088 | Junction 87088 (degree 1) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (25 m). → Split pipe 56430 at junction 87088 so both are connected. | Open |
| 242 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387092 | Junction 87092 (degree 1) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56430 at junction 87092 so both are connected. | Open |
| 243 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038716 | Junction 8716 (degree 1) lies on pipe 89497-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 89497-1 at junction 8716 so both are connected. | Open |
| 244 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038718 | Junction 8718 (degree 1) lies on pipe 89497-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 89497-1 at junction 8718 so both are connected. | Open |
| 245 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038719 | Junction 8719 (degree 1) lies on pipe 89497-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 89497-1 at junction 8719 so both are connected. | Open |
| 246 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038720 | Junction 8720 (degree 1) lies on pipe 89497-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89497-1 at junction 8720 so both are connected. | Open |
| 247 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038725 | Junction 8725 (degree 1) lies on pipe 89497-2 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 89497-2 at junction 8725 so both are connected. | Open |
| 248 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038728 | Junction 8728 (degree 1) lies on pipe 52908-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 16 pipe(s) (261 m). → Split pipe 52908-2 at junction 8728 so both are connected. | Open |
| 249 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387324 | Junction 87324 (degree 1) lies on pipe 56526-1 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56526-1 at junction 87324 so both are connected. | Open |
| 250 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387330 | Junction 87330 (degree 1) lies on pipe 56526-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56526-2 at junction 87330 so both are connected. | Open |
| 251 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387332 | Junction 87332 (degree 1) lies on pipe 56526-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56526-2 at junction 87332 so both are connected. | Open |
| 252 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387334 | Junction 87334 (degree 1) lies on pipe 56526-3 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56526-3 at junction 87334 so both are connected. | Open |
| 253 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387336 | Junction 87336 (degree 1) lies on pipe 56526-3 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56526-3 at junction 87336 so both are connected. | Open |
| 254 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387338 | Junction 87338 (degree 1) lies on pipe 56526-3 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56526-3 at junction 87338 so both are connected. | Open |
| 255 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387340 | Junction 87340 (degree 1) lies on pipe 56526-3 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56526-3 at junction 87340 so both are connected. | Open |
| 256 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387342 | Junction 87342 (degree 1) lies on pipe 56526-3 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56526-3 at junction 87342 so both are connected. | Open |
| 257 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387344 | Junction 87344 (degree 1) lies on pipe 56526-3 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56526-3 at junction 87344 so both are connected. | Open |
| 258 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387476 | Junction 87476 (degree 1) lies on pipe 56419-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56419-2 at junction 87476 so both are connected. | Open |
| 259 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387484 | Junction 87484 (degree 1) lies on pipe 56419-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56419-2 at junction 87484 so both are connected. | Open |
| 260 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387486 | Junction 87486 (degree 1) lies on pipe 56419-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56419-1 at junction 87486 so both are connected. | Open |
| 261 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387713 | Junction 87713 (degree 2) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (22 m). → Split pipe 56412 at junction 87713 so both are connected. | Open |
| 262 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387715 | Junction 87715 (degree 1) lies on pipe 56453 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56453 at junction 87715 so both are connected. | Open |
| 263 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387717 | Junction 87717 (degree 1) lies on pipe 56453 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56453 at junction 87717 so both are connected. | Open |
| 264 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387719 | Junction 87719 (degree 2) lies on pipe 56447 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (29 m). → Split pipe 56447 at junction 87719 so both are connected. | Open |
| 265 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387721 | Junction 87721 (degree 1) lies on pipe 56448 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 56448 at junction 87721 so both are connected. | Open |
| 266 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387723 | Junction 87723 (degree 1) lies on pipe 56428 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56428 at junction 87723 so both are connected. | Open |
| 267 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387725 | Junction 87725 (degree 1) lies on pipe 56453 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56453 at junction 87725 so both are connected. | Open |
| 268 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387727 | Junction 87727 (degree 1) lies on pipe 56453 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56453 at junction 87727 so both are connected. | Open |
| 269 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387729 | Junction 87729 (degree 1) lies on pipe 56453 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56453 at junction 87729 so both are connected. | Open |
| 270 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387731 | Junction 87731 (degree 2) lies on pipe 56466 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (38 m). → Split pipe 56466 at junction 87731 so both are connected. | Open |
| 271 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387733 | Junction 87733 (degree 1) lies on pipe 56465 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56465 at junction 87733 so both are connected. | Open |
| 272 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387735 | Junction 87735 (degree 1) lies on pipe 56465 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56465 at junction 87735 so both are connected. | Open |
| 273 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387739 | Junction 87739 (degree 1) lies on pipe 56411 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56411 at junction 87739 so both are connected. | Open |
| 274 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387741 | Junction 87741 (degree 2) lies on pipe 56407-1 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (23 m). → Split pipe 56407-1 at junction 87741 so both are connected. | Open |
| 275 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387743 | Junction 87743 (degree 2) lies on pipe 56413 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 56413 at junction 87743 so both are connected. | Open |
| 276 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387745 | Junction 87745 (degree 1) lies on pipe 56411 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56411 at junction 87745 so both are connected. | Open |
| 277 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387747 | Junction 87747 (degree 1) lies on pipe 56407-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56407-2 at junction 87747 so both are connected. | Open |
| 278 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387749 | Junction 87749 (degree 1) lies on pipe 56411 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (30 m). → Split pipe 56411 at junction 87749 so both are connected. | Open |
| 279 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387751 | Junction 87751 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56412 at junction 87751 so both are connected. | Open |
| 280 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387753 | Junction 87753 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 56412 at junction 87753 so both are connected. | Open |
| 281 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387759 | Junction 87759 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 56412 at junction 87759 so both are connected. | Open |
| 282 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387761 | Junction 87761 (degree 2) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 56412 at junction 87761 so both are connected. | Open |
| 283 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387764 | Junction 87764 (degree 1) lies on pipe 56413 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56413 at junction 87764 so both are connected. | Open |
| 284 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387766 | Junction 87766 (degree 2) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (29 m). → Split pipe 56412 at junction 87766 so both are connected. | Open |
| 285 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387768 | Junction 87768 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56412 at junction 87768 so both are connected. | Open |
| 286 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387770 | Junction 87770 (degree 2) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (18 m). → Split pipe 56412 at junction 87770 so both are connected. | Open |
| 287 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387772 | Junction 87772 (degree 1) lies on pipe 56406 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 56406 at junction 87772 so both are connected. | Open |
| 288 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387774 | Junction 87774 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56412 at junction 87774 so both are connected. | Open |
| 289 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387776 | Junction 87776 (degree 1) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 56399-2 at junction 87776 so both are connected. | Open |
| 290 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387778 | Junction 87778 (degree 2) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (32 m). → Split pipe 56399-2 at junction 87778 so both are connected. | Open |
| 291 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387780 | Junction 87780 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56412 at junction 87780 so both are connected. | Open |
| 292 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387784 | Junction 87784 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56412 at junction 87784 so both are connected. | Open |
| 293 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387788 | Junction 87788 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56412 at junction 87788 so both are connected. | Open |
| 294 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387790 | Junction 87790 (degree 1) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 56399-2 at junction 87790 so both are connected. | Open |
| 295 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387792 | Junction 87792 (degree 2) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (23 m). → Split pipe 56399-2 at junction 87792 so both are connected. | Open |
| 296 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387794 | Junction 87794 (degree 2) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 56399-2 at junction 87794 so both are connected. | Open |
| 297 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387796 | Junction 87796 (degree 2) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (26 m). → Split pipe 56399-2 at junction 87796 so both are connected. | Open |
| 298 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387798 | Junction 87798 (degree 1) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (24 m). → Split pipe 56399-2 at junction 87798 so both are connected. | Open |
| 299 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387802 | Junction 87802 (degree 2) lies on pipe 56399-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (33 m). → Split pipe 56399-1 at junction 87802 so both are connected. | Open |
| 300 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387811 | Junction 87811 (degree 1) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56399-2 at junction 87811 so both are connected. | Open |
| 301 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387814 | Junction 87814 (degree 1) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 56399-2 at junction 87814 so both are connected. | Open |
| 302 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387816 | Junction 87816 (degree 1) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 56399-2 at junction 87816 so both are connected. | Open |
| 303 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387820 | Junction 87820 (degree 1) lies on pipe 56399-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56399-2 at junction 87820 so both are connected. | Open |
| 304 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387823 | Junction 87823 (degree 1) lies on pipe 56397 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56397 at junction 87823 so both are connected. | Open |
| 305 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387825 | Junction 87825 (degree 1) lies on pipe 56397 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56397 at junction 87825 so both are connected. | Open |
| 306 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387859 | Junction 87859 (degree 1) lies on pipe 52882-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52882-1 at junction 87859 so both are connected. | Open |
| 307 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387861 | Junction 87861 (degree 1) lies on pipe 52882-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52882-1 at junction 87861 so both are connected. | Open |
| 308 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387863 | Junction 87863 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52882-2 at junction 87863 so both are connected. | Open |
| 309 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387865 | Junction 87865 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52882-2 at junction 87865 so both are connected. | Open |
| 310 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387867 | Junction 87867 (degree 2) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (17 m). → Split pipe 52882-2 at junction 87867 so both are connected. | Open |
| 311 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387871 | Junction 87871 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52882-2 at junction 87871 so both are connected. | Open |
| 312 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387874 | Junction 87874 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52882-2 at junction 87874 so both are connected. | Open |
| 313 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387876 | Junction 87876 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52882-2 at junction 87876 so both are connected. | Open |
| 314 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387878 | Junction 87878 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52882-2 at junction 87878 so both are connected. | Open |
| 315 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387880 | Junction 87880 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52882-2 at junction 87880 so both are connected. | Open |
| 316 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387882 | Junction 87882 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52882-2 at junction 87882 so both are connected. | Open |
| 317 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387884 | Junction 87884 (degree 2) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 52882-2 at junction 87884 so both are connected. | Open |
| 318 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387886 | Junction 87886 (degree 2) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 52882-2 at junction 87886 so both are connected. | Open |
| 319 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387889 | Junction 87889 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52882-2 at junction 87889 so both are connected. | Open |
| 320 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387892 | Junction 87892 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52882-2 at junction 87892 so both are connected. | Open |
| 321 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387894 | Junction 87894 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52882-2 at junction 87894 so both are connected. | Open |
| 322 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387896 | Junction 87896 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52882-2 at junction 87896 so both are connected. | Open |
| 323 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387898 | Junction 87898 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52882-2 at junction 87898 so both are connected. | Open |
| 324 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387900 | Junction 87900 (degree 2) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (17 m). → Split pipe 52882-2 at junction 87900 so both are connected. | Open |
| 325 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387902 | Junction 87902 (degree 2) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (17 m). → Split pipe 52882-2 at junction 87902 so both are connected. | Open |
| 326 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387904 | Junction 87904 (degree 1) lies on pipe 52882-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52882-2 at junction 87904 so both are connected. | Open |
| 327 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387908 | Junction 87908 (degree 1) lies on pipe 52883 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52883 at junction 87908 so both are connected. | Open |
| 328 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387910 | Junction 87910 (degree 1) lies on pipe 52883 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52883 at junction 87910 so both are connected. | Open |
| 329 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387912 | Junction 87912 (degree 1) lies on pipe 52883 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 52883 at junction 87912 so both are connected. | Open |
| 330 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387914 | Junction 87914 (degree 1) lies on pipe 52884 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52884 at junction 87914 so both are connected. | Open |
| 331 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387916 | Junction 87916 (degree 1) lies on pipe 52884 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52884 at junction 87916 so both are connected. | Open |
| 332 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387918 | Junction 87918 (degree 1) lies on pipe 52884 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52884 at junction 87918 so both are connected. | Open |
| 333 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387920 | Junction 87920 (degree 1) lies on pipe 52884 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52884 at junction 87920 so both are connected. | Open |
| 334 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387922 | Junction 87922 (degree 1) lies on pipe 52884 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52884 at junction 87922 so both are connected. | Open |
| 335 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387924 | Junction 87924 (degree 2) lies on pipe 52879 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (18 m). → Split pipe 52879 at junction 87924 so both are connected. | Open |
| 336 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387926 | Junction 87926 (degree 2) lies on pipe 52879 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 52879 at junction 87926 so both are connected. | Open |
| 337 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387928 | Junction 87928 (degree 1) lies on pipe 52879 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52879 at junction 87928 so both are connected. | Open |
| 338 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387940 | Junction 87940 (degree 1) lies on pipe 52885 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52885 at junction 87940 so both are connected. | Open |
| 339 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387942 | Junction 87942 (degree 1) lies on pipe 52885 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52885 at junction 87942 so both are connected. | Open |
| 340 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387944 | Junction 87944 (degree 1) lies on pipe 52885 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52885 at junction 87944 so both are connected. | Open |
| 341 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387948 | Junction 87948 (degree 2) lies on pipe 52886-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (12 m). → Split pipe 52886-2 at junction 87948 so both are connected. | Open |
| 342 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387950 | Junction 87950 (degree 2) lies on pipe 52886-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (15 m). → Split pipe 52886-2 at junction 87950 so both are connected. | Open |
| 343 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387952 | Junction 87952 (degree 2) lies on pipe 52886-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (14 m). → Split pipe 52886-2 at junction 87952 so both are connected. | Open |
| 344 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387954 | Junction 87954 (degree 1) lies on pipe 52886-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52886-2 at junction 87954 so both are connected. | Open |
| 345 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387956 | Junction 87956 (degree 1) lies on pipe 52886-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52886-2 at junction 87956 so both are connected. | Open |
| 346 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387958 | Junction 87958 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52887 at junction 87958 so both are connected. | Open |
| 347 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387960 | Junction 87960 (degree 2) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (16 m). → Split pipe 52887 at junction 87960 so both are connected. | Open |
| 348 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387962 | Junction 87962 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52887 at junction 87962 so both are connected. | Open |
| 349 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387964 | Junction 87964 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52887 at junction 87964 so both are connected. | Open |
| 350 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387980 | Junction 87980 (degree 1) lies on pipe 52885 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52885 at junction 87980 so both are connected. | Open |
| 351 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387982 | Junction 87982 (degree 1) lies on pipe 52885 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52885 at junction 87982 so both are connected. | Open |
| 352 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387984 | Junction 87984 (degree 1) lies on pipe 52886-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52886-1 at junction 87984 so both are connected. | Open |
| 353 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387986 | Junction 87986 (degree 1) lies on pipe 52886-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52886-2 at junction 87986 so both are connected. | Open |
| 354 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387990 | Junction 87990 (degree 1) lies on pipe 52886-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52886-2 at junction 87990 so both are connected. | Open |
| 355 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387993 | Junction 87993 (degree 1) lies on pipe 52886-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52886-2 at junction 87993 so both are connected. | Open |
| 356 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387995 | Junction 87995 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52887 at junction 87995 so both are connected. | Open |
| 357 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387997 | Junction 87997 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52887 at junction 87997 so both are connected. | Open |
| 358 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387999 | Junction 87999 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52887 at junction 87999 so both are connected. | Open |
| 359 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388001 | Junction 88001 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52887 at junction 88001 so both are connected. | Open |
| 360 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388003 | Junction 88003 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52887 at junction 88003 so both are connected. | Open |
| 361 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388006 | Junction 88006 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52887 at junction 88006 so both are connected. | Open |
| 362 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388008 | Junction 88008 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52887 at junction 88008 so both are connected. | Open |
| 363 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388012 | Junction 88012 (degree 2) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 56492 at junction 88012 so both are connected. | Open |
| 364 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388015 | Junction 88015 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56492 at junction 88015 so both are connected. | Open |
| 365 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388017 | Junction 88017 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56492 at junction 88017 so both are connected. | Open |
| 366 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388019 | Junction 88019 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56492 at junction 88019 so both are connected. | Open |
| 367 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388021 | Junction 88021 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56492 at junction 88021 so both are connected. | Open |
| 368 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388023 | Junction 88023 (degree 2) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 56492 at junction 88023 so both are connected. | Open |
| 369 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388026 | Junction 88026 (degree 2) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (18 m). → Split pipe 56492 at junction 88026 so both are connected. | Open |
| 370 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388029 | Junction 88029 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56492 at junction 88029 so both are connected. | Open |
| 371 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388031 | Junction 88031 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56492 at junction 88031 so both are connected. | Open |
| 372 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388033 | Junction 88033 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56492 at junction 88033 so both are connected. | Open |
| 373 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388035 | Junction 88035 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56492 at junction 88035 so both are connected. | Open |
| 374 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388037 | Junction 88037 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56492 at junction 88037 so both are connected. | Open |
| 375 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388039 | Junction 88039 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56492 at junction 88039 so both are connected. | Open |
| 376 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388041 | Junction 88041 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56492 at junction 88041 so both are connected. | Open |
| 377 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388043 | Junction 88043 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56492 at junction 88043 so both are connected. | Open |
| 378 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388045 | Junction 88045 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56492 at junction 88045 so both are connected. | Open |
| 379 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388047 | Junction 88047 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56492 at junction 88047 so both are connected. | Open |
| 380 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388051 | Junction 88051 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53728 at junction 88051 so both are connected. | Open |
| 381 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388053 | Junction 88053 (degree 2) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 53728 at junction 88053 so both are connected. | Open |
| 382 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388055 | Junction 88055 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53728 at junction 88055 so both are connected. | Open |
| 383 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388057 | Junction 88057 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53728 at junction 88057 so both are connected. | Open |
| 384 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388059 | Junction 88059 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53728 at junction 88059 so both are connected. | Open |
| 385 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388061 | Junction 88061 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53728 at junction 88061 so both are connected. | Open |
| 386 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388063 | Junction 88063 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53728 at junction 88063 so both are connected. | Open |
| 387 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388065 | Junction 88065 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 53728 at junction 88065 so both are connected. | Open |
| 388 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388067 | Junction 88067 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 53728 at junction 88067 so both are connected. | Open |
| 389 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388069 | Junction 88069 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 53728 at junction 88069 so both are connected. | Open |
| 390 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388071 | Junction 88071 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53728 at junction 88071 so both are connected. | Open |
| 391 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388074 | Junction 88074 (degree 1) lies on pipe 53728 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53728 at junction 88074 so both are connected. | Open |
| 392 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388076 | Junction 88076 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52899 at junction 88076 so both are connected. | Open |
| 393 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388078 | Junction 88078 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52899 at junction 88078 so both are connected. | Open |
| 394 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388080 | Junction 88080 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52899 at junction 88080 so both are connected. | Open |
| 395 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388082 | Junction 88082 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52899 at junction 88082 so both are connected. | Open |
| 396 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388084 | Junction 88084 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52899 at junction 88084 so both are connected. | Open |
| 397 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388086 | Junction 88086 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52899 at junction 88086 so both are connected. | Open |
| 398 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388088 | Junction 88088 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52899 at junction 88088 so both are connected. | Open |
| 399 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388090 | Junction 88090 (degree 1) lies on pipe 52889 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52889 at junction 88090 so both are connected. | Open |
| 400 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388092 | Junction 88092 (degree 1) lies on pipe 52910-4 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52910-4 at junction 88092 so both are connected. | Open |
| 401 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388094 | Junction 88094 (degree 1) lies on pipe 52889 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52889 at junction 88094 so both are connected. | Open |
| 402 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388098 | Junction 88098 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52899 at junction 88098 so both are connected. | Open |
| 403 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388100 | Junction 88100 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52899 at junction 88100 so both are connected. | Open |
| 404 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388102 | Junction 88102 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52899 at junction 88102 so both are connected. | Open |
| 405 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388104 | Junction 88104 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52899 at junction 88104 so both are connected. | Open |
| 406 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388106 | Junction 88106 (degree 1) lies on pipe 52899 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52899 at junction 88106 so both are connected. | Open |
| 407 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388108 | Junction 88108 (degree 1) lies on pipe 52889 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52889 at junction 88108 so both are connected. | Open |
| 408 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388110 | Junction 88110 (degree 1) lies on pipe 52910-4 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52910-4 at junction 88110 so both are connected. | Open |
| 409 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388112 | Junction 88112 (degree 1) lies on pipe 52910-3 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52910-3 at junction 88112 so both are connected. | Open |
| 410 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388114 | Junction 88114 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89616 at junction 88114 so both are connected. | Open |
| 411 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388116 | Junction 88116 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89616 at junction 88116 so both are connected. | Open |
| 412 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388118 | Junction 88118 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89616 at junction 88118 so both are connected. | Open |
| 413 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388120 | Junction 88120 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 89616 at junction 88120 so both are connected. | Open |
| 414 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388165 | Junction 88165 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52978-2 at junction 88165 so both are connected. | Open |
| 415 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388167 | Junction 88167 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52978-2 at junction 88167 so both are connected. | Open |
| 416 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388170 | Junction 88170 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52978-2 at junction 88170 so both are connected. | Open |
| 417 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388171 | Junction 88171 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52978-2 at junction 88171 so both are connected. | Open |
| 418 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388174 | Junction 88174 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 52978-2 at junction 88174 so both are connected. | Open |
| 419 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388176 | Junction 88176 (degree 1) lies on pipe 56468-1 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-1 at junction 88176 so both are connected. | Open |
| 420 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388178 | Junction 88178 (degree 1) lies on pipe 56468-1 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-1 at junction 88178 so both are connected. | Open |
| 421 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038818 | Junction 8818 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 89522-1 at junction 8818 so both are connected. | Open |
| 422 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388180 | Junction 88180 (degree 1) lies on pipe 56468-1 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56468-1 at junction 88180 so both are connected. | Open |
| 423 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388184 | Junction 88184 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (17 m). → Split pipe 56468-2 at junction 88184 so both are connected. | Open |
| 424 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388186 | Junction 88186 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-2 at junction 88186 so both are connected. | Open |
| 425 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388188 | Junction 88188 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56468-2 at junction 88188 so both are connected. | Open |
| 426 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388190 | Junction 88190 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-2 at junction 88190 so both are connected. | Open |
| 427 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388192 | Junction 88192 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56468-2 at junction 88192 so both are connected. | Open |
| 428 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388194 | Junction 88194 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56468-2 at junction 88194 so both are connected. | Open |
| 429 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388196 | Junction 88196 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56468-2 at junction 88196 so both are connected. | Open |
| 430 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388198 | Junction 88198 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (13 m). → Split pipe 56468-2 at junction 88198 so both are connected. | Open |
| 431 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388200 | Junction 88200 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-2 at junction 88200 so both are connected. | Open |
| 432 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388202 | Junction 88202 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56468-2 at junction 88202 so both are connected. | Open |
| 433 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388204 | Junction 88204 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (13 m). → Split pipe 56468-2 at junction 88204 so both are connected. | Open |
| 434 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388206 | Junction 88206 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (13 m). → Split pipe 56468-2 at junction 88206 so both are connected. | Open |
| 435 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388208 | Junction 88208 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (16 m). → Split pipe 56468-2 at junction 88208 so both are connected. | Open |
| 436 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038821 | Junction 8821 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 89522-1 at junction 8821 so both are connected. | Open |
| 437 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388210 | Junction 88210 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-2 at junction 88210 so both are connected. | Open |
| 438 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388213 | Junction 88213 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-2 at junction 88213 so both are connected. | Open |
| 439 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388215 | Junction 88215 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-2 at junction 88215 so both are connected. | Open |
| 440 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388217 | Junction 88217 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56468-2 at junction 88217 so both are connected. | Open |
| 441 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388219 | Junction 88219 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-2 at junction 88219 so both are connected. | Open |
| 442 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038822 | Junction 8822 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 89522-1 at junction 8822 so both are connected. | Open |
| 443 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388222 | Junction 88222 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56468-2 at junction 88222 so both are connected. | Open |
| 444 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388224 | Junction 88224 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-2 at junction 88224 so both are connected. | Open |
| 445 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388229 | Junction 88229 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56468-2 at junction 88229 so both are connected. | Open |
| 446 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038823 | Junction 8823 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89522-1 at junction 8823 so both are connected. | Open |
| 447 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388231 | Junction 88231 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-2 at junction 88231 so both are connected. | Open |
| 448 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388233 | Junction 88233 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-2 at junction 88233 so both are connected. | Open |
| 449 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388235 | Junction 88235 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56468-2 at junction 88235 so both are connected. | Open |
| 450 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388237 | Junction 88237 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (13 m). → Split pipe 56468-2 at junction 88237 so both are connected. | Open |
| 451 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388239 | Junction 88239 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (15 m). → Split pipe 56468-2 at junction 88239 so both are connected. | Open |
| 452 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038824 | Junction 8824 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 89522-1 at junction 8824 so both are connected. | Open |
| 453 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388241 | Junction 88241 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56468-2 at junction 88241 so both are connected. | Open |
| 454 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388243 | Junction 88243 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-2 at junction 88243 so both are connected. | Open |
| 455 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388245 | Junction 88245 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 56468-2 at junction 88245 so both are connected. | Open |
| 456 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388247 | Junction 88247 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56468-2 at junction 88247 so both are connected. | Open |
| 457 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388249 | Junction 88249 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56468-2 at junction 88249 so both are connected. | Open |
| 458 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038825 | Junction 8825 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 89522-1 at junction 8825 so both are connected. | Open |
| 459 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388251 | Junction 88251 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-2 at junction 88251 so both are connected. | Open |
| 460 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388253 | Junction 88253 (degree 2) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (16 m). → Split pipe 56468-2 at junction 88253 so both are connected. | Open |
| 461 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388255 | Junction 88255 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56468-2 at junction 88255 so both are connected. | Open |
| 462 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388257 | Junction 88257 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56468-2 at junction 88257 so both are connected. | Open |
| 463 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388259 | Junction 88259 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56468-2 at junction 88259 so both are connected. | Open |
| 464 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038826 | Junction 8826 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 89522-1 at junction 8826 so both are connected. | Open |
| 465 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388261 | Junction 88261 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-2 at junction 88261 so both are connected. | Open |
| 466 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388263 | Junction 88263 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56468-2 at junction 88263 so both are connected. | Open |
| 467 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388266 | Junction 88266 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-2 at junction 88266 so both are connected. | Open |
| 468 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388268 | Junction 88268 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56468-2 at junction 88268 so both are connected. | Open |
| 469 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388270 | Junction 88270 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56468-2 at junction 88270 so both are connected. | Open |
| 470 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388272 | Junction 88272 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56468-2 at junction 88272 so both are connected. | Open |
| 471 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388275 | Junction 88275 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56468-2 at junction 88275 so both are connected. | Open |
| 472 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388279 | Junction 88279 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56468-2 at junction 88279 so both are connected. | Open |
| 473 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038828 | Junction 8828 (degree 1) lies on pipe 89522-2 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89522-2 at junction 8828 so both are connected. | Open |
| 474 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388281 | Junction 88281 (degree 1) lies on pipe 56468-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56468-2 at junction 88281 so both are connected. | Open |
| 475 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388283 | Junction 88283 (degree 1) lies on pipe 52863 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52863 at junction 88283 so both are connected. | Open |
| 476 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388285 | Junction 88285 (degree 2) lies on pipe 56474-1 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (12 m). → Split pipe 56474-1 at junction 88285 so both are connected. | Open |
| 477 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388287 | Junction 88287 (degree 1) lies on pipe 56474-1 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56474-1 at junction 88287 so both are connected. | Open |
| 478 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388289 | Junction 88289 (degree 1) lies on pipe 56474-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56474-2 at junction 88289 so both are connected. | Open |
| 479 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038829 | Junction 8829 (degree 1) lies on pipe 89522-1 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89522-1 at junction 8829 so both are connected. | Open |
| 480 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388291 | Junction 88291 (degree 1) lies on pipe 56474-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56474-2 at junction 88291 so both are connected. | Open |
| 481 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388293 | Junction 88293 (degree 2) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (16 m). → Split pipe 56473 at junction 88293 so both are connected. | Open |
| 482 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388295 | Junction 88295 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56473 at junction 88295 so both are connected. | Open |
| 483 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388297 | Junction 88297 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56473 at junction 88297 so both are connected. | Open |
| 484 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388299 | Junction 88299 (degree 1) lies on pipe 52862 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52862 at junction 88299 so both are connected. | Open |
| 485 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038830 | Junction 8830 (degree 1) lies on pipe 89522-3 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 89522-3 at junction 8830 so both are connected. | Open |
| 486 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388301 | Junction 88301 (degree 1) lies on pipe 52862 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52862 at junction 88301 so both are connected. | Open |
| 487 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388303 | Junction 88303 (degree 1) lies on pipe 52862 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52862 at junction 88303 so both are connected. | Open |
| 488 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388306 | Junction 88306 (degree 1) lies on pipe 56474-1 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56474-1 at junction 88306 so both are connected. | Open |
| 489 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388308 | Junction 88308 (degree 1) lies on pipe 56474-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56474-2 at junction 88308 so both are connected. | Open |
| 490 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388310 | Junction 88310 (degree 1) lies on pipe 56474-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56474-2 at junction 88310 so both are connected. | Open |
| 491 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388312 | Junction 88312 (degree 1) lies on pipe 56474-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56474-2 at junction 88312 so both are connected. | Open |
| 492 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388314 | Junction 88314 (degree 1) lies on pipe 56474-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56474-2 at junction 88314 so both are connected. | Open |
| 493 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388316 | Junction 88316 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56473 at junction 88316 so both are connected. | Open |
| 494 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388318 | Junction 88318 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56473 at junction 88318 so both are connected. | Open |
| 495 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388320 | Junction 88320 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56473 at junction 88320 so both are connected. | Open |
| 496 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388323 | Junction 88323 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56473 at junction 88323 so both are connected. | Open |
| 497 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388325 | Junction 88325 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56473 at junction 88325 so both are connected. | Open |
| 498 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038833 | Junction 8833 (degree 1) lies on pipe 89522-3 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 89522-3 at junction 8833 so both are connected. | Open |
| 499 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038834 | Junction 8834 (degree 1) lies on pipe 89522-3 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89522-3 at junction 8834 so both are connected. | Open |
| 500 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038835 | Junction 8835 (degree 1) lies on pipe 89522-3 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 89522-3 at junction 8835 so both are connected. | Open |
| 501 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038840 | Junction 8840 (degree 1) lies on pipe 53721 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 12 pipe(s) (322 m). → Split pipe 53721 at junction 8840 so both are connected. | Open |
| 502 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388525 | Junction 88525 (degree 1) lies on pipe 53720 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53720 at junction 88525 so both are connected. | Open |
| 503 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388527 | Junction 88527 (degree 2) lies on pipe 53720 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 53720 at junction 88527 so both are connected. | Open |
| 504 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388529 | Junction 88529 (degree 1) lies on pipe 53720 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53720 at junction 88529 so both are connected. | Open |
| 505 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388531 | Junction 88531 (degree 1) lies on pipe 53720 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53720 at junction 88531 so both are connected. | Open |
| 506 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388533 | Junction 88533 (degree 1) lies on pipe 53720 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53720 at junction 88533 so both are connected. | Open |
| 507 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388535 | Junction 88535 (degree 1) lies on pipe 53721 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53721 at junction 88535 so both are connected. | Open |
| 508 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388537 | Junction 88537 (degree 1) lies on pipe 53721 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53721 at junction 88537 so both are connected. | Open |
| 509 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388539 | Junction 88539 (degree 1) lies on pipe 53723 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53723 at junction 88539 so both are connected. | Open |
| 510 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388541 | Junction 88541 (degree 1) lies on pipe 53723 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53723 at junction 88541 so both are connected. | Open |
| 511 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388543 | Junction 88543 (degree 1) lies on pipe 53724 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 53724 at junction 88543 so both are connected. | Open |
| 512 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388545 | Junction 88545 (degree 1) lies on pipe 53724 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53724 at junction 88545 so both are connected. | Open |
| 513 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388547 | Junction 88547 (degree 1) lies on pipe 53724 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53724 at junction 88547 so both are connected. | Open |
| 514 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388549 | Junction 88549 (degree 1) lies on pipe 53724 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53724 at junction 88549 so both are connected. | Open |
| 515 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388551 | Junction 88551 (degree 1) lies on pipe 53724 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53724 at junction 88551 so both are connected. | Open |
| 516 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388553 | Junction 88553 (degree 1) lies on pipe 53724 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53724 at junction 88553 so both are connected. | Open |
| 517 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388555 | Junction 88555 (degree 1) lies on pipe 53723 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 53723 at junction 88555 so both are connected. | Open |
| 518 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388557 | Junction 88557 (degree 1) lies on pipe 53723 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53723 at junction 88557 so both are connected. | Open |
| 519 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388559 | Junction 88559 (degree 1) lies on pipe 53722 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53722 at junction 88559 so both are connected. | Open |
| 520 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388561 | Junction 88561 (degree 1) lies on pipe 53722 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53722 at junction 88561 so both are connected. | Open |
| 521 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388563 | Junction 88563 (degree 1) lies on pipe 53721 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53721 at junction 88563 so both are connected. | Open |
| 522 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388565 | Junction 88565 (degree 1) lies on pipe 53721 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53721 at junction 88565 so both are connected. | Open |
| 523 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388567 | Junction 88567 (degree 1) lies on pipe 53720 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53720 at junction 88567 so both are connected. | Open |
| 524 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388569 | Junction 88569 (degree 1) lies on pipe 53720 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 53720 at junction 88569 so both are connected. | Open |
| 525 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388572 | Junction 88572 (degree 1) lies on pipe 53720 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53720 at junction 88572 so both are connected. | Open |
| 526 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388576 | Junction 88576 (degree 2) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (11 m). → Split pipe 56525-4 at junction 88576 so both are connected. | Open |
| 527 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388578 | Junction 88578 (degree 1) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56525-4 at junction 88578 so both are connected. | Open |
| 528 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388584 | Junction 88584 (degree 1) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56525-4 at junction 88584 so both are connected. | Open |
| 529 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388586 | Junction 88586 (degree 1) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56525-4 at junction 88586 so both are connected. | Open |
| 530 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388588 | Junction 88588 (degree 1) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56525-4 at junction 88588 so both are connected. | Open |
| 531 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388590 | Junction 88590 (degree 1) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56525-4 at junction 88590 so both are connected. | Open |
| 532 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388592 | Junction 88592 (degree 1) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56525-4 at junction 88592 so both are connected. | Open |
| 533 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388594 | Junction 88594 (degree 1) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56525-4 at junction 88594 so both are connected. | Open |
| 534 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388597 | Junction 88597 (degree 1) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56525-4 at junction 88597 so both are connected. | Open |
| 535 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388621 | Junction 88621 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53725 at junction 88621 so both are connected. | Open |
| 536 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388623 | Junction 88623 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 53725 at junction 88623 so both are connected. | Open |
| 537 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388625 | Junction 88625 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53725 at junction 88625 so both are connected. | Open |
| 538 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388627 | Junction 88627 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53725 at junction 88627 so both are connected. | Open |
| 539 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388629 | Junction 88629 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53725 at junction 88629 so both are connected. | Open |
| 540 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388631 | Junction 88631 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53725 at junction 88631 so both are connected. | Open |
| 541 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388633 | Junction 88633 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 53725 at junction 88633 so both are connected. | Open |
| 542 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388635 | Junction 88635 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53725 at junction 88635 so both are connected. | Open |
| 543 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388637 | Junction 88637 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 53725 at junction 88637 so both are connected. | Open |
| 544 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388639 | Junction 88639 (degree 1) lies on pipe 53725 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 53725 at junction 88639 so both are connected. | Open |
| 545 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388641 | Junction 88641 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89933 at junction 88641 so both are connected. | Open |
| 546 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388643 | Junction 88643 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89933 at junction 88643 so both are connected. | Open |
| 547 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388645 | Junction 88645 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 89933 at junction 88645 so both are connected. | Open |
| 548 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388647 | Junction 88647 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (45 m). → Split pipe 89933 at junction 88647 so both are connected. | Open |
| 549 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388649 | Junction 88649 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89933 at junction 88649 so both are connected. | Open |
| 550 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388651 | Junction 88651 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89933 at junction 88651 so both are connected. | Open |
| 551 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388653 | Junction 88653 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89933 at junction 88653 so both are connected. | Open |
| 552 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388655 | Junction 88655 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89933 at junction 88655 so both are connected. | Open |
| 553 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388657 | Junction 88657 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 89933 at junction 88657 so both are connected. | Open |
| 554 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388659 | Junction 88659 (degree 1) lies on pipe 89933 (DN 50, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 89933 at junction 88659 so both are connected. | Open |
| 555 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388681 | Junction 88681 (degree 1) lies on pipe 52864 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52864 at junction 88681 so both are connected. | Open |
| 556 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388683 | Junction 88683 (degree 1) lies on pipe 52864 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52864 at junction 88683 so both are connected. | Open |
| 557 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388685 | Junction 88685 (degree 1) lies on pipe 52864 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52864 at junction 88685 so both are connected. | Open |
| 558 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388687 | Junction 88687 (degree 1) lies on pipe 52864 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52864 at junction 88687 so both are connected. | Open |
| 559 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388689 | Junction 88689 (degree 1) lies on pipe 52864 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52864 at junction 88689 so both are connected. | Open |
| 560 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388691 | Junction 88691 (degree 1) lies on pipe 52864 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52864 at junction 88691 so both are connected. | Open |
| 561 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388693 | Junction 88693 (degree 1) lies on pipe 52864 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52864 at junction 88693 so both are connected. | Open |
| 562 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388695 | Junction 88695 (degree 1) lies on pipe 52864 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52864 at junction 88695 so both are connected. | Open |
| 563 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388799 | Junction 88799 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56469 at junction 88799 so both are connected. | Open |
| 564 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388801 | Junction 88801 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 56469 at junction 88801 so both are connected. | Open |
| 565 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388803 | Junction 88803 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56469 at junction 88803 so both are connected. | Open |
| 566 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388805 | Junction 88805 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56469 at junction 88805 so both are connected. | Open |
| 567 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388807 | Junction 88807 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56469 at junction 88807 so both are connected. | Open |
| 568 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388809 | Junction 88809 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56469 at junction 88809 so both are connected. | Open |
| 569 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388811 | Junction 88811 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56469 at junction 88811 so both are connected. | Open |
| 570 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388813 | Junction 88813 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56469 at junction 88813 so both are connected. | Open |
| 571 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388815 | Junction 88815 (degree 1) lies on pipe 56470-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56470-1 at junction 88815 so both are connected. | Open |
| 572 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388817 | Junction 88817 (degree 2) lies on pipe 56470-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (14 m). → Split pipe 56470-2 at junction 88817 so both are connected. | Open |
| 573 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388819 | Junction 88819 (degree 1) lies on pipe 56470-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56470-2 at junction 88819 so both are connected. | Open |
| 574 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388823 | Junction 88823 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56470-3 at junction 88823 so both are connected. | Open |
| 575 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388825 | Junction 88825 (degree 2) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 56470-3 at junction 88825 so both are connected. | Open |
| 576 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388827 | Junction 88827 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56470-3 at junction 88827 so both are connected. | Open |
| 577 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388829 | Junction 88829 (degree 1) lies on pipe 56470-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56470-1 at junction 88829 so both are connected. | Open |
| 578 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388834 | Junction 88834 (degree 1) lies on pipe 56470-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56470-2 at junction 88834 so both are connected. | Open |
| 579 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388836 | Junction 88836 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56470-3 at junction 88836 so both are connected. | Open |
| 580 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388838 | Junction 88838 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56470-3 at junction 88838 so both are connected. | Open |
| 581 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388840 | Junction 88840 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56470-3 at junction 88840 so both are connected. | Open |
| 582 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388842 | Junction 88842 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 56470-3 at junction 88842 so both are connected. | Open |
| 583 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388844 | Junction 88844 (degree 2) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (13 m). → Split pipe 56482 at junction 88844 so both are connected. | Open |
| 584 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388846 | Junction 88846 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (25 m). → Split pipe 56482 at junction 88846 so both are connected. | Open |
| 585 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388848 | Junction 88848 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56482 at junction 88848 so both are connected. | Open |
| 586 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388850 | Junction 88850 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56482 at junction 88850 so both are connected. | Open |
| 587 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388852 | Junction 88852 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56482 at junction 88852 so both are connected. | Open |
| 588 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388854 | Junction 88854 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56482 at junction 88854 so both are connected. | Open |
| 589 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388856 | Junction 88856 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56482 at junction 88856 so both are connected. | Open |
| 590 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388858 | Junction 88858 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56482 at junction 88858 so both are connected. | Open |
| 591 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388860 | Junction 88860 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56482 at junction 88860 so both are connected. | Open |
| 592 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388862 | Junction 88862 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56482 at junction 88862 so both are connected. | Open |
| 593 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388865 | Junction 88865 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56482 at junction 88865 so both are connected. | Open |
| 594 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388867 | Junction 88867 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56482 at junction 88867 so both are connected. | Open |
| 595 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388869 | Junction 88869 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56482 at junction 88869 so both are connected. | Open |
| 596 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388871 | Junction 88871 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56482 at junction 88871 so both are connected. | Open |
| 597 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388873 | Junction 88873 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56482 at junction 88873 so both are connected. | Open |
| 598 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388875 | Junction 88875 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56482 at junction 88875 so both are connected. | Open |
| 599 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388930 | Junction 88930 (degree 1) lies on pipe 52905-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52905-2 at junction 88930 so both are connected. | Open |
| 600 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388932 | Junction 88932 (degree 1) lies on pipe 52905-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52905-1 at junction 88932 so both are connected. | Open |
| 601 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388934 | Junction 88934 (degree 1) lies on pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52904 at junction 88934 so both are connected. | Open |
| 602 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388936 | Junction 88936 (degree 1) lies on pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52904 at junction 88936 so both are connected. | Open |
| 603 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388938 | Junction 88938 (degree 1) lies on pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52904 at junction 88938 so both are connected. | Open |
| 604 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388940 | Junction 88940 (degree 1) lies on pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52904 at junction 88940 so both are connected. | Open |
| 605 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388942 | Junction 88942 (degree 1) lies on pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52904 at junction 88942 so both are connected. | Open |
| 606 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388950 | Junction 88950 (degree 1) lies on pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52904 at junction 88950 so both are connected. | Open |
| 607 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388952 | Junction 88952 (degree 1) lies on pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52904 at junction 88952 so both are connected. | Open |
| 608 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389028 | Junction 89028 (degree 1) lies on pipe 53505 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53505 at junction 89028 so both are connected. | Open |
| 609 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389030 | Junction 89030 (degree 1) lies on pipe 53505 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 53505 at junction 89030 so both are connected. | Open |
| 610 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389032 | Junction 89032 (degree 1) lies on pipe 53505 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 53505 at junction 89032 so both are connected. | Open |
| 611 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389034 | Junction 89034 (degree 1) lies on pipe 53505 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53505 at junction 89034 so both are connected. | Open |
| 612 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389050 | Junction 89050 (degree 1) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52881 at junction 89050 so both are connected. | Open |
| 613 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389052 | Junction 89052 (degree 1) lies on pipe 52881 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 52881 at junction 89052 so both are connected. | Open |
| 614 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389056 | Junction 89056 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52877 at junction 89056 so both are connected. | Open |
| 615 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389058 | Junction 89058 (degree 1) lies on pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52877 at junction 89058 so both are connected. | Open |
| 616 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389061 | Junction 89061 (degree 1) lies on pipe 53731 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 53731 at junction 89061 so both are connected. | Open |
| 617 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389063 | Junction 89063 (degree 1) lies on pipe 53730-2 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (32 m). → Split pipe 53730-2 at junction 89063 so both are connected. | Open |
| 618 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389065 | Junction 89065 (degree 1) lies on pipe 53730-1 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53730-1 at junction 89065 so both are connected. | Open |
| 619 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389078 | Junction 89078 (degree 1) lies on pipe 56526-3 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 56526-3 at junction 89078 so both are connected. | Open |
| 620 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389080 | Junction 89080 (degree 1) lies on pipe 56526-3 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (34 m). → Split pipe 56526-3 at junction 89080 so both are connected. | Open |
| 621 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389096 | Junction 89096 (degree 1) lies on pipe 56447 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 56447 at junction 89096 so both are connected. | Open |
| 622 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389100 | Junction 89100 (degree 1) lies on pipe 56447 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 56447 at junction 89100 so both are connected. | Open |
| 623 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389102 | Junction 89102 (degree 1) lies on pipe 56466 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56466 at junction 89102 so both are connected. | Open |
| 624 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389106 | Junction 89106 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56412 at junction 89106 so both are connected. | Open |
| 625 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389108 | Junction 89108 (degree 1) lies on pipe 52882-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 52882-1 at junction 89108 so both are connected. | Open |
| 626 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389110 | Junction 89110 (degree 1) lies on pipe 52884 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52884 at junction 89110 so both are connected. | Open |
| 627 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389112 | Junction 89112 (degree 1) lies on pipe 52884 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52884 at junction 89112 so both are connected. | Open |
| 628 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389116 | Junction 89116 (degree 1) lies on pipe 52879 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 52879 at junction 89116 so both are connected. | Open |
| 629 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389118 | Junction 89118 (degree 1) lies on pipe 52879 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 52879 at junction 89118 so both are connected. | Open |
| 630 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389120 | Junction 89120 (degree 1) lies on pipe 56551 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56551 at junction 89120 so both are connected. | Open |
| 631 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389122 | Junction 89122 (degree 1) lies on pipe 56551 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56551 at junction 89122 so both are connected. | Open |
| 632 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389124 | Junction 89124 (degree 1) lies on pipe 52879 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52879 at junction 89124 so both are connected. | Open |
| 633 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389126 | Junction 89126 (degree 1) lies on pipe 52879 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52879 at junction 89126 so both are connected. | Open |
| 634 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389128 | Junction 89128 (degree 1) lies on pipe 53727 (DN 32, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 53727 at junction 89128 so both are connected. | Open |
| 635 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389130 | Junction 89130 (degree 1) lies on pipe 53727 (DN 32, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 53727 at junction 89130 so both are connected. | Open |
| 636 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389132 | Junction 89132 (degree 1) lies on pipe 53727 (DN 32, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 53727 at junction 89132 so both are connected. | Open |
| 637 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389134 | Junction 89134 (degree 1) lies on pipe 53727 (DN 32, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 53727 at junction 89134 so both are connected. | Open |
| 638 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389136 | Junction 89136 (degree 1) lies on pipe 52888 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52888 at junction 89136 so both are connected. | Open |
| 639 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389150 | Junction 89150 (degree 1) lies on pipe 53701 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 53701 at junction 89150 so both are connected. | Open |
| 640 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389152 | Junction 89152 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56492 at junction 89152 so both are connected. | Open |
| 641 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389154 | Junction 89154 (degree 1) lies on pipe 56492 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (25 m). → Split pipe 56492 at junction 89154 so both are connected. | Open |
| 642 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389158 | Junction 89158 (degree 1) lies on pipe 56464 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (66 m). → Split pipe 56464 at junction 89158 so both are connected. | Open |
| 643 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389160 | Junction 89160 (degree 2) lies on pipe 56411 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (40 m). → Split pipe 56411 at junction 89160 so both are connected. | Open |
| 644 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389162 | Junction 89162 (degree 1) lies on pipe 56411 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (31 m). → Split pipe 56411 at junction 89162 so both are connected. | Open |
| 645 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389164 | Junction 89164 (degree 2) lies on pipe 56411 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (44 m). → Split pipe 56411 at junction 89164 so both are connected. | Open |
| 646 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389166 | Junction 89166 (degree 1) lies on pipe 56412 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56412 at junction 89166 so both are connected. | Open |
| 647 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389172 | Junction 89172 (degree 1) lies on pipe 52873-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52873-2 at junction 89172 so both are connected. | Open |
| 648 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389182 | Junction 89182 (degree 1) lies on pipe 56493-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56493-2 at junction 89182 so both are connected. | Open |
| 649 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389186 | Junction 89186 (degree 1) lies on pipe 89718-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 89718-2 at junction 89186 so both are connected. | Open |
| 650 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389188 | Junction 89188 (degree 1) lies on pipe 89718-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 89718-2 at junction 89188 so both are connected. | Open |
| 651 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389190 | Junction 89190 (degree 1) lies on pipe 89718-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 89718-2 at junction 89190 so both are connected. | Open |
| 652 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389192 | Junction 89192 (degree 1) lies on pipe 89718-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 89718-2 at junction 89192 so both are connected. | Open |
| 653 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389194 | Junction 89194 (degree 1) lies on pipe 52910-3 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52910-3 at junction 89194 so both are connected. | Open |
| 654 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389198 | Junction 89198 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89616 at junction 89198 so both are connected. | Open |
| 655 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389208 | Junction 89208 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52978-2 at junction 89208 so both are connected. | Open |
| 656 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389210 | Junction 89210 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52978-2 at junction 89210 so both are connected. | Open |
| 657 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389212 | Junction 89212 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52978-2 at junction 89212 so both are connected. | Open |
| 658 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389214 | Junction 89214 (degree 1) lies on pipe 52978-2 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52978-2 at junction 89214 so both are connected. | Open |
| 659 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389216 | Junction 89216 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56557 at junction 89216 so both are connected. | Open |
| 660 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389220 | Junction 89220 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56473 at junction 89220 so both are connected. | Open |
| 661 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389222 | Junction 89222 (degree 1) lies on pipe 56473 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56473 at junction 89222 so both are connected. | Open |
| 662 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389253 | Junction 89253 (degree 2) lies on pipe 56525-4 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 56525-4 at junction 89253 so both are connected. | Open |
| 663 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389274 | Junction 89274 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (28 m). → Split pipe 56469 at junction 89274 so both are connected. | Open |
| 664 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389276 | Junction 89276 (degree 1) lies on pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56469 at junction 89276 so both are connected. | Open |
| 665 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389278 | Junction 89278 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56470-3 at junction 89278 so both are connected. | Open |
| 666 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389280 | Junction 89280 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 56470-3 at junction 89280 so both are connected. | Open |
| 667 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389282 | Junction 89282 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 56470-3 at junction 89282 so both are connected. | Open |
| 668 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389285 | Junction 89285 (degree 1) lies on pipe 56470-3 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56470-3 at junction 89285 so both are connected. | Open |
| 669 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389287 | Junction 89287 (degree 1) lies on pipe 56482 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (28 m). → Split pipe 56482 at junction 89287 so both are connected. | Open |
| 670 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389318 | Junction 89318 (degree 1) lies on pipe 56419-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56419-1 at junction 89318 so both are connected. | Open |
| 671 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389345 | Junction 89345 (degree 1) lies on pipe 56411 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (31 m). → Split pipe 56411 at junction 89345 so both are connected. | Open |
| 672 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389348 | Junction 89348 (degree 1) lies on pipe 56551 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (65 m). → Split pipe 56551 at junction 89348 so both are connected. | Open |
| 673 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389363 | Junction 89363 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52887 at junction 89363 so both are connected. | Open |
| 674 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389365 | Junction 89365 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52887 at junction 89365 so both are connected. | Open |
| 675 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389367 | Junction 89367 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52887 at junction 89367 so both are connected. | Open |
| 676 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389369 | Junction 89369 (degree 1) lies on pipe 52887 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (25 m). → Split pipe 52887 at junction 89369 so both are connected. | Open |
| 677 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389377 | Junction 89377 (degree 1) lies on pipe 89718-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 89718-2 at junction 89377 so both are connected. | Open |
| 678 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389391 | Junction 89391 (degree 1) lies on pipe 52873-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (28 m). → Split pipe 52873-1 at junction 89391 so both are connected. | Open |
| 679 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389403 | Junction 89403 (degree 1) lies on pipe 52872 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52872 at junction 89403 so both are connected. | Open |
| 680 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389405 | Junction 89405 (degree 1) lies on pipe 56493-3 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56493-3 at junction 89405 so both are connected. | Open |
| 681 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389407 | Junction 89407 (degree 1) lies on pipe 56493-3 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56493-3 at junction 89407 so both are connected. | Open |
| 682 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389409 | Junction 89409 (degree 1) lies on pipe 56493-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56493-2 at junction 89409 so both are connected. | Open |
| 683 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389411 | Junction 89411 (degree 1) lies on pipe 56493-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56493-2 at junction 89411 so both are connected. | Open |
| 684 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389413 | Junction 89413 (degree 1) lies on pipe 56493-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56493-2 at junction 89413 so both are connected. | Open |
| 685 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389415 | Junction 89415 (degree 1) lies on pipe 56493-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56493-2 at junction 89415 so both are connected. | Open |
| 686 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389419 | Junction 89419 (degree 1) lies on pipe 52855-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52855-2 at junction 89419 so both are connected. | Open |
| 687 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389421 | Junction 89421 (degree 1) lies on pipe 52856 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52856 at junction 89421 so both are connected. | Open |
| 688 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389423 | Junction 89423 (degree 1) lies on pipe 52859 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52859 at junction 89423 so both are connected. | Open |
| 689 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389425 | Junction 89425 (degree 2) lies on pipe 52859 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 52859 at junction 89425 so both are connected. | Open |
| 690 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389427 | Junction 89427 (degree 1) lies on pipe 52859 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52859 at junction 89427 so both are connected. | Open |
| 691 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389429 | Junction 89429 (degree 1) lies on pipe 52859 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52859 at junction 89429 so both are connected. | Open |
| 692 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389431 | Junction 89431 (degree 1) lies on pipe 52860 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52860 at junction 89431 so both are connected. | Open |
| 693 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389433 | Junction 89433 (degree 1) lies on pipe 52882-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52882-1 at junction 89433 so both are connected. | Open |
| 694 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389438 | Junction 89438 (degree 1) lies on pipe 52873-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52873-2 at junction 89438 so both are connected. | Open |
| 695 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389440 | Junction 89440 (degree 1) lies on pipe 52873-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52873-2 at junction 89440 so both are connected. | Open |
| 696 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389442 | Junction 89442 (degree 1) lies on pipe 52910-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52910-2 at junction 89442 so both are connected. | Open |
| 697 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389444 | Junction 89444 (degree 1) lies on pipe 52910-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52910-2 at junction 89444 so both are connected. | Open |
| 698 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389446 | Junction 89446 (degree 1) lies on pipe 52910-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52910-2 at junction 89446 so both are connected. | Open |
| 699 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389448 | Junction 89448 (degree 1) lies on pipe 56369-2 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 56369-2 at junction 89448 so both are connected. | Open |
| 700 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389450 | Junction 89450 (degree 1) lies on pipe 56369-2 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56369-2 at junction 89450 so both are connected. | Open |
| 701 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389454 | Junction 89454 (degree 1) lies on pipe 52978-1 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52978-1 at junction 89454 so both are connected. | Open |
| 702 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389473 | Junction 89473 (degree 1) lies on pipe 56430 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (39 m). → Split pipe 56430 at junction 89473 so both are connected. | Open |
| 703 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389493 | Junction 89493 (degree 1) lies on pipe 52879 (DN 125, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52879 at junction 89493 so both are connected. | Open |
| 704 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389495 | Junction 89495 (degree 1) lies on pipe 52910-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52910-2 at junction 89495 so both are connected. | Open |
| 705 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389499 | Junction 89499 (degree 1) lies on pipe 52910-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52910-1 at junction 89499 so both are connected. | Open |
| 706 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389501 | Junction 89501 (degree 1) lies on pipe 52910-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52910-1 at junction 89501 so both are connected. | Open |
| 707 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389503 | Junction 89503 (degree 1) lies on pipe 52910-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52910-1 at junction 89503 so both are connected. | Open |
| 708 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389505 | Junction 89505 (degree 1) lies on pipe 52910-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (26 m). → Split pipe 52910-2 at junction 89505 so both are connected. | Open |
| 709 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389507 | Junction 89507 (degree 1) lies on pipe 56369-1 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56369-1 at junction 89507 so both are connected. | Open |
| 710 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389509 | Junction 89509 (degree 1) lies on pipe 56369-1 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56369-1 at junction 89509 so both are connected. | Open |
| 711 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389511 | Junction 89511 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89616 at junction 89511 so both are connected. | Open |
| 712 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389513 | Junction 89513 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89616 at junction 89513 so both are connected. | Open |
| 713 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389515 | Junction 89515 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 89616 at junction 89515 so both are connected. | Open |
| 714 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389519 | Junction 89519 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89616 at junction 89519 so both are connected. | Open |
| 715 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389521 | Junction 89521 (degree 1) lies on pipe 89616 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 89616 at junction 89521 so both are connected. | Open |
| 716 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389524 | Junction 89524 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56557 at junction 89524 so both are connected. | Open |
| 717 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389526 | Junction 89526 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56557 at junction 89526 so both are connected. | Open |
| 718 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389528 | Junction 89528 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56557 at junction 89528 so both are connected. | Open |
| 719 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389530 | Junction 89530 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 56557 at junction 89530 so both are connected. | Open |
| 720 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389532 | Junction 89532 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 56557 at junction 89532 so both are connected. | Open |
| 721 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389533 | Junction 89533 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 56557 at junction 89533 so both are connected. | Open |
| 722 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389535 | Junction 89535 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (30 m). → Split pipe 56557 at junction 89535 so both are connected. | Open |
| 723 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389537 | Junction 89537 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56557 at junction 89537 so both are connected. | Open |
| 724 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389540 | Junction 89540 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (27 m). → Split pipe 56557 at junction 89540 so both are connected. | Open |
| 725 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389542 | Junction 89542 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56557 at junction 89542 so both are connected. | Open |
| 726 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389544 | Junction 89544 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56557 at junction 89544 so both are connected. | Open |
| 727 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389546 | Junction 89546 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56557 at junction 89546 so both are connected. | Open |
| 728 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389548 | Junction 89548 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 56557 at junction 89548 so both are connected. | Open |
| 729 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389550 | Junction 89550 (degree 1) lies on pipe 56557 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56557 at junction 89550 so both are connected. | Open |
| 730 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389560 | Junction 89560 (degree 1) lies on pipe 52905-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (27 m). → Split pipe 52905-2 at junction 89560 so both are connected. | Open |
| 731 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389562 | Junction 89562 (degree 1) lies on pipe 52905-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (29 m). → Split pipe 52905-2 at junction 89562 so both are connected. | Open |
| 732 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389564 | Junction 89564 (degree 1) lies on pipe 52905-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (30 m). → Split pipe 52905-2 at junction 89564 so both are connected. | Open |
| 733 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389566 | Junction 89566 (degree 1) lies on pipe 52875 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (70 m). → Split pipe 52875 at junction 89566 so both are connected. | Open |
| 734 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389568 | Junction 89568 (degree 1) lies on pipe 52908-1 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52908-1 at junction 89568 so both are connected. | Open |
| 735 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389570 | Junction 89570 (degree 1) lies on pipe 52880-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52880-2 at junction 89570 so both are connected. | Open |
| 736 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389572 | Junction 89572 (degree 1) lies on pipe 52880-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52880-2 at junction 89572 so both are connected. | Open |
| 737 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389574 | Junction 89574 (degree 1) lies on pipe 52908-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52908-2 at junction 89574 so both are connected. | Open |
| 738 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389576 | Junction 89576 (degree 1) lies on pipe 53503 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (33 m). → Split pipe 53503 at junction 89576 so both are connected. | Open |
| 739 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389582 | Junction 89582 (degree 1) lies on pipe 56395 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (29 m). → Split pipe 56395 at junction 89582 so both are connected. | Open |
| 740 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389584 | Junction 89584 (degree 1) lies on pipe 53705 (DN 90, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53705 at junction 89584 so both are connected. | Open |
| 741 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389617 | Junction 89617 (degree 1) lies on pipe 56464 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (42 m). → Split pipe 56464 at junction 89617 so both are connected. | Open |
| 742 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389631 | Junction 89631 (degree 1) lies on pipe 53521 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (56 m). → Split pipe 53521 at junction 89631 so both are connected. | Open |
| 743 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389684 | Junction 89684 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 53734 at junction 89684 so both are connected. | Open |
| 744 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389686 | Junction 89686 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53734 at junction 89686 so both are connected. | Open |
| 745 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389688 | Junction 89688 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53734 at junction 89688 so both are connected. | Open |
| 746 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389690 | Junction 89690 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 53734 at junction 89690 so both are connected. | Open |
| 747 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389692 | Junction 89692 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 53734 at junction 89692 so both are connected. | Open |
| 748 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389694 | Junction 89694 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 53734 at junction 89694 so both are connected. | Open |
| 749 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389696 | Junction 89696 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (56 m). → Split pipe 53734 at junction 89696 so both are connected. | Open |
| 750 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389698 | Junction 89698 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53734 at junction 89698 so both are connected. | Open |
| 751 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389700 | Junction 89700 (degree 1) lies on pipe 53734 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (37 m). → Split pipe 53734 at junction 89700 so both are connected. | Open |
| 752 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389710 | Junction 89710 (degree 1) lies on pipe 52896-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52896-1 at junction 89710 so both are connected. | Open |
| 753 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389712 | Junction 89712 (degree 1) lies on pipe 52837 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 52837 at junction 89712 so both are connected. | Open |
| 754 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389714 | Junction 89714 (degree 1) lies on pipe 52898 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 52898 at junction 89714 so both are connected. | Open |
| 755 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389718 | Junction 89718 (degree 1) lies on pipe 52838 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52838 at junction 89718 so both are connected. | Open |
| 756 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389720 | Junction 89720 (degree 1) lies on pipe 52839 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52839 at junction 89720 so both are connected. | Open |
| 757 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389722 | Junction 89722 (degree 1) lies on pipe 52841 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52841 at junction 89722 so both are connected. | Open |
| 758 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389723 | Junction 89723 (degree 1) lies on pipe 52837 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52837 at junction 89723 so both are connected. | Open |
| 759 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389726 | Junction 89726 (degree 1) lies on pipe 52903 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52903 at junction 89726 so both are connected. | Open |
| 760 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389728 | Junction 89728 (degree 1) lies on pipe 52903 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52903 at junction 89728 so both are connected. | Open |
| 761 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389730 | Junction 89730 (degree 1) lies on pipe 52902 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52902 at junction 89730 so both are connected. | Open |
| 762 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389732 | Junction 89732 (degree 1) lies on pipe 52896-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52896-1 at junction 89732 so both are connected. | Open |
| 763 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389733 | Junction 89733 (degree 1) lies on pipe 52898 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 52898 at junction 89733 so both are connected. | Open |
| 764 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389735 | Junction 89735 (degree 1) lies on pipe 52898 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 52898 at junction 89735 so both are connected. | Open |
| 765 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389753 | Junction 89753 (degree 1) lies on pipe 56442 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 56442 at junction 89753 so both are connected. | Open |
| 766 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389784 | Junction 89784 (degree 1) lies on pipe 56442 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56442 at junction 89784 so both are connected. | Open |
| 767 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389805 | Junction 89805 (degree 1) lies on pipe 56369-1 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56369-1 at junction 89805 so both are connected. | Open |
| 768 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389807 | Junction 89807 (degree 1) lies on pipe 56369-1 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 56369-1 at junction 89807 so both are connected. | Open |
| 769 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389809 | Junction 89809 (degree 1) lies on pipe 56369-1 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56369-1 at junction 89809 so both are connected. | Open |
| 770 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389811 | Junction 89811 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56369-3 at junction 89811 so both are connected. | Open |
| 771 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389813 | Junction 89813 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56369-3 at junction 89813 so both are connected. | Open |
| 772 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389815 | Junction 89815 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56369-3 at junction 89815 so both are connected. | Open |
| 773 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389817 | Junction 89817 (degree 1) lies on pipe 52741-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52741-1 at junction 89817 so both are connected. | Open |
| 774 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389821 | Junction 89821 (degree 1) lies on pipe 56369-2 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56369-2 at junction 89821 so both are connected. | Open |
| 775 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389825 | Junction 89825 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56369-3 at junction 89825 so both are connected. | Open |
| 776 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389827 | Junction 89827 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56369-3 at junction 89827 so both are connected. | Open |
| 777 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389829 | Junction 89829 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56369-3 at junction 89829 so both are connected. | Open |
| 778 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389831 | Junction 89831 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56369-3 at junction 89831 so both are connected. | Open |
| 779 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389833 | Junction 89833 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56369-3 at junction 89833 so both are connected. | Open |
| 780 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389835 | Junction 89835 (degree 1) lies on pipe 56369-3 (transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56369-3 at junction 89835 so both are connected. | Open |
| 781 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389839 | Junction 89839 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52741-2 at junction 89839 so both are connected. | Open |
| 782 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389841 | Junction 89841 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52741-2 at junction 89841 so both are connected. | Open |
| 783 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389843 | Junction 89843 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52741-2 at junction 89843 so both are connected. | Open |
| 784 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389845 | Junction 89845 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52741-2 at junction 89845 so both are connected. | Open |
| 785 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389847 | Junction 89847 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52741-2 at junction 89847 so both are connected. | Open |
| 786 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389849 | Junction 89849 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52741-2 at junction 89849 so both are connected. | Open |
| 787 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389851 | Junction 89851 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52741-2 at junction 89851 so both are connected. | Open |
| 788 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389853 | Junction 89853 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52741-2 at junction 89853 so both are connected. | Open |
| 789 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389855 | Junction 89855 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52741-2 at junction 89855 so both are connected. | Open |
| 790 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389857 | Junction 89857 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52741-2 at junction 89857 so both are connected. | Open |
| 791 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389859 | Junction 89859 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52741-2 at junction 89859 so both are connected. | Open |
| 792 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389861 | Junction 89861 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52741-2 at junction 89861 so both are connected. | Open |
| 793 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389863 | Junction 89863 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 52741-2 at junction 89863 so both are connected. | Open |
| 794 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389865 | Junction 89865 (degree 1) lies on pipe 52741-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52741-1 at junction 89865 so both are connected. | Open |
| 795 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389867 | Junction 89867 (degree 1) lies on pipe 52741-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52741-1 at junction 89867 so both are connected. | Open |
| 796 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389869 | Junction 89869 (degree 1) lies on pipe 52741-1 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52741-1 at junction 89869 so both are connected. | Open |
| 797 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389871 | Junction 89871 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52741-2 at junction 89871 so both are connected. | Open |
| 798 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389873 | Junction 89873 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52741-2 at junction 89873 so both are connected. | Open |
| 799 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389875 | Junction 89875 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52741-2 at junction 89875 so both are connected. | Open |
| 800 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389877 | Junction 89877 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52741-2 at junction 89877 so both are connected. | Open |
| 801 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389879 | Junction 89879 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52741-2 at junction 89879 so both are connected. | Open |
| 802 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389881 | Junction 89881 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52741-2 at junction 89881 so both are connected. | Open |
| 803 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389883 | Junction 89883 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52741-2 at junction 89883 so both are connected. | Open |
| 804 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389885 | Junction 89885 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 52741-2 at junction 89885 so both are connected. | Open |
| 805 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389887 | Junction 89887 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52741-2 at junction 89887 so both are connected. | Open |
| 806 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389889 | Junction 89889 (degree 1) lies on pipe 52741-2 (DN 40, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52741-2 at junction 89889 so both are connected. | Open |
| 807 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389891 | Junction 89891 (degree 1) lies on pipe 53497-3 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 53497-3 at junction 89891 so both are connected. | Open |
| 808 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389893 | Junction 89893 (degree 1) lies on pipe 53497-3 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 53497-3 at junction 89893 so both are connected. | Open |
| 809 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389899 | Junction 89899 (degree 1) lies on pipe 53499 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53499 at junction 89899 so both are connected. | Open |
| 810 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389901 | Junction 89901 (degree 1) lies on pipe 53499 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53499 at junction 89901 so both are connected. | Open |
| 811 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389903 | Junction 89903 (degree 1) lies on pipe 53497-1 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 53497-1 at junction 89903 so both are connected. | Open |
| 812 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389905 | Junction 89905 (degree 1) lies on pipe 53497-1 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53497-1 at junction 89905 so both are connected. | Open |
| 813 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389907 | Junction 89907 (degree 1) lies on pipe 53497-1 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 53497-1 at junction 89907 so both are connected. | Open |
| 814 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389909 | Junction 89909 (degree 1) lies on pipe 53497-1 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 53497-1 at junction 89909 so both are connected. | Open |
| 815 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389911 | Junction 89911 (degree 1) lies on pipe 53497-1 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53497-1 at junction 89911 so both are connected. | Open |
| 816 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389913 | Junction 89913 (degree 1) lies on pipe 53497-1 (DN 25, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 53497-1 at junction 89913 so both are connected. | Open |
| 817 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389924 | Junction 89924 (degree 1) lies on pipe 56447 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 56447 at junction 89924 so both are connected. | Open |
| 818 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389927 | Junction 89927 (degree 1) lies on pipe 56447 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56447 at junction 89927 so both are connected. | Open |
| 819 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389933 | Junction 89933 (degree 1) lies on pipe 56418-1 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 56418-1 at junction 89933 so both are connected. | Open |
| 820 | ERROR P100 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0390009 | Junction 90009 (degree 1) lies on pipe 52871 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (102 m). → Split pipe 52871 at junction 90009 so both are connected. | Open |
| 821 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0311697 | Junction 11697 (degree 1) is 0.30 m from pipe 56681-15 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 10 pipe(s) (281 m). → Extend/snap to pipe 56681-15 and split it there, or confirm the gap is real. | Open |
| 822 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0314624 | Junction 14624 (degree 1) is 0.63 m from pipe 52877 (DN 200, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (32 m). → Extend/snap to pipe 52877 and split it there, or confirm the gap is real. | Open |
| 823 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318681 | Junction 18681 (degree 1) is 0.91 m from pipe 95354 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Extend/snap to pipe 95354 and split it there, or confirm the gap is real. | Open |
| 824 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318769 | Junction 18769 (degree 1) is 0.75 m from pipe 95312 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Extend/snap to pipe 95312 and split it there, or confirm the gap is real. | Open |
| 825 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0320002 | Junction 20002 (degree 1) is 0.98 m from pipe 95313 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Extend/snap to pipe 95313 and split it there, or confirm the gap is real. | Open |
| 826 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0320028 | Junction 20028 (degree 1) is 0.20 m from pipe 56469 (DN 63, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 5 pipe(s) (494 m). → Extend/snap to pipe 56469 and split it there, or confirm the gap is real. | Open |
| 827 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0325081 | Junction 25081 (degree 1) is 0.98 m from pipe 56477 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Extend/snap to pipe 56477 and split it there, or confirm the gap is real. | Open |
| 828 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0333494 | Junction 33494 (degree 1) is 0.15 m from pipe 52905-2 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (36 m). → Extend/snap to pipe 52905-2 and split it there, or confirm the gap is real. | Open |
| 829 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358472 | Junction 58472 (degree 1) is 0.57 m from pipe 93649 (DN 110, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 7 pipe(s) (2,354 m). → Extend/snap to pipe 93649 and split it there, or confirm the gap is real. | Open |
| 830 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0367607 | Junction 67607 (degree 1) is 0.14 m from pipe 56427 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 16 pipe(s) (388 m). → Extend/snap to pipe 56427 and split it there, or confirm the gap is real. | Open |
| 831 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378341 | Junction 78341 (degree 1) is 0.51 m from pipe 53737 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 179 pipe(s) (3,395 m). → Extend/snap to pipe 53737 and split it there, or confirm the gap is real. | Open |
| 832 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378763 | Junction 78763 (degree 1) is 0.88 m from pipe 53737 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 179 pipe(s) (3,395 m). → Extend/snap to pipe 53737 and split it there, or confirm the gap is real. | Open |
| 833 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378765 | Junction 78765 (degree 1) is 0.78 m from pipe 53737 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 179 pipe(s) (3,395 m). → Extend/snap to pipe 53737 and split it there, or confirm the gap is real. | Open |
| 834 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038633 | Junction 8633 (degree 1) is 0.64 m from pipe 53737 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 179 pipe(s) (3,395 m). → Extend/snap to pipe 53737 and split it there, or confirm the gap is real. | Open |
| 835 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038643 | Junction 8643 (degree 1) is 0.66 m from pipe 53737 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 179 pipe(s) (3,395 m). → Extend/snap to pipe 53737 and split it there, or confirm the gap is real. | Open |
| 836 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038645 | Junction 8645 (degree 1) is 0.63 m from pipe 53737 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 179 pipe(s) (3,395 m). → Extend/snap to pipe 53737 and split it there, or confirm the gap is real. | Open |
| 837 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0387755 | Junction 87755 (degree 1) is 0.05 m from pipe 56407-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 56407-2 and split it there, or confirm the gap is real. | Open |
| 838 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388944 | Junction 88944 (degree 1) is 0.06 m from pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 52904 and split it there, or confirm the gap is real. | Open |
| 839 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388948 | Junction 88948 (degree 1) is 0.11 m from pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Extend/snap to pipe 52904 and split it there, or confirm the gap is real. | Open |
| 840 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388954 | Junction 88954 (degree 1) is 0.05 m from pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Extend/snap to pipe 52904 and split it there, or confirm the gap is real. | Open |
| 841 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388956 | Junction 88956 (degree 1) is 0.08 m from pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Extend/snap to pipe 52904 and split it there, or confirm the gap is real. | Open |
| 842 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388958 | Junction 88958 (degree 1) is 0.07 m from pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Extend/snap to pipe 52904 and split it there, or confirm the gap is real. | Open |
| 843 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388961 | Junction 88961 (degree 1) is 0.10 m from pipe 52904 (DN 150, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Extend/snap to pipe 52904 and split it there, or confirm the gap is real. | Open |
| 844 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389104 | Junction 89104 (degree 1) is 0.13 m from pipe 56407-2 (DN 100, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Extend/snap to pipe 56407-2 and split it there, or confirm the gap is real. | Open |
| 845 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039160 | Junction 9160 (degree 1) is 0.30 m from pipe 95578 (DN 160, transmission) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 6 pipe(s) (2,996 m). → Extend/snap to pipe 95578 and split it there, or confirm the gap is real. | Open |
| 846 | ERROR P100 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039261 | Junction 9261 (degree 1) is 0.25 m from pipe 56380 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 10 pipe(s) (556 m). → Extend/snap to pipe 56380 and split it there, or confirm the gap is real. | Open |
| 847 | ERROR P98 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev03116100 | Junction 116100 (degree 1) lies on pipe 56542 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 4 pipe(s) (285 m). → Split pipe 56542 at junction 116100 so both are connected. | Open |
| 848 | ERROR P98 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033037 | Junction 3037 (degree 1) lies on pipe 56462 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 3 pipe(s) (43 m). → Split pipe 56462 at junction 3037 so both are connected. | Open |
| 849 | ERROR P96 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev0418 pipes near 53740 | 18 pipe(s), 1,101 m in total incl. 18 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 850 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033033 | Junction 3033 (degree 1) lies on pipe 56462 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 56462 at junction 3033 so both are connected. | Open |
| 851 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387106 | Junction 87106 (degree 2) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 52835-3 at junction 87106 so both are connected. | Open |
| 852 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387116 | Junction 87116 (degree 2) lies on pipe 52835-2 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 52835-2 at junction 87116 so both are connected. | Open |
| 853 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387124 | Junction 87124 (degree 2) lies on pipe 52835-2 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 52835-2 at junction 87124 so both are connected. | Open |
| 854 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387291 | Junction 87291 (degree 2) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 56568 at junction 87291 so both are connected. | Open |
| 855 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387295 | Junction 87295 (degree 2) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 56568 at junction 87295 so both are connected. | Open |
| 856 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387297 | Junction 87297 (degree 2) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 56568 at junction 87297 so both are connected. | Open |
| 857 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387299 | Junction 87299 (degree 2) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (23 m). → Split pipe 56568 at junction 87299 so both are connected. | Open |
| 858 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387301 | Junction 87301 (degree 2) lies on pipe 56572 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 56572 at junction 87301 so both are connected. | Open |
| 859 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387322 | Junction 87322 (degree 2) lies on pipe 52827-9 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 52827-9 at junction 87322 so both are connected. | Open |
| 860 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387426 | Junction 87426 (degree 2) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 56417 at junction 87426 so both are connected. | Open |
| 861 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387437 | Junction 87437 (degree 2) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 56417 at junction 87437 so both are connected. | Open |
| 862 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387467 | Junction 87467 (degree 2) lies on pipe 56416-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (28 m). → Split pipe 56416-1 at junction 87467 so both are connected. | Open |
| 863 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387500 | Junction 87500 (degree 2) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (18 m). → Split pipe 52823 at junction 87500 so both are connected. | Open |
| 864 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387503 | Junction 87503 (degree 2) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (22 m). → Split pipe 52823 at junction 87503 so both are connected. | Open |
| 865 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387506 | Junction 87506 (degree 2) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 52823 at junction 87506 so both are connected. | Open |
| 866 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387517 | Junction 87517 (degree 2) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (23 m). → Split pipe 52822-2 at junction 87517 so both are connected. | Open |
| 867 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387528 | Junction 87528 (degree 2) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (40 m). → Split pipe 52822-1 at junction 87528 so both are connected. | Open |
| 868 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387532 | Junction 87532 (degree 2) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (25 m). → Split pipe 52822-1 at junction 87532 so both are connected. | Open |
| 869 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387534 | Junction 87534 (degree 2) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (25 m). → Split pipe 52822-1 at junction 87534 so both are connected. | Open |
| 870 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387543 | Junction 87543 (degree 2) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (57 m). → Split pipe 52822-1 at junction 87543 so both are connected. | Open |
| 871 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387545 | Junction 87545 (degree 2) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (30 m). → Split pipe 52822-1 at junction 87545 so both are connected. | Open |
| 872 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387549 | Junction 87549 (degree 2) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (59 m). → Split pipe 52822-1 at junction 87549 so both are connected. | Open |
| 873 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387555 | Junction 87555 (degree 2) lies on pipe 52820-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 52820-2 at junction 87555 so both are connected. | Open |
| 874 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387602 | Junction 87602 (degree 2) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 52820-1 at junction 87602 so both are connected. | Open |
| 875 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387604 | Junction 87604 (degree 2) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 52820-1 at junction 87604 so both are connected. | Open |
| 876 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387612 | Junction 87612 (degree 2) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 52820-1 at junction 87612 so both are connected. | Open |
| 877 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387617 | Junction 87617 (degree 2) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (26 m). → Split pipe 52820-1 at junction 87617 so both are connected. | Open |
| 878 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387626 | Junction 87626 (degree 2) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (26 m). → Split pipe 52820-1 at junction 87626 so both are connected. | Open |
| 879 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387695 | Junction 87695 (degree 2) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (29 m). → Split pipe 56384 at junction 87695 so both are connected. | Open |
| 880 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388367 | Junction 88367 (degree 2) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (20 m). → Split pipe 52832-1 at junction 88367 so both are connected. | Open |
| 881 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388393 | Junction 88393 (degree 2) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 56415 at junction 88393 so both are connected. | Open |
| 882 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388404 | Junction 88404 (degree 2) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (22 m). → Split pipe 56415 at junction 88404 so both are connected. | Open |
| 883 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388406 | Junction 88406 (degree 2) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 56414 at junction 88406 so both are connected. | Open |
| 884 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388408 | Junction 88408 (degree 2) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 56414 at junction 88408 so both are connected. | Open |
| 885 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388412 | Junction 88412 (degree 2) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (17 m). → Split pipe 56414 at junction 88412 so both are connected. | Open |
| 886 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388418 | Junction 88418 (degree 2) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 56414 at junction 88418 so both are connected. | Open |
| 887 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388723 | Junction 88723 (degree 2) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (21 m). → Split pipe 52895 at junction 88723 so both are connected. | Open |
| 888 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388728 | Junction 88728 (degree 2) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (22 m). → Split pipe 52895 at junction 88728 so both are connected. | Open |
| 889 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388735 | Junction 88735 (degree 2) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 52895 at junction 88735 so both are connected. | Open |
| 890 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388740 | Junction 88740 (degree 2) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (19 m). → Split pipe 52895 at junction 88740 so both are connected. | Open |
| 891 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388742 | Junction 88742 (degree 2) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (23 m). → Split pipe 52895 at junction 88742 so both are connected. | Open |
| 892 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388744 | Junction 88744 (degree 2) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (23 m). → Split pipe 52895 at junction 88744 so both are connected. | Open |
| 893 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389006 | Junction 89006 (degree 2) lies on pipe 56368 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (24 m). → Split pipe 56368 at junction 89006 so both are connected. | Open |
| 894 | ERROR P96 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039781 | Junction 9781 (degree 2) lies on pipe 89723-11 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (16 m). → Split pipe 89723-11 at junction 9781 so both are connected. | Open |
| 895 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314587 | Junction 14587 (degree 1) lies on pipe 52827-7 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 52827-7 at junction 14587 so both are connected. | Open |
| 896 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314588 | Junction 14588 (degree 1) lies on pipe 91552-6 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 91552-6 at junction 14588 so both are connected. | Open |
| 897 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314596 | Junction 14596 (degree 1) lies on pipe 52827-9 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52827-9 at junction 14596 so both are connected. | Open |
| 898 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314598 | Junction 14598 (degree 1) lies on pipe 91552-8 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (42 m). → Split pipe 91552-8 at junction 14598 so both are connected. | Open |
| 899 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314601 | Junction 14601 (degree 1) lies on pipe 91552-8 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 91552-8 at junction 14601 so both are connected. | Open |
| 900 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314603 | Junction 14603 (degree 1) lies on pipe 91552-8 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (32 m). → Split pipe 91552-8 at junction 14603 so both are connected. | Open |
| 901 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314606 | Junction 14606 (degree 1) lies on pipe 91552-6 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (25 m). → Split pipe 91552-6 at junction 14606 so both are connected. | Open |
| 902 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314607 | Junction 14607 (degree 1) lies on pipe 91552-6 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 91552-6 at junction 14607 so both are connected. | Open |
| 903 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314609 | Junction 14609 (degree 1) lies on pipe 91552-6 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 91552-6 at junction 14609 so both are connected. | Open |
| 904 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0314611 | Junction 14611 (degree 1) lies on pipe 56423-6 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56423-6 at junction 14611 so both are connected. | Open |
| 905 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0320311 | Junction 20311 (degree 1) lies on pipe 95548 (DN 355, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 95548 at junction 20311 so both are connected. | Open |
| 906 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0325135 | Junction 25135 (degree 1) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56568 at junction 25135 so both are connected. | Open |
| 907 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033018 | Junction 3018 (degree 1) lies on pipe 56682-7 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56682-7 at junction 3018 so both are connected. | Open |
| 908 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033027 | Junction 3027 (degree 1) lies on pipe 65711-3 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 65711-3 at junction 3027 so both are connected. | Open |
| 909 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033029 | Junction 3029 (degree 1) lies on pipe 65711-3 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 65711-3 at junction 3029 so both are connected. | Open |
| 910 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033034 | Junction 3034 (degree 1) lies on pipe 56462 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (68 m). → Split pipe 56462 at junction 3034 so both are connected. | Open |
| 911 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033044 | Junction 3044 (degree 1) lies on pipe 56681-14 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56681-14 at junction 3044 so both are connected. | Open |
| 912 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033045 | Junction 3045 (degree 1) lies on pipe 56674-1 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56674-1 at junction 3045 so both are connected. | Open |
| 913 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033046 | Junction 3046 (degree 1) lies on pipe 56674-1 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56674-1 at junction 3046 so both are connected. | Open |
| 914 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033047 | Junction 3047 (degree 1) lies on pipe 85842 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 85842 at junction 3047 so both are connected. | Open |
| 915 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033048 | Junction 3048 (degree 1) lies on pipe 85842 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 85842 at junction 3048 so both are connected. | Open |
| 916 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033049 | Junction 3049 (degree 1) lies on pipe 85842 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 85842 at junction 3049 so both are connected. | Open |
| 917 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033050 | Junction 3050 (degree 1) lies on pipe 85842 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 85842 at junction 3050 so both are connected. | Open |
| 918 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033051 | Junction 3051 (degree 1) lies on pipe 85842 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 85842 at junction 3051 so both are connected. | Open |
| 919 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033052 | Junction 3052 (degree 1) lies on pipe 85842 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 85842 at junction 3052 so both are connected. | Open |
| 920 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033053 | Junction 3053 (degree 1) lies on pipe 85840 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 85840 at junction 3053 so both are connected. | Open |
| 921 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033056 | Junction 3056 (degree 1) lies on pipe 85840 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 85840 at junction 3056 so both are connected. | Open |
| 922 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033292 | Junction 3292 (degree 1) lies on pipe 56681-2 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56681-2 at junction 3292 so both are connected. | Open |
| 923 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0333398 | Junction 33398 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 89724 at junction 33398 so both are connected. | Open |
| 924 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev037729 | Junction 7729 (degree 1) lies on pipe 89340-2 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 89340-2 at junction 7729 so both are connected. | Open |
| 925 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0377385 | Junction 77385 (degree 1) lies on pipe 89535-4 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 89535-4 at junction 77385 so both are connected. | Open |
| 926 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev037758 | Junction 7758 (degree 1) lies on pipe 89337 (DN 125, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 89337 at junction 7758 so both are connected. | Open |
| 927 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev037760 | Junction 7760 (degree 1) lies on pipe 89125 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 89125 at junction 7760 so both are connected. | Open |
| 928 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0377669 | Junction 77669 (degree 1) lies on pipe 89566-5 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 89566-5 at junction 77669 so both are connected. | Open |
| 929 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev037778 | Junction 7778 (degree 1) lies on pipe 89355 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 89355 at junction 7778 so both are connected. | Open |
| 930 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0378416 | Junction 78416 (degree 1) lies on pipe 89488-13 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 89488-13 at junction 78416 so both are connected. | Open |
| 931 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0378531 | Junction 78531 (degree 1) lies on pipe 89472-4 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 89472-4 at junction 78531 so both are connected. | Open |
| 932 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0378754 | Junction 78754 (degree 1) lies on pipe 89470-6 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 89470-6 at junction 78754 so both are connected. | Open |
| 933 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038198 | Junction 8198 (degree 1) lies on pipe 53700 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 53700 at junction 8198 so both are connected. | Open |
| 934 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038199 | Junction 8199 (degree 1) lies on pipe 89381-1 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 89381-1 at junction 8199 so both are connected. | Open |
| 935 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038520 | Junction 8520 (degree 1) lies on pipe 56635-6 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 56635-6 at junction 8520 so both are connected. | Open |
| 936 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038550 | Junction 8550 (degree 1) lies on pipe 56366-2 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Split pipe 56366-2 at junction 8550 so both are connected. | Open |
| 937 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038582 | Junction 8582 (degree 1) lies on pipe 89488-15 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 89488-15 at junction 8582 so both are connected. | Open |
| 938 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038585 | Junction 8585 (degree 1) lies on pipe 89488-14 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 89488-14 at junction 8585 so both are connected. | Open |
| 939 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038621 | Junction 8621 (degree 1) lies on pipe 56633-19 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 56633-19 at junction 8621 so both are connected. | Open |
| 940 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038665 | Junction 8665 (degree 1) lies on pipe 56672-1 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 56672-1 at junction 8665 so both are connected. | Open |
| 941 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386652 | Junction 86652 (degree 1) lies on pipe 56571 (DN 25, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56571 at junction 86652 so both are connected. | Open |
| 942 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386654 | Junction 86654 (degree 1) lies on pipe 56588 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56588 at junction 86654 so both are connected. | Open |
| 943 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386662 | Junction 86662 (degree 1) lies on pipe 56588 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56588 at junction 86662 so both are connected. | Open |
| 944 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038668 | Junction 8668 (degree 1) lies on pipe 56672-1 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 56672-1 at junction 8668 so both are connected. | Open |
| 945 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386719 | Junction 86719 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52834-2 at junction 86719 so both are connected. | Open |
| 946 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386723 | Junction 86723 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52834-2 at junction 86723 so both are connected. | Open |
| 947 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386725 | Junction 86725 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52834-2 at junction 86725 so both are connected. | Open |
| 948 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386727 | Junction 86727 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52834-2 at junction 86727 so both are connected. | Open |
| 949 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386735 | Junction 86735 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52834-2 at junction 86735 so both are connected. | Open |
| 950 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386739 | Junction 86739 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52834-2 at junction 86739 so both are connected. | Open |
| 951 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386743 | Junction 86743 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52834-2 at junction 86743 so both are connected. | Open |
| 952 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386747 | Junction 86747 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52834-2 at junction 86747 so both are connected. | Open |
| 953 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386751 | Junction 86751 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52834-2 at junction 86751 so both are connected. | Open |
| 954 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386753 | Junction 86753 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52833 at junction 86753 so both are connected. | Open |
| 955 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386755 | Junction 86755 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52833 at junction 86755 so both are connected. | Open |
| 956 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386757 | Junction 86757 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52833 at junction 86757 so both are connected. | Open |
| 957 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386759 | Junction 86759 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52833 at junction 86759 so both are connected. | Open |
| 958 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386761 | Junction 86761 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52833 at junction 86761 so both are connected. | Open |
| 959 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386763 | Junction 86763 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52833 at junction 86763 so both are connected. | Open |
| 960 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386765 | Junction 86765 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52833 at junction 86765 so both are connected. | Open |
| 961 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386767 | Junction 86767 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52833 at junction 86767 so both are connected. | Open |
| 962 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0386769 | Junction 86769 (degree 1) lies on pipe 52833 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 52833 at junction 86769 so both are connected. | Open |
| 963 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387090 | Junction 87090 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52835-3 at junction 87090 so both are connected. | Open |
| 964 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387098 | Junction 87098 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (30 m). → Split pipe 52835-3 at junction 87098 so both are connected. | Open |
| 965 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387100 | Junction 87100 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52835-3 at junction 87100 so both are connected. | Open |
| 966 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387102 | Junction 87102 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52835-3 at junction 87102 so both are connected. | Open |
| 967 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387104 | Junction 87104 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52835-3 at junction 87104 so both are connected. | Open |
| 968 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387108 | Junction 87108 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52835-3 at junction 87108 so both are connected. | Open |
| 969 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387110 | Junction 87110 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52835-3 at junction 87110 so both are connected. | Open |
| 970 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387112 | Junction 87112 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (41 m). → Split pipe 52835-3 at junction 87112 so both are connected. | Open |
| 971 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387118 | Junction 87118 (degree 1) lies on pipe 52835-2 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52835-2 at junction 87118 so both are connected. | Open |
| 972 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387120 | Junction 87120 (degree 1) lies on pipe 52835-2 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 52835-2 at junction 87120 so both are connected. | Open |
| 973 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387122 | Junction 87122 (degree 1) lies on pipe 52835-2 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52835-2 at junction 87122 so both are connected. | Open |
| 974 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387126 | Junction 87126 (degree 1) lies on pipe 52835-2 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52835-2 at junction 87126 so both are connected. | Open |
| 975 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387130 | Junction 87130 (degree 1) lies on pipe 52835-1 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52835-1 at junction 87130 so both are connected. | Open |
| 976 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387132 | Junction 87132 (degree 1) lies on pipe 52835-2 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52835-2 at junction 87132 so both are connected. | Open |
| 977 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387136 | Junction 87136 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52835-3 at junction 87136 so both are connected. | Open |
| 978 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387138 | Junction 87138 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52835-3 at junction 87138 so both are connected. | Open |
| 979 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387141 | Junction 87141 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52835-3 at junction 87141 so both are connected. | Open |
| 980 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387143 | Junction 87143 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52835-3 at junction 87143 so both are connected. | Open |
| 981 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387145 | Junction 87145 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52835-3 at junction 87145 so both are connected. | Open |
| 982 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387147 | Junction 87147 (degree 1) lies on pipe 52835-3 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52835-3 at junction 87147 so both are connected. | Open |
| 983 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387149 | Junction 87149 (degree 1) lies on pipe 52831 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 52831 at junction 87149 so both are connected. | Open |
| 984 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387159 | Junction 87159 (degree 1) lies on pipe 52831 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52831 at junction 87159 so both are connected. | Open |
| 985 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387161 | Junction 87161 (degree 1) lies on pipe 52831 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52831 at junction 87161 so both are connected. | Open |
| 986 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387163 | Junction 87163 (degree 1) lies on pipe 52831 (DN 100, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52831 at junction 87163 so both are connected. | Open |
| 987 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387189 | Junction 87189 (degree 1) lies on pipe 56423-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56423-1 at junction 87189 so both are connected. | Open |
| 988 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387199 | Junction 87199 (degree 1) lies on pipe 56423-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56423-1 at junction 87199 so both are connected. | Open |
| 989 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387201 | Junction 87201 (degree 1) lies on pipe 56423-4 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56423-4 at junction 87201 so both are connected. | Open |
| 990 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387203 | Junction 87203 (degree 1) lies on pipe 56423-4 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56423-4 at junction 87203 so both are connected. | Open |
| 991 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387205 | Junction 87205 (degree 1) lies on pipe 56423-4 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56423-4 at junction 87205 so both are connected. | Open |
| 992 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387207 | Junction 87207 (degree 1) lies on pipe 56423-4 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56423-4 at junction 87207 so both are connected. | Open |
| 993 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387209 | Junction 87209 (degree 1) lies on pipe 56423-5 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56423-5 at junction 87209 so both are connected. | Open |
| 994 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387211 | Junction 87211 (degree 1) lies on pipe 56423-6 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56423-6 at junction 87211 so both are connected. | Open |
| 995 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387213 | Junction 87213 (degree 1) lies on pipe 56423-6 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56423-6 at junction 87213 so both are connected. | Open |
| 996 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387215 | Junction 87215 (degree 1) lies on pipe 56423-6 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56423-6 at junction 87215 so both are connected. | Open |
| 997 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387217 | Junction 87217 (degree 1) lies on pipe 56423-6 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56423-6 at junction 87217 so both are connected. | Open |
| 998 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387219 | Junction 87219 (degree 1) lies on pipe 56423-6 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 56423-6 at junction 87219 so both are connected. | Open |
| 999 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387221 | Junction 87221 (degree 1) lies on pipe 56423-7 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56423-7 at junction 87221 so both are connected. | Open |
| 1000 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387223 | Junction 87223 (degree 1) lies on pipe 56423-8 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56423-8 at junction 87223 so both are connected. | Open |
| 1001 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387225 | Junction 87225 (degree 1) lies on pipe 52827-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52827-1 at junction 87225 so both are connected. | Open |
| 1002 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387227 | Junction 87227 (degree 1) lies on pipe 52827-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52827-2 at junction 87227 so both are connected. | Open |
| 1003 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387229 | Junction 87229 (degree 1) lies on pipe 52827-3 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52827-3 at junction 87229 so both are connected. | Open |
| 1004 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387231 | Junction 87231 (degree 1) lies on pipe 52827-3 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52827-3 at junction 87231 so both are connected. | Open |
| 1005 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387233 | Junction 87233 (degree 1) lies on pipe 52827-4 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52827-4 at junction 87233 so both are connected. | Open |
| 1006 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387235 | Junction 87235 (degree 1) lies on pipe 52827-5 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52827-5 at junction 87235 so both are connected. | Open |
| 1007 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387237 | Junction 87237 (degree 1) lies on pipe 52827-8 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52827-8 at junction 87237 so both are connected. | Open |
| 1008 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387239 | Junction 87239 (degree 1) lies on pipe 52827-8 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52827-8 at junction 87239 so both are connected. | Open |
| 1009 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387241 | Junction 87241 (degree 1) lies on pipe 52827-8 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52827-8 at junction 87241 so both are connected. | Open |
| 1010 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387243 | Junction 87243 (degree 1) lies on pipe 52827-8 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52827-8 at junction 87243 so both are connected. | Open |
| 1011 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387245 | Junction 87245 (degree 1) lies on pipe 52827-8 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52827-8 at junction 87245 so both are connected. | Open |
| 1012 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387247 | Junction 87247 (degree 1) lies on pipe 52827-9 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52827-9 at junction 87247 so both are connected. | Open |
| 1013 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387289 | Junction 87289 (degree 1) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56568 at junction 87289 so both are connected. | Open |
| 1014 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387293 | Junction 87293 (degree 1) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56568 at junction 87293 so both are connected. | Open |
| 1015 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387303 | Junction 87303 (degree 1) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (30 m). → Split pipe 56568 at junction 87303 so both are connected. | Open |
| 1016 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387305 | Junction 87305 (degree 1) lies on pipe 56572 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56572 at junction 87305 so both are connected. | Open |
| 1017 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387308 | Junction 87308 (degree 1) lies on pipe 56572 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56572 at junction 87308 so both are connected. | Open |
| 1018 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387313 | Junction 87313 (degree 1) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56568 at junction 87313 so both are connected. | Open |
| 1019 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387316 | Junction 87316 (degree 1) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56568 at junction 87316 so both are connected. | Open |
| 1020 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387318 | Junction 87318 (degree 1) lies on pipe 52827-10 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52827-10 at junction 87318 so both are connected. | Open |
| 1021 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387320 | Junction 87320 (degree 1) lies on pipe 52827-9 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52827-9 at junction 87320 so both are connected. | Open |
| 1022 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387429 | Junction 87429 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56417 at junction 87429 so both are connected. | Open |
| 1023 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387431 | Junction 87431 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56417 at junction 87431 so both are connected. | Open |
| 1024 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387433 | Junction 87433 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 56417 at junction 87433 so both are connected. | Open |
| 1025 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387435 | Junction 87435 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 56417 at junction 87435 so both are connected. | Open |
| 1026 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387439 | Junction 87439 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56417 at junction 87439 so both are connected. | Open |
| 1027 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387441 | Junction 87441 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56417 at junction 87441 so both are connected. | Open |
| 1028 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387444 | Junction 87444 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56417 at junction 87444 so both are connected. | Open |
| 1029 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387446 | Junction 87446 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 56417 at junction 87446 so both are connected. | Open |
| 1030 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387448 | Junction 87448 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56417 at junction 87448 so both are connected. | Open |
| 1031 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387450 | Junction 87450 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 56417 at junction 87450 so both are connected. | Open |
| 1032 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387452 | Junction 87452 (degree 1) lies on pipe 56416-2 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56416-2 at junction 87452 so both are connected. | Open |
| 1033 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387454 | Junction 87454 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 56417 at junction 87454 so both are connected. | Open |
| 1034 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387458 | Junction 87458 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (27 m). → Split pipe 56417 at junction 87458 so both are connected. | Open |
| 1035 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387460 | Junction 87460 (degree 1) lies on pipe 56416-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56416-1 at junction 87460 so both are connected. | Open |
| 1036 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387463 | Junction 87463 (degree 1) lies on pipe 56416-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56416-1 at junction 87463 so both are connected. | Open |
| 1037 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387465 | Junction 87465 (degree 1) lies on pipe 56416-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56416-1 at junction 87465 so both are connected. | Open |
| 1038 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387470 | Junction 87470 (degree 1) lies on pipe 56416-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56416-1 at junction 87470 so both are connected. | Open |
| 1039 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387472 | Junction 87472 (degree 1) lies on pipe 56416-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56416-1 at junction 87472 so both are connected. | Open |
| 1040 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387474 | Junction 87474 (degree 1) lies on pipe 56416-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56416-1 at junction 87474 so both are connected. | Open |
| 1041 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387482 | Junction 87482 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52823 at junction 87482 so both are connected. | Open |
| 1042 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387488 | Junction 87488 (degree 1) lies on pipe 56417 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56417 at junction 87488 so both are connected. | Open |
| 1043 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387490 | Junction 87490 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52823 at junction 87490 so both are connected. | Open |
| 1044 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387492 | Junction 87492 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52823 at junction 87492 so both are connected. | Open |
| 1045 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387494 | Junction 87494 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52823 at junction 87494 so both are connected. | Open |
| 1046 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387496 | Junction 87496 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (27 m). → Split pipe 52823 at junction 87496 so both are connected. | Open |
| 1047 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387498 | Junction 87498 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 52823 at junction 87498 so both are connected. | Open |
| 1048 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387509 | Junction 87509 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52822-2 at junction 87509 so both are connected. | Open |
| 1049 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387511 | Junction 87511 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52822-2 at junction 87511 so both are connected. | Open |
| 1050 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387513 | Junction 87513 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 52822-2 at junction 87513 so both are connected. | Open |
| 1051 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387515 | Junction 87515 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (41 m). → Split pipe 52822-2 at junction 87515 so both are connected. | Open |
| 1052 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387519 | Junction 87519 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52822-2 at junction 87519 so both are connected. | Open |
| 1053 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387521 | Junction 87521 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52822-2 at junction 87521 so both are connected. | Open |
| 1054 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387523 | Junction 87523 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52822-2 at junction 87523 so both are connected. | Open |
| 1055 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387526 | Junction 87526 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (27 m). → Split pipe 52822-2 at junction 87526 so both are connected. | Open |
| 1056 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387530 | Junction 87530 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 52822-2 at junction 87530 so both are connected. | Open |
| 1057 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387536 | Junction 87536 (degree 1) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 52822-1 at junction 87536 so both are connected. | Open |
| 1058 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387541 | Junction 87541 (degree 1) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52822-1 at junction 87541 so both are connected. | Open |
| 1059 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387552 | Junction 87552 (degree 1) lies on pipe 52821 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (26 m). → Split pipe 52821 at junction 87552 so both are connected. | Open |
| 1060 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387557 | Junction 87557 (degree 1) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 52822-1 at junction 87557 so both are connected. | Open |
| 1061 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387559 | Junction 87559 (degree 1) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (33 m). → Split pipe 52822-1 at junction 87559 so both are connected. | Open |
| 1062 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387561 | Junction 87561 (degree 1) lies on pipe 52820-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 52820-2 at junction 87561 so both are connected. | Open |
| 1063 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387563 | Junction 87563 (degree 1) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52822-1 at junction 87563 so both are connected. | Open |
| 1064 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387567 | Junction 87567 (degree 1) lies on pipe 52821 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 52821 at junction 87567 so both are connected. | Open |
| 1065 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387570 | Junction 87570 (degree 1) lies on pipe 52820-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52820-2 at junction 87570 so both are connected. | Open |
| 1066 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387572 | Junction 87572 (degree 1) lies on pipe 52820-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52820-2 at junction 87572 so both are connected. | Open |
| 1067 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387574 | Junction 87574 (degree 1) lies on pipe 52820-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52820-2 at junction 87574 so both are connected. | Open |
| 1068 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387576 | Junction 87576 (degree 1) lies on pipe 52820-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52820-2 at junction 87576 so both are connected. | Open |
| 1069 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387578 | Junction 87578 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52820-1 at junction 87578 so both are connected. | Open |
| 1070 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387580 | Junction 87580 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52820-1 at junction 87580 so both are connected. | Open |
| 1071 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387582 | Junction 87582 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52820-1 at junction 87582 so both are connected. | Open |
| 1072 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387584 | Junction 87584 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52820-1 at junction 87584 so both are connected. | Open |
| 1073 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387586 | Junction 87586 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52820-1 at junction 87586 so both are connected. | Open |
| 1074 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387588 | Junction 87588 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52820-1 at junction 87588 so both are connected. | Open |
| 1075 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387590 | Junction 87590 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52820-1 at junction 87590 so both are connected. | Open |
| 1076 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387592 | Junction 87592 (degree 1) lies on pipe 52820-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52820-2 at junction 87592 so both are connected. | Open |
| 1077 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387594 | Junction 87594 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52820-1 at junction 87594 so both are connected. | Open |
| 1078 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387596 | Junction 87596 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52820-1 at junction 87596 so both are connected. | Open |
| 1079 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387598 | Junction 87598 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52820-1 at junction 87598 so both are connected. | Open |
| 1080 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387600 | Junction 87600 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52820-1 at junction 87600 so both are connected. | Open |
| 1081 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387606 | Junction 87606 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52820-1 at junction 87606 so both are connected. | Open |
| 1082 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387608 | Junction 87608 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52820-1 at junction 87608 so both are connected. | Open |
| 1083 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387610 | Junction 87610 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52820-1 at junction 87610 so both are connected. | Open |
| 1084 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387614 | Junction 87614 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52820-1 at junction 87614 so both are connected. | Open |
| 1085 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387619 | Junction 87619 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52820-1 at junction 87619 so both are connected. | Open |
| 1086 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387621 | Junction 87621 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52820-1 at junction 87621 so both are connected. | Open |
| 1087 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387624 | Junction 87624 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52820-1 at junction 87624 so both are connected. | Open |
| 1088 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387628 | Junction 87628 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52820-1 at junction 87628 so both are connected. | Open |
| 1089 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387630 | Junction 87630 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52820-1 at junction 87630 so both are connected. | Open |
| 1090 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387633 | Junction 87633 (degree 1) lies on pipe 52820-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52820-1 at junction 87633 so both are connected. | Open |
| 1091 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387637 | Junction 87637 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52817 at junction 87637 so both are connected. | Open |
| 1092 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387639 | Junction 87639 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52817 at junction 87639 so both are connected. | Open |
| 1093 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387641 | Junction 87641 (degree 1) lies on pipe 56387 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 56387 at junction 87641 so both are connected. | Open |
| 1094 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387643 | Junction 87643 (degree 1) lies on pipe 52819 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 52819 at junction 87643 so both are connected. | Open |
| 1095 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387645 | Junction 87645 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52817 at junction 87645 so both are connected. | Open |
| 1096 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387647 | Junction 87647 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52817 at junction 87647 so both are connected. | Open |
| 1097 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387649 | Junction 87649 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52817 at junction 87649 so both are connected. | Open |
| 1098 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387651 | Junction 87651 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52817 at junction 87651 so both are connected. | Open |
| 1099 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387653 | Junction 87653 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (29 m). → Split pipe 52817 at junction 87653 so both are connected. | Open |
| 1100 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387655 | Junction 87655 (degree 1) lies on pipe 52817 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52817 at junction 87655 so both are connected. | Open |
| 1101 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387657 | Junction 87657 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52918 at junction 87657 so both are connected. | Open |
| 1102 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387659 | Junction 87659 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52918 at junction 87659 so both are connected. | Open |
| 1103 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387661 | Junction 87661 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 52918 at junction 87661 so both are connected. | Open |
| 1104 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387663 | Junction 87663 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52918 at junction 87663 so both are connected. | Open |
| 1105 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387665 | Junction 87665 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52918 at junction 87665 so both are connected. | Open |
| 1106 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387667 | Junction 87667 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52918 at junction 87667 so both are connected. | Open |
| 1107 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387671 | Junction 87671 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52918 at junction 87671 so both are connected. | Open |
| 1108 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387675 | Junction 87675 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52918 at junction 87675 so both are connected. | Open |
| 1109 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387679 | Junction 87679 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52918 at junction 87679 so both are connected. | Open |
| 1110 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387687 | Junction 87687 (degree 1) lies on pipe 52918 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52918 at junction 87687 so both are connected. | Open |
| 1111 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387689 | Junction 87689 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56384 at junction 87689 so both are connected. | Open |
| 1112 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387691 | Junction 87691 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56384 at junction 87691 so both are connected. | Open |
| 1113 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387693 | Junction 87693 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56384 at junction 87693 so both are connected. | Open |
| 1114 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387697 | Junction 87697 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 56384 at junction 87697 so both are connected. | Open |
| 1115 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387699 | Junction 87699 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56384 at junction 87699 so both are connected. | Open |
| 1116 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387701 | Junction 87701 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56384 at junction 87701 so both are connected. | Open |
| 1117 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387703 | Junction 87703 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56384 at junction 87703 so both are connected. | Open |
| 1118 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387705 | Junction 87705 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (28 m). → Split pipe 56384 at junction 87705 so both are connected. | Open |
| 1119 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387707 | Junction 87707 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56384 at junction 87707 so both are connected. | Open |
| 1120 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387709 | Junction 87709 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56384 at junction 87709 so both are connected. | Open |
| 1121 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387711 | Junction 87711 (degree 1) lies on pipe 53735 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 53735 at junction 87711 so both are connected. | Open |
| 1122 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387930 | Junction 87930 (degree 1) lies on pipe 56576 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56576 at junction 87930 so both are connected. | Open |
| 1123 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387932 | Junction 87932 (degree 1) lies on pipe 56576 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56576 at junction 87932 so both are connected. | Open |
| 1124 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387934 | Junction 87934 (degree 1) lies on pipe 56576 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56576 at junction 87934 so both are connected. | Open |
| 1125 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387936 | Junction 87936 (degree 1) lies on pipe 56576 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56576 at junction 87936 so both are connected. | Open |
| 1126 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0387938 | Junction 87938 (degree 1) lies on pipe 56576 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 56576 at junction 87938 so both are connected. | Open |
| 1127 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388122 | Junction 88122 (degree 1) lies on pipe 56561 (DN 25, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56561 at junction 88122 so both are connected. | Open |
| 1128 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388369 | Junction 88369 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52832-1 at junction 88369 so both are connected. | Open |
| 1129 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388371 | Junction 88371 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52832-1 at junction 88371 so both are connected. | Open |
| 1130 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388373 | Junction 88373 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52832-1 at junction 88373 so both are connected. | Open |
| 1131 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388375 | Junction 88375 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52832-1 at junction 88375 so both are connected. | Open |
| 1132 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388377 | Junction 88377 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52832-1 at junction 88377 so both are connected. | Open |
| 1133 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388379 | Junction 88379 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52832-1 at junction 88379 so both are connected. | Open |
| 1134 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388381 | Junction 88381 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52832-1 at junction 88381 so both are connected. | Open |
| 1135 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388383 | Junction 88383 (degree 1) lies on pipe 52832-2 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52832-2 at junction 88383 so both are connected. | Open |
| 1136 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388389 | Junction 88389 (degree 1) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56415 at junction 88389 so both are connected. | Open |
| 1137 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388391 | Junction 88391 (degree 1) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56415 at junction 88391 so both are connected. | Open |
| 1138 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388395 | Junction 88395 (degree 1) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Split pipe 56415 at junction 88395 so both are connected. | Open |
| 1139 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388397 | Junction 88397 (degree 1) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56415 at junction 88397 so both are connected. | Open |
| 1140 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388399 | Junction 88399 (degree 1) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56415 at junction 88399 so both are connected. | Open |
| 1141 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388402 | Junction 88402 (degree 1) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56415 at junction 88402 so both are connected. | Open |
| 1142 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388410 | Junction 88410 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56414 at junction 88410 so both are connected. | Open |
| 1143 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388414 | Junction 88414 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56414 at junction 88414 so both are connected. | Open |
| 1144 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388416 | Junction 88416 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56414 at junction 88416 so both are connected. | Open |
| 1145 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388420 | Junction 88420 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 56414 at junction 88420 so both are connected. | Open |
| 1146 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388423 | Junction 88423 (degree 1) lies on pipe 56415 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56415 at junction 88423 so both are connected. | Open |
| 1147 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388426 | Junction 88426 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56414 at junction 88426 so both are connected. | Open |
| 1148 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388429 | Junction 88429 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56414 at junction 88429 so both are connected. | Open |
| 1149 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038843 | Junction 8843 (degree 1) lies on pipe 89524-23 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 89524-23 at junction 8843 so both are connected. | Open |
| 1150 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388431 | Junction 88431 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56414 at junction 88431 so both are connected. | Open |
| 1151 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388434 | Junction 88434 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 56414 at junction 88434 so both are connected. | Open |
| 1152 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388436 | Junction 88436 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56414 at junction 88436 so both are connected. | Open |
| 1153 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388439 | Junction 88439 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56414 at junction 88439 so both are connected. | Open |
| 1154 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388441 | Junction 88441 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56414 at junction 88441 so both are connected. | Open |
| 1155 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388443 | Junction 88443 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 56414 at junction 88443 so both are connected. | Open |
| 1156 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388445 | Junction 88445 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56414 at junction 88445 so both are connected. | Open |
| 1157 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388447 | Junction 88447 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 56414 at junction 88447 so both are connected. | Open |
| 1158 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388449 | Junction 88449 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56414 at junction 88449 so both are connected. | Open |
| 1159 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388451 | Junction 88451 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 56414 at junction 88451 so both are connected. | Open |
| 1160 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388453 | Junction 88453 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56414 at junction 88453 so both are connected. | Open |
| 1161 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388455 | Junction 88455 (degree 1) lies on pipe 56414 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 56414 at junction 88455 so both are connected. | Open |
| 1162 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038851 | Junction 8851 (degree 1) lies on pipe 89524-22 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 89524-22 at junction 8851 so both are connected. | Open |
| 1163 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038854 | Junction 8854 (degree 1) lies on pipe 89524-15 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89524-15 at junction 8854 so both are connected. | Open |
| 1164 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038856 | Junction 8856 (degree 1) lies on pipe 89524-17 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Split pipe 89524-17 at junction 8856 so both are connected. | Open |
| 1165 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038865 | Junction 8865 (degree 1) lies on pipe 89524-13 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 89524-13 at junction 8865 so both are connected. | Open |
| 1166 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388725 | Junction 88725 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52895 at junction 88725 so both are connected. | Open |
| 1167 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388730 | Junction 88730 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52895 at junction 88730 so both are connected. | Open |
| 1168 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388732 | Junction 88732 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 52895 at junction 88732 so both are connected. | Open |
| 1169 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388738 | Junction 88738 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52895 at junction 88738 so both are connected. | Open |
| 1170 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388746 | Junction 88746 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52895 at junction 88746 so both are connected. | Open |
| 1171 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388748 | Junction 88748 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52895 at junction 88748 so both are connected. | Open |
| 1172 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388752 | Junction 88752 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (26 m). → Split pipe 52895 at junction 88752 so both are connected. | Open |
| 1173 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388755 | Junction 88755 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Split pipe 52895 at junction 88755 so both are connected. | Open |
| 1174 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388757 | Junction 88757 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52895 at junction 88757 so both are connected. | Open |
| 1175 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388759 | Junction 88759 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Split pipe 52895 at junction 88759 so both are connected. | Open |
| 1176 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388761 | Junction 88761 (degree 1) lies on pipe 52894 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52894 at junction 88761 so both are connected. | Open |
| 1177 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0388791 | Junction 88791 (degree 1) lies on pipe 52894 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52894 at junction 88791 so both are connected. | Open |
| 1178 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389008 | Junction 89008 (degree 1) lies on pipe 56368 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56368 at junction 89008 so both are connected. | Open |
| 1179 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389010 | Junction 89010 (degree 1) lies on pipe 56368 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 56368 at junction 89010 so both are connected. | Open |
| 1180 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389012 | Junction 89012 (degree 1) lies on pipe 56368 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56368 at junction 89012 so both are connected. | Open |
| 1181 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389014 | Junction 89014 (degree 1) lies on pipe 56368 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56368 at junction 89014 so both are connected. | Open |
| 1182 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389026 | Junction 89026 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52823 at junction 89026 so both are connected. | Open |
| 1183 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389036 | Junction 89036 (degree 1) lies on pipe 89381-1 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (26 m). → Split pipe 89381-1 at junction 89036 so both are connected. | Open |
| 1184 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389068 | Junction 89068 (degree 1) lies on pipe 56568 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (25 m). → Split pipe 56568 at junction 89068 so both are connected. | Open |
| 1185 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389091 | Junction 89091 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 52822-2 at junction 89091 so both are connected. | Open |
| 1186 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389093 | Junction 89093 (degree 1) lies on pipe 52822-1 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (39 m). → Split pipe 52822-1 at junction 89093 so both are connected. | Open |
| 1187 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389228 | Junction 89228 (degree 1) lies on pipe 52836 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 52836 at junction 89228 so both are connected. | Open |
| 1188 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389231 | Junction 89231 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52832-1 at junction 89231 so both are connected. | Open |
| 1189 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389233 | Junction 89233 (degree 1) lies on pipe 52832-1 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 52832-1 at junction 89233 so both are connected. | Open |
| 1190 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389268 | Junction 89268 (degree 1) lies on pipe 52895 (DN 200, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 52895 at junction 89268 so both are connected. | Open |
| 1191 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389314 | Junction 89314 (degree 1) lies on pipe 52819 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (34 m). → Split pipe 52819 at junction 89314 so both are connected. | Open |
| 1192 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389316 | Junction 89316 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52823 at junction 89316 so both are connected. | Open |
| 1193 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389328 | Junction 89328 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 56384 at junction 89328 so both are connected. | Open |
| 1194 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389330 | Junction 89330 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (52 m). → Split pipe 56384 at junction 89330 so both are connected. | Open |
| 1195 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389332 | Junction 89332 (degree 1) lies on pipe 56384 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56384 at junction 89332 so both are connected. | Open |
| 1196 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389334 | Junction 89334 (degree 1) lies on pipe 53735 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (47 m). → Split pipe 53735 at junction 89334 so both are connected. | Open |
| 1197 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389336 | Junction 89336 (degree 1) lies on pipe 53737 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 53737 at junction 89336 so both are connected. | Open |
| 1198 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389338 | Junction 89338 (degree 1) lies on pipe 53736 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (25 m). → Split pipe 53736 at junction 89338 so both are connected. | Open |
| 1199 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389340 | Junction 89340 (degree 1) lies on pipe 53736 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 53736 at junction 89340 so both are connected. | Open |
| 1200 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389342 | Junction 89342 (degree 1) lies on pipe 53736 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Split pipe 53736 at junction 89342 so both are connected. | Open |
| 1201 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389469 | Junction 89469 (degree 1) lies on pipe 56588 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56588 at junction 89469 so both are connected. | Open |
| 1202 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389471 | Junction 89471 (degree 1) lies on pipe 56588 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 56588 at junction 89471 so both are connected. | Open |
| 1203 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389489 | Junction 89489 (degree 1) lies on pipe 89381-1 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Split pipe 89381-1 at junction 89489 so both are connected. | Open |
| 1204 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389605 | Junction 89605 (degree 1) lies on pipe 52822-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52822-2 at junction 89605 so both are connected. | Open |
| 1205 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389609 | Junction 89609 (degree 1) lies on pipe 53735 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 53735 at junction 89609 so both are connected. | Open |
| 1206 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389611 | Junction 89611 (degree 1) lies on pipe 52823 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 52823 at junction 89611 so both are connected. | Open |
| 1207 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389621 | Junction 89621 (degree 1) lies on pipe 56486 (DN 32, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 56486 at junction 89621 so both are connected. | Open |
| 1208 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389623 | Junction 89623 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 56487 at junction 89623 so both are connected. | Open |
| 1209 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389649 | Junction 89649 (degree 1) lies on pipe 52740 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 52740 at junction 89649 so both are connected. | Open |
| 1210 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389651 | Junction 89651 (degree 1) lies on pipe 52740 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52740 at junction 89651 so both are connected. | Open |
| 1211 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389653 | Junction 89653 (degree 1) lies on pipe 52740 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52740 at junction 89653 so both are connected. | Open |
| 1212 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389654 | Junction 89654 (degree 1) lies on pipe 52740 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 52740 at junction 89654 so both are connected. | Open |
| 1213 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389658 | Junction 89658 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56487 at junction 89658 so both are connected. | Open |
| 1214 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389660 | Junction 89660 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56487 at junction 89660 so both are connected. | Open |
| 1215 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389662 | Junction 89662 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56487 at junction 89662 so both are connected. | Open |
| 1216 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389664 | Junction 89664 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Split pipe 56487 at junction 89664 so both are connected. | Open |
| 1217 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389666 | Junction 89666 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56487 at junction 89666 so both are connected. | Open |
| 1218 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389668 | Junction 89668 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56487 at junction 89668 so both are connected. | Open |
| 1219 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389670 | Junction 89670 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 56487 at junction 89670 so both are connected. | Open |
| 1220 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389672 | Junction 89672 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Split pipe 56487 at junction 89672 so both are connected. | Open |
| 1221 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389674 | Junction 89674 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56487 at junction 89674 so both are connected. | Open |
| 1222 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389676 | Junction 89676 (degree 1) lies on pipe 56487 (DN 40, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56487 at junction 89676 so both are connected. | Open |
| 1223 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389708 | Junction 89708 (degree 1) lies on pipe 56391 (DN 80, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (82 m). → Split pipe 56391 at junction 89708 so both are connected. | Open |
| 1224 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389782 | Junction 89782 (degree 1) lies on pipe 52834-2 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 52834-2 at junction 89782 so both are connected. | Open |
| 1225 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389799 | Junction 89799 (degree 1) lies on pipe 56366-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (42 m). → Split pipe 56366-1 at junction 89799 so both are connected. | Open |
| 1226 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389802 | Junction 89802 (degree 1) lies on pipe 56366-1 (DN 90, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (28 m). → Split pipe 56366-1 at junction 89802 so both are connected. | Open |
| 1227 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039723 | Junction 9723 (degree 1) lies on pipe 89723-3 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89723-3 at junction 9723 so both are connected. | Open |
| 1228 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039724 | Junction 9724 (degree 1) lies on pipe 99702-1 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 99702-1 at junction 9724 so both are connected. | Open |
| 1229 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039726 | Junction 9726 (degree 1) lies on pipe 99702-1 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 99702-1 at junction 9726 so both are connected. | Open |
| 1230 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039727 | Junction 9727 (degree 1) lies on pipe 99702-2 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Split pipe 99702-2 at junction 9727 so both are connected. | Open |
| 1231 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039731 | Junction 9731 (degree 1) lies on pipe 99702-3 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 99702-3 at junction 9731 so both are connected. | Open |
| 1232 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039732 | Junction 9732 (degree 1) lies on pipe 99702-3 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 99702-3 at junction 9732 so both are connected. | Open |
| 1233 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039733 | Junction 9733 (degree 1) lies on pipe 89723-2 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (15 m). → Split pipe 89723-2 at junction 9733 so both are connected. | Open |
| 1234 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039734 | Junction 9734 (degree 1) lies on pipe 89723-2 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 89723-2 at junction 9734 so both are connected. | Open |
| 1235 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039736 | Junction 9736 (degree 1) lies on pipe 89723-5 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 89723-5 at junction 9736 so both are connected. | Open |
| 1236 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039737 | Junction 9737 (degree 1) lies on pipe 89723-3 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Split pipe 89723-3 at junction 9737 so both are connected. | Open |
| 1237 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039740 | Junction 9740 (degree 1) lies on pipe 89723-11 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 89723-11 at junction 9740 so both are connected. | Open |
| 1238 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039746 | Junction 9746 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89724 at junction 9746 so both are connected. | Open |
| 1239 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039747 | Junction 9747 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89724 at junction 9747 so both are connected. | Open |
| 1240 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039762 | Junction 9762 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 89724 at junction 9762 so both are connected. | Open |
| 1241 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039769 | Junction 9769 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89724 at junction 9769 so both are connected. | Open |
| 1242 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039771 | Junction 9771 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89724 at junction 9771 so both are connected. | Open |
| 1243 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039773 | Junction 9773 (degree 1) lies on pipe 89723-11 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 89723-11 at junction 9773 so both are connected. | Open |
| 1244 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039791 | Junction 9791 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89724 at junction 9791 so both are connected. | Open |
| 1245 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039794 | Junction 9794 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89724 at junction 9794 so both are connected. | Open |
| 1246 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039796 | Junction 9796 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89724 at junction 9796 so both are connected. | Open |
| 1247 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039798 | Junction 9798 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89724 at junction 9798 so both are connected. | Open |
| 1248 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039800 | Junction 9800 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 89724 at junction 9800 so both are connected. | Open |
| 1249 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039802 | Junction 9802 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89724 at junction 9802 so both are connected. | Open |
| 1250 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039804 | Junction 9804 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89724 at junction 9804 so both are connected. | Open |
| 1251 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039806 | Junction 9806 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 89724 at junction 9806 so both are connected. | Open |
| 1252 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039808 | Junction 9808 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 89724 at junction 9808 so both are connected. | Open |
| 1253 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039812 | Junction 9812 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89724 at junction 9812 so both are connected. | Open |
| 1254 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039814 | Junction 9814 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89724 at junction 9814 so both are connected. | Open |
| 1255 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039820 | Junction 9820 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89724 at junction 9820 so both are connected. | Open |
| 1256 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039822 | Junction 9822 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89724 at junction 9822 so both are connected. | Open |
| 1257 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039824 | Junction 9824 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89724 at junction 9824 so both are connected. | Open |
| 1258 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039826 | Junction 9826 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Split pipe 89724 at junction 9826 so both are connected. | Open |
| 1259 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039828 | Junction 9828 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89724 at junction 9828 so both are connected. | Open |
| 1260 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039830 | Junction 9830 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89724 at junction 9830 so both are connected. | Open |
| 1261 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039832 | Junction 9832 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 89724 at junction 9832 so both are connected. | Open |
| 1262 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039834 | Junction 9834 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 89724 at junction 9834 so both are connected. | Open |
| 1263 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039836 | Junction 9836 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Split pipe 89724 at junction 9836 so both are connected. | Open |
| 1264 | ERROR P95 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039838 | Junction 9838 (degree 1) lies on pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Split pipe 89724 at junction 9838 so both are connected. | Open |
| 1265 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0314586 | Junction 14586 (degree 1) is 0.28 m from pipe 91552-6 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Extend/snap to pipe 91552-6 and split it there, or confirm the gap is real. | Open |
| 1266 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0314602 | Junction 14602 (degree 1) is 0.09 m from pipe 52827-6 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Extend/snap to pipe 52827-6 and split it there, or confirm the gap is real. | Open |
| 1267 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0314612 | Junction 14612 (degree 1) is 0.10 m from pipe 91552-7 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Extend/snap to pipe 91552-7 and split it there, or confirm the gap is real. | Open |
| 1268 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0314618 | Junction 14618 (degree 1) is 0.06 m from pipe 52827-3 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Extend/snap to pipe 52827-3 and split it there, or confirm the gap is real. | Open |
| 1269 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev033297 | Junction 3297 (degree 1) is 0.45 m from pipe 56681-2 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Extend/snap to pipe 56681-2 and split it there, or confirm the gap is real. | Open |
| 1270 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0372346 | Junction 72346 (degree 1) is 0.07 m from pipe 89927 (DN 110, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (102 m). → Extend/snap to pipe 89927 and split it there, or confirm the gap is real. | Open |
| 1271 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0375967 | Junction 75967 (degree 1) is 0.70 m from pipe 56543 (DN 150, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Extend/snap to pipe 56543 and split it there, or confirm the gap is real. | Open |
| 1272 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0375969 | Junction 75969 (degree 1) is 0.73 m from pipe 56539 (distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Extend/snap to pipe 56539 and split it there, or confirm the gap is real. | Open |
| 1273 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0386552 | Junction 86552 (degree 1) is 0.71 m from pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Extend/snap to pipe 89724 and split it there, or confirm the gap is real. | Open |
| 1274 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0386562 | Junction 86562 (degree 1) is 0.85 m from pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Extend/snap to pipe 89724 and split it there, or confirm the gap is real. | Open |
| 1275 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0387183 | Junction 87183 (degree 1) is 0.82 m from pipe 91552-5 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 91552-5 and split it there, or confirm the gap is real. | Open |
| 1276 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039729 | Junction 9729 (degree 1) is 0.16 m from pipe 99702-2 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Extend/snap to pipe 99702-2 and split it there, or confirm the gap is real. | Open |
| 1277 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039739 | Junction 9739 (degree 1) is 0.17 m from pipe 89723-9 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Extend/snap to pipe 89723-9 and split it there, or confirm the gap is real. | Open |
| 1278 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039744 | Junction 9744 (degree 1) is 0.09 m from pipe 89723-5 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Extend/snap to pipe 89723-5 and split it there, or confirm the gap is real. | Open |
| 1279 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039759 | Junction 9759 (degree 1) is 0.19 m from pipe 89723-15 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Extend/snap to pipe 89723-15 and split it there, or confirm the gap is real. | Open |
| 1280 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039764 | Junction 9764 (degree 1) is 0.22 m from pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Extend/snap to pipe 89724 and split it there, or confirm the gap is real. | Open |
| 1281 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039780 | Junction 9780 (degree 1) is 0.16 m from pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Extend/snap to pipe 89724 and split it there, or confirm the gap is real. | Open |
| 1282 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039787 | Junction 9787 (degree 1) is 0.08 m from pipe 89723-20 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 89723-20 and split it there, or confirm the gap is real. | Open |
| 1283 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039810 | Junction 9810 (degree 1) is 0.26 m from pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 89724 and split it there, or confirm the gap is real. | Open |
| 1284 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039816 | Junction 9816 (degree 1) is 0.12 m from pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Extend/snap to pipe 89724 and split it there, or confirm the gap is real. | Open |
| 1285 | ERROR P95 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039818 | Junction 9818 (degree 1) is 0.15 m from pipe 89724 (DN 63, distribution) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Extend/snap to pipe 89724 and split it there, or confirm the gap is real. | Open |
| 1286 | ERROR P93 | Missing pipe diameter · 1567 featuresATTR_DIAMETER_MISSINGCompleteness | Pipe_Functional_Rev041,567 Pipe_Functional_Rev04 features | 1,567 of 3,754 Pipe_Functional_Rev04 features (42%): missing pipe diameter. Example: Pipe 56368 has diameter 0 (placeholder); material 'PE'. 96% of them have Material = 'Unknown', which points to a systematic gap for that group. → Enter the nominal diameter from records or field survey. This is a systematic data gap: fix it in bulk in the source system. | Open |
| 1287 | ERROR P89 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389702 | Junction 89702 (degree 1) is 0.67 m from pipe 89528 (DN 110, hydrant) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (36 m). → Extend/snap to pipe 89528 and split it there, or confirm the gap is real. | Open |
| 1288 | ERROR P88 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev044 pipes near 77106 | 4 pipe(s), 285 m in total incl. 4 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1289 | ERROR P88 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378558 | Junction 78558 (degree 1) is 0.36 m from pipe 65670 (DN 20, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 3 pipe(s) (8 m). → Extend/snap to pipe 65670 and split it there, or confirm the gap is real. | Open |
| 1290 | ERROR P88 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378641 | Junction 78641 (degree 1) is 0.88 m from pipe 60593 (DN 50, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 4 pipe(s) (26 m). → Extend/snap to pipe 60593 and split it there, or confirm the gap is real. | Open |
| 1291 | ERROR P86 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0386774 | Junction 86774 (degree 1) is 0.52 m from pipe 65452 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 2 pipe(s) (22 m). → Extend/snap to pipe 65452 and split it there, or confirm the gap is real. | Open |
| 1292 | ERROR P85 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 76999 | 2 pipe(s), 37 m in total incl. 2 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1293 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev033017 | Junction 3017 (degree 1) lies on pipe 60726 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 60726 at junction 3017 so both are connected. | Open |
| 1294 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0367525 | Junction 67525 (degree 5) lies on pipe 59013 (DN 40, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 59013 at junction 67525 so both are connected. | Open |
| 1295 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0375928 | Junction 75928 (degree 2) lies on pipe 65705 (DN 100, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 65705 at junction 75928 so both are connected. | Open |
| 1296 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389371 | Junction 89371 (degree 1) lies on pipe 65717 (DN 31.75, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (24 m). → Split pipe 65717 at junction 89371 so both are connected. | Open |
| 1297 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389383 | Junction 89383 (degree 1) lies on pipe 65717 (DN 31.75, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 65717 at junction 89383 so both are connected. | Open |
| 1298 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389397 | Junction 89397 (degree 1) lies on pipe 65717 (DN 31.75, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (23 m). → Split pipe 65717 at junction 89397 so both are connected. | Open |
| 1299 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389399 | Junction 89399 (degree 1) lies on pipe 65717 (DN 31.75, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Split pipe 65717 at junction 89399 so both are connected. | Open |
| 1300 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389401 | Junction 89401 (degree 1) lies on pipe 65717 (DN 31.75, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Split pipe 65717 at junction 89401 so both are connected. | Open |
| 1301 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389467 | Junction 89467 (degree 1) lies on pipe 65716 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 65716 at junction 89467 so both are connected. | Open |
| 1302 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389487 | Junction 89487 (degree 1) lies on pipe 56559 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Split pipe 56559 at junction 89487 so both are connected. | Open |
| 1303 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389596 | Junction 89596 (degree 1) lies on pipe 56559 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (37 m). → Split pipe 56559 at junction 89596 so both are connected. | Open |
| 1304 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389598 | Junction 89598 (degree 1) lies on pipe 56559 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Split pipe 56559 at junction 89598 so both are connected. | Open |
| 1305 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389600 | Junction 89600 (degree 1) lies on pipe 56559 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (11 m). → Split pipe 56559 at junction 89600 so both are connected. | Open |
| 1306 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389741 | Junction 89741 (degree 1) lies on pipe 65674 (DN 100, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (19 m). → Split pipe 65674 at junction 89741 so both are connected. | Open |
| 1307 | ERROR P85 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0389744 | Junction 89744 (degree 1) lies on pipe 65691 (DN 100, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (13 m). → Split pipe 65691 at junction 89744 so both are connected. | Open |
| 1308 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0314626 | Junction 14626 (degree 1) is 0.98 m from pipe 64035 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Extend/snap to pipe 64035 and split it there, or confirm the gap is real. | Open |
| 1309 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318663 | Junction 18663 (degree 1) is 0.68 m from pipe 93176 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (20 m). → Extend/snap to pipe 93176 and split it there, or confirm the gap is real. | Open |
| 1310 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318667 | Junction 18667 (degree 1) is 0.77 m from pipe 93175 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Extend/snap to pipe 93175 and split it there, or confirm the gap is real. | Open |
| 1311 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318679 | Junction 18679 (degree 1) is 0.95 m from pipe 65058 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 65058 and split it there, or confirm the gap is real. | Open |
| 1312 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318709 | Junction 18709 (degree 1) is 0.49 m from pipe 65060 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (2 m). → Extend/snap to pipe 65060 and split it there, or confirm the gap is real. | Open |
| 1313 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318719 | Junction 18719 (degree 1) is 0.37 m from pipe 65055 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Extend/snap to pipe 65055 and split it there, or confirm the gap is real. | Open |
| 1314 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318772 | Junction 18772 (degree 1) is 0.86 m from pipe 93230 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Extend/snap to pipe 93230 and split it there, or confirm the gap is real. | Open |
| 1315 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318774 | Junction 18774 (degree 1) is 0.86 m from pipe 93229 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Extend/snap to pipe 93229 and split it there, or confirm the gap is real. | Open |
| 1316 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318782 | Junction 18782 (degree 1) is 0.92 m from pipe 93235 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 93235 and split it there, or confirm the gap is real. | Open |
| 1317 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318784 | Junction 18784 (degree 1) is 0.93 m from pipe 93234 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 93234 and split it there, or confirm the gap is real. | Open |
| 1318 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0372355 | Junction 72355 (degree 1) is 0.93 m from pipe 65525 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Extend/snap to pipe 65525 and split it there, or confirm the gap is real. | Open |
| 1319 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378253 | Junction 78253 (degree 1) is 0.90 m from pipe 59048 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Extend/snap to pipe 59048 and split it there, or confirm the gap is real. | Open |
| 1320 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378255 | Junction 78255 (degree 1) is 0.91 m from pipe 59047 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (4 m). → Extend/snap to pipe 59047 and split it there, or confirm the gap is real. | Open |
| 1321 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378532 | Junction 78532 (degree 1) is 0.79 m from pipe 65641 (DN 63, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (1 m). → Extend/snap to pipe 65641 and split it there, or confirm the gap is real. | Open |
| 1322 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378651 | Junction 78651 (degree 1) is 0.27 m from pipe 59251 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Extend/snap to pipe 59251 and split it there, or confirm the gap is real. | Open |
| 1323 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381376 | Junction 81376 (degree 1) is 0.08 m from pipe 93176 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Extend/snap to pipe 93176 and split it there, or confirm the gap is real. | Open |
| 1324 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381377 | Junction 81377 (degree 1) is 0.13 m from pipe 93176 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Extend/snap to pipe 93176 and split it there, or confirm the gap is real. | Open |
| 1325 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0386448 | Junction 86448 (degree 1) is 0.99 m from pipe 65449 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Extend/snap to pipe 65449 and split it there, or confirm the gap is real. | Open |
| 1326 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0386846 | Junction 86846 (degree 1) is 0.44 m from pipe 64021 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Extend/snap to pipe 64021 and split it there, or confirm the gap is real. | Open |
| 1327 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0386848 | Junction 86848 (degree 1) is 0.49 m from pipe 64020 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (7 m). → Extend/snap to pipe 64020 and split it there, or confirm the gap is real. | Open |
| 1328 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0387022 | Junction 87022 (degree 1) is 0.66 m from pipe 65453 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Extend/snap to pipe 65453 and split it there, or confirm the gap is real. | Open |
| 1329 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0387085 | Junction 87085 (degree 1) is 0.74 m from pipe 64146 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 64146 and split it there, or confirm the gap is real. | Open |
| 1330 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0387512 | Junction 87512 (degree 1) is 0.26 m from pipe 64367 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Extend/snap to pipe 64367 and split it there, or confirm the gap is real. | Open |
| 1331 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0387556 | Junction 87556 (degree 1) is 0.55 m from pipe 64392 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Extend/snap to pipe 64392 and split it there, or confirm the gap is real. | Open |
| 1332 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0387736 | Junction 87736 (degree 1) is 0.35 m from pipe 65204 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Extend/snap to pipe 65204 and split it there, or confirm the gap is real. | Open |
| 1333 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0387929 | Junction 87929 (degree 1) is 0.40 m from pipe 64593 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Extend/snap to pipe 64593 and split it there, or confirm the gap is real. | Open |
| 1334 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388000 | Junction 88000 (degree 1) is 0.73 m from pipe 65344 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (10 m). → Extend/snap to pipe 65344 and split it there, or confirm the gap is real. | Open |
| 1335 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388117 | Junction 88117 (degree 1) is 0.86 m from pipe 64688 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 64688 and split it there, or confirm the gap is real. | Open |
| 1336 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388119 | Junction 88119 (degree 1) is 0.87 m from pipe 64687 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 64687 and split it there, or confirm the gap is real. | Open |
| 1337 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388382 | Junction 88382 (degree 1) is 0.81 m from pipe 65439 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 65439 and split it there, or confirm the gap is real. | Open |
| 1338 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0388870 | Junction 88870 (degree 1) is 0.52 m from pipe 65300 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (9 m). → Extend/snap to pipe 65300 and split it there, or confirm the gap is real. | Open |
| 1339 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389049 | Junction 89049 (degree 1) is 0.49 m from pipe 65175 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (17 m). → Extend/snap to pipe 65175 and split it there, or confirm the gap is real. | Open |
| 1340 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389077 | Junction 89077 (degree 1) is 0.73 m from pipe 65190 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Extend/snap to pipe 65190 and split it there, or confirm the gap is real. | Open |
| 1341 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389103 | Junction 89103 (degree 1) is 0.35 m from pipe 64484 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (18 m). → Extend/snap to pipe 64484 and split it there, or confirm the gap is real. | Open |
| 1342 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389115 | Junction 89115 (degree 1) is 0.27 m from pipe 65212 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Extend/snap to pipe 65212 and split it there, or confirm the gap is real. | Open |
| 1343 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389117 | Junction 89117 (degree 1) is 0.29 m from pipe 65211 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (22 m). → Extend/snap to pipe 65211 and split it there, or confirm the gap is real. | Open |
| 1344 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389181 | Junction 89181 (degree 1) is 0.57 m from pipe 65365 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 65365 and split it there, or confirm the gap is real. | Open |
| 1345 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389339 | Junction 89339 (degree 1) is 0.84 m from pipe 65327 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (21 m). → Extend/snap to pipe 65327 and split it there, or confirm the gap is real. | Open |
| 1346 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389361 | Junction 89361 (degree 1) is 0.73 m from pipe 58883 (DN 25, service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (25 m). → Extend/snap to pipe 58883 and split it there, or confirm the gap is real. | Open |
| 1347 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389362 | Junction 89362 (degree 1) is 0.34 m from pipe 65342 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 65342 and split it there, or confirm the gap is real. | Open |
| 1348 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389364 | Junction 89364 (degree 1) is 0.36 m from pipe 65341 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 65341 and split it there, or confirm the gap is real. | Open |
| 1349 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389366 | Junction 89366 (degree 1) is 0.43 m from pipe 65342 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (6 m). → Extend/snap to pipe 65342 and split it there, or confirm the gap is real. | Open |
| 1350 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389404 | Junction 89404 (degree 1) is 0.62 m from pipe 65363 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 65363 and split it there, or confirm the gap is real. | Open |
| 1351 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389406 | Junction 89406 (degree 1) is 0.69 m from pipe 65362 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 65362 and split it there, or confirm the gap is real. | Open |
| 1352 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389410 | Junction 89410 (degree 1) is 0.46 m from pipe 65366 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 65366 and split it there, or confirm the gap is real. | Open |
| 1353 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389412 | Junction 89412 (degree 1) is 0.52 m from pipe 65365 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (5 m). → Extend/snap to pipe 65365 and split it there, or confirm the gap is real. | Open |
| 1354 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389426 | Junction 89426 (degree 1) is 0.20 m from pipe 65374 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Extend/snap to pipe 65374 and split it there, or confirm the gap is real. | Open |
| 1355 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389428 | Junction 89428 (degree 1) is 0.20 m from pipe 65373 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (3 m). → Extend/snap to pipe 65373 and split it there, or confirm the gap is real. | Open |
| 1356 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389518 | Junction 89518 (degree 1) is 0.61 m from pipe 65421 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (8 m). → Extend/snap to pipe 65421 and split it there, or confirm the gap is real. | Open |
| 1357 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389531 | Junction 89531 (degree 1) is 0.88 m from pipe 65431 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (16 m). → Extend/snap to pipe 65431 and split it there, or confirm the gap is real. | Open |
| 1358 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389559 | Junction 89559 (degree 1) is 0.50 m from pipe 65442 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (27 m). → Extend/snap to pipe 65442 and split it there, or confirm the gap is real. | Open |
| 1359 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389561 | Junction 89561 (degree 1) is 0.50 m from pipe 65443 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (29 m). → Extend/snap to pipe 65443 and split it there, or confirm the gap is real. | Open |
| 1360 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389563 | Junction 89563 (degree 1) is 0.50 m from pipe 65442 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (29 m). → Extend/snap to pipe 65442 and split it there, or confirm the gap is real. | Open |
| 1361 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389583 | Junction 89583 (degree 1) is 0.55 m from pipe 64113 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (12 m). → Extend/snap to pipe 64113 and split it there, or confirm the gap is real. | Open |
| 1362 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389704 | Junction 89704 (degree 1) is 0.59 m from pipe 65515 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (59 m). → Extend/snap to pipe 65515 and split it there, or confirm the gap is real. | Open |
| 1363 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389705 | Junction 89705 (degree 1) is 0.59 m from pipe 65514 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (59 m). → Extend/snap to pipe 65514 and split it there, or confirm the gap is real. | Open |
| 1364 | ERROR P85 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389931 | Junction 89931 (degree 1) is 0.54 m from pipe 64513 (service) but is not connected to it, so the hydraulic model treats them as separate networks. Fixing it reconnects 1 pipe(s) (14 m). → Extend/snap to pipe 64513 and split it there, or confirm the gap is real. | Open |
| 1365 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 53745 | 1 pipe(s), 13 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1366 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 56535 | 1 pipe(s), 7 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1367 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 56539 | 1 pipe(s), 14 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1368 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 56549 | 1 pipe(s), 24 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1369 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 56550 | 1 pipe(s), 20 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1370 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 56595 | 1 pipe(s), 10 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1371 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 93643 | 1 pipe(s), 26 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1372 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 93647 | 1 pipe(s), 6 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1373 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 95548 | 1 pipe(s), 44 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1374 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 95549 | 1 pipe(s), 2 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1375 | ERROR P82 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 95551 | 1 pipe(s), 13 m in total incl. 1 main(s), are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1376 | ERROR P80 | Zero-length pipeGEOM_ZERO_LENGTHGeometry | Pipe_Functional_Rev0489455-30 | Pipe 89455-30 is 0.057 m long (minimum 0.1 m). → Delete the degenerate pipe or redraw it. | Open |
| 1377 | ERROR P80 | Zero-length pipeGEOM_ZERO_LENGTHGeometry | Pipe_Functional_Rev0489498-6 | Pipe 89498-6 is 0.099 m long (minimum 0.1 m). → Delete the degenerate pipe or redraw it. | Open |
| 1378 | ERROR P76 | Zero-length pipeGEOM_ZERO_LENGTHGeometry | Pipe_Functional_Rev0456383-1 | Pipe 56383-1 is 0.010 m long (minimum 0.1 m). → Delete the degenerate pipe or redraw it. | Open |
| 1379 | ERROR P76 | Zero-length pipeGEOM_ZERO_LENGTHGeometry | Pipe_Functional_Rev0456675-4 | Pipe 56675-4 is 0.040 m long (minimum 0.1 m). → Delete the degenerate pipe or redraw it. | Open |
| 1380 | ERROR P70 | Coincident junctionsTOPO_COINCIDENT_NODESTopology | Junction_Rev0376044 | Junctions 76044 and 19607 are at the same location. → Merge them and re-point pipes to the surviving junction. | Open |
| 1381 | WARNING P60 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038392 | Junction 8392 (degree 1) lies on pipe 53701 (DN 90, transmission) but is not connected to it. → Split pipe 53701 at junction 8392 so both are connected. | Open |
| 1382 | WARNING P60 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038456 | Junction 8456 (degree 1) lies on pipe 56399-1 (DN 90, transmission) but is not connected to it. → Split pipe 56399-1 at junction 8456 so both are connected. | Open |
| 1383 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0320035 | Junction 20035 (degree 1) is 0.64 m from pipe 95312 (DN 110, transmission) but is not connected to it. → Extend/snap to pipe 95312 and split it there, or confirm the gap is real. | Open |
| 1384 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0325347 | Junction 25347 (degree 1) is 0.99 m from pipe 89713 (DN 160, transmission) but is not connected to it. → Extend/snap to pipe 89713 and split it there, or confirm the gap is real. | Open |
| 1385 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358411 | Junction 58411 (degree 1) is 0.33 m from pipe 56493-1 (DN 150, transmission) but is not connected to it. → Extend/snap to pipe 56493-1 and split it there, or confirm the gap is real. | Open |
| 1386 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358412 | Junction 58412 (degree 1) is 0.85 m from pipe 52864 (DN 100, transmission) but is not connected to it. → Extend/snap to pipe 52864 and split it there, or confirm the gap is real. | Open |
| 1387 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358415 | Junction 58415 (degree 1) is 0.85 m from pipe 56397 (DN 63, transmission) but is not connected to it. → Extend/snap to pipe 56397 and split it there, or confirm the gap is real. | Open |
| 1388 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358419 | Junction 58419 (degree 1) is 0.84 m from pipe 52888 (DN 150, transmission) but is not connected to it. → Extend/snap to pipe 52888 and split it there, or confirm the gap is real. | Open |
| 1389 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358435 | Junction 58435 (degree 1) is 0.19 m from pipe 56451-2 (DN 100, transmission) but is not connected to it. → Extend/snap to pipe 56451-2 and split it there, or confirm the gap is real. | Open |
| 1390 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358459 | Junction 58459 (degree 1) is 0.25 m from pipe 56591 (DN 63, transmission) but is not connected to it. → Extend/snap to pipe 56591 and split it there, or confirm the gap is real. | Open |
| 1391 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0367588 | Junction 67588 (degree 1) is 0.79 m from pipe 89530-4 (DN 110, transmission) but is not connected to it. → Extend/snap to pipe 89530-4 and split it there, or confirm the gap is real. | Open |
| 1392 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0376049 | Junction 76049 (degree 1) is 0.67 m from pipe 89469-1 (DN 110, transmission) but is not connected to it. → Extend/snap to pipe 89469-1 and split it there, or confirm the gap is real. | Open |
| 1393 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0377378 | Junction 77378 (degree 1) is 0.80 m from pipe 89498-4 (DN 110, transmission) but is not connected to it. → Extend/snap to pipe 89498-4 and split it there, or confirm the gap is real. | Open |
| 1394 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038396 | Junction 8396 (degree 1) is 0.74 m from pipe 99643-3 (DN 75, transmission) but is not connected to it. → Extend/snap to pipe 99643-3 and split it there, or confirm the gap is real. | Open |
| 1395 | WARNING P60 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038398 | Junction 8398 (degree 1) is 0.34 m from pipe 99643-3 (DN 75, transmission) but is not connected to it. → Extend/snap to pipe 99643-3 and split it there, or confirm the gap is real. | Open |
| 1396 | WARNING P56 | Missing or unknown pipe material · 1511 featuresATTR_MATERIAL_MISSINGCompleteness | Pipe_Functional_Rev041,511 Pipe_Functional_Rev04 features | 1,511 of 3,754 Pipe_Functional_Rev04 features (40%): missing or unknown pipe material. Example: Pipe 58901 material is “Unknown”. → Record the pipe material (affects roughness, failure risk and renewal planning). This is a systematic data gap: fix it in bulk in the source system. | Open |
| 1397 | WARNING P52 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev038268 | Junction 8268 (degree 1) lies on pipe 89420 (DN 90, distribution) but is not connected to it. → Split pipe 89420 at junction 8268 so both are connected. | Open |
| 1398 | WARNING P52 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev039420 | Junction 9420 (degree 1) lies on pipe 56490 (DN 32, distribution) but is not connected to it. → Split pipe 56490 at junction 9420 so both are connected. | Open |
| 1399 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358431 | Junction 58431 (degree 1) is 0.31 m from pipe 52817 (DN 150, distribution) but is not connected to it. → Extend/snap to pipe 52817 and split it there, or confirm the gap is real. | Open |
| 1400 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358461 | Junction 58461 (degree 1) is 0.35 m from pipe 56625-15 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56625-15 and split it there, or confirm the gap is real. | Open |
| 1401 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358468 | Junction 58468 (degree 1) is 0.61 m from pipe 56635-7 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56635-7 and split it there, or confirm the gap is real. | Open |
| 1402 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0376034 | Junction 76034 (degree 1) is 0.63 m from pipe 56635-8 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56635-8 and split it there, or confirm the gap is real. | Open |
| 1403 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev037786 | Junction 7786 (degree 1) is 0.92 m from pipe 89361 (DN 63, distribution) but is not connected to it. → Extend/snap to pipe 89361 and split it there, or confirm the gap is real. | Open |
| 1404 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev037793 | Junction 7793 (degree 1) is 0.76 m from pipe 89375 (DN 63, distribution) but is not connected to it. → Extend/snap to pipe 89375 and split it there, or confirm the gap is real. | Open |
| 1405 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev037795 | Junction 7795 (degree 1) is 0.97 m from pipe 89378 (DN 63, distribution) but is not connected to it. → Extend/snap to pipe 89378 and split it there, or confirm the gap is real. | Open |
| 1406 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378325 | Junction 78325 (degree 1) is 0.87 m from pipe 56633-38 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-38 and split it there, or confirm the gap is real. | Open |
| 1407 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378333 | Junction 78333 (degree 1) is 0.48 m from pipe 56633-33 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-33 and split it there, or confirm the gap is real. | Open |
| 1408 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378335 | Junction 78335 (degree 1) is 0.99 m from pipe 56633-31 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-31 and split it there, or confirm the gap is real. | Open |
| 1409 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378337 | Junction 78337 (degree 1) is 0.77 m from pipe 56633-30 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-30 and split it there, or confirm the gap is real. | Open |
| 1410 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378371 | Junction 78371 (degree 1) is 0.75 m from pipe 56633-12 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-12 and split it there, or confirm the gap is real. | Open |
| 1411 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378373 | Junction 78373 (degree 1) is 0.97 m from pipe 56633-10 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-10 and split it there, or confirm the gap is real. | Open |
| 1412 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378511 | Junction 78511 (degree 1) is 0.43 m from pipe 89472-1 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 89472-1 and split it there, or confirm the gap is real. | Open |
| 1413 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038527 | Junction 8527 (degree 1) is 0.95 m from pipe 56637-13 (distribution) but is not connected to it. → Extend/snap to pipe 56637-13 and split it there, or confirm the gap is real. | Open |
| 1414 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038629 | Junction 8629 (degree 1) is 0.78 m from pipe 56633-25 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-25 and split it there, or confirm the gap is real. | Open |
| 1415 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038638 | Junction 8638 (degree 1) is 0.32 m from pipe 56633-32 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-32 and split it there, or confirm the gap is real. | Open |
| 1416 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038641 | Junction 8641 (degree 1) is 0.61 m from pipe 56633-41 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-41 and split it there, or confirm the gap is real. | Open |
| 1417 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038648 | Junction 8648 (degree 1) is 0.66 m from pipe 56633-36 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-36 and split it there, or confirm the gap is real. | Open |
| 1418 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038650 | Junction 8650 (degree 1) is 0.67 m from pipe 56633-35 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-35 and split it there, or confirm the gap is real. | Open |
| 1419 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038652 | Junction 8652 (degree 1) is 0.64 m from pipe 56633-34 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-34 and split it there, or confirm the gap is real. | Open |
| 1420 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038655 | Junction 8655 (degree 1) is 0.86 m from pipe 56633-36 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-36 and split it there, or confirm the gap is real. | Open |
| 1421 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev038657 | Junction 8657 (degree 1) is 0.38 m from pipe 56633-42 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-42 and split it there, or confirm the gap is real. | Open |
| 1422 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389961 | Junction 89961 (degree 1) is 0.69 m from pipe 89706-2 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 89706-2 and split it there, or confirm the gap is real. | Open |
| 1423 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0390047 | Junction 90047 (degree 1) is 0.71 m from pipe 56633-10 (DN 110, distribution) but is not connected to it. → Extend/snap to pipe 56633-10 and split it there, or confirm the gap is real. | Open |
| 1424 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039058 | Junction 9058 (degree 1) is 0.62 m from pipe 89587 (DN 63, distribution) but is not connected to it. → Extend/snap to pipe 89587 and split it there, or confirm the gap is real. | Open |
| 1425 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039059 | Junction 9059 (degree 1) is 0.74 m from pipe 89595 (DN 63, distribution) but is not connected to it. → Extend/snap to pipe 89595 and split it there, or confirm the gap is real. | Open |
| 1426 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039060 | Junction 9060 (degree 1) is 0.45 m from pipe 89596 (DN 63, distribution) but is not connected to it. → Extend/snap to pipe 89596 and split it there, or confirm the gap is real. | Open |
| 1427 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039062 | Junction 9062 (degree 1) is 0.78 m from pipe 89548-2 (DN 75, distribution) but is not connected to it. → Extend/snap to pipe 89548-2 and split it there, or confirm the gap is real. | Open |
| 1428 | WARNING P52 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev039071 | Junction 9071 (degree 1) is 0.83 m from pipe 89542-2 (DN 90, distribution) but is not connected to it. → Extend/snap to pipe 89542-2 and split it there, or confirm the gap is real. | Open |
| 1429 | WARNING P50 | Abrupt diameter changeATTR_DIAMETER_JUMPPlausibility | Pipe_Functional_Rev0456501-1 | Diameter drops from 100 mm (52878) to 20 mm (56501-1) at a simple connection. → Check for a typo in either diameter, or a missing branch/reducer. | Open |
| 1430 | WARNING P50 | Abrupt diameter changeATTR_DIAMETER_JUMPPlausibility | Pipe_Functional_Rev0459075 | Diameter drops from 110 mm (56641-7) to 25 mm (59075) at a simple connection. → Check for a typo in either diameter, or a missing branch/reducer. | Open |
| 1431 | WARNING P50 | Abrupt diameter changeATTR_DIAMETER_JUMPPlausibility | Pipe_Functional_Rev0459080 | Diameter drops from 110 mm (56641-1) to 25 mm (59080) at a simple connection. → Check for a typo in either diameter, or a missing branch/reducer. | Open |
| 1432 | WARNING P50 | Abrupt diameter changeATTR_DIAMETER_JUMPPlausibility | Pipe_Functional_Rev0489619-1 | Diameter drops from 150 mm (56562) to 25.4 mm (89619-1) at a simple connection. → Check for a typo in either diameter, or a missing branch/reducer. | Open |
| 1433 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452847 | Pipes 52847 (DN 150, transmission) and 89713 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1434 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452857 | Pipes 52857 (DN 150, transmission) and 89718-2 (DN 150, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1435 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452889 | Pipes 52889 (DN 150, transmission) and 89468 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1436 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453726 | Pipes 53726 (DN 110, transmission) and 89718-2 (DN 150, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1437 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453727 | Pipes 53727 (DN 32, transmission) and 56551 (DN 125, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1438 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453728 | Pipes 53728 (DN 40, transmission) and 89522-2 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1439 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453745 | Pipes 53745 (DN 110, transmission) and 53746 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1440 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456468-2 | Pipes 56468-2 (DN 63, transmission) and 89530-4 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1441 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456469 | Pipes 56469 (DN 63, transmission) and 95343 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1442 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456473 | Pipes 56473 (DN 100, transmission) and 89713 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1443 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456562 | Pipes 56562 (DN 150, transmission) and 89718-2 (DN 150, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1444 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456591 | Pipes 56591 (DN 63, transmission) and 56659-1 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1445 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0465346-9 | Pipes 65346-9 (DN 19.05, transmission) and 89718-1 (DN 150, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1446 | WARNING P50 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0489518 | Pipes 89518 (DN 110, transmission) and 56451-2 (DN 100, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1447 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452823 | Pipes 52823 (DN 150, distribution) and 102634-1 (DN 50, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1448 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452836 | Pipes 52836 (DN 200, distribution) and 56618-1 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1449 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452836 | Pipes 52836 (DN 200, distribution) and 56451-2 (DN 100, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1450 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452836 | Pipes 52836 (DN 200, distribution) and 89518 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1451 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452836 | Pipes 52836 (DN 200, distribution) and 56617-1 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1452 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452847 | Pipes 52847 (DN 150, transmission) and 52870 (DN 150, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1453 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452867 | Pipes 52867 (DN 200, distribution) and 65346-9 (DN 19.05, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1454 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452870 | Pipes 52870 (DN 150, distribution) and 56473 (DN 100, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1455 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452870 | Pipes 52870 (DN 150, distribution) and 89713 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1456 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452898 | Pipes 52898 (DN 150, transmission) and 56508 (distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1457 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0452916 | Pipes 52916 (DN 150, distribution) and 89501-13 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1458 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453519 | Pipes 53519 (DN 150, distribution) and 76999 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1459 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456380 | Pipes 56380 (DN 90, distribution) and 95582 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1460 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456439 | Pipes 56439 (DN 63, distribution) and 56619-11 (DN 110, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1461 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456473 | Pipes 56473 (DN 100, transmission) and 99702-4 (DN 63, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1462 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456490 | Pipes 56490 (DN 32, distribution) and 89712 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1463 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456542 | Pipes 56542 (DN 200, distribution) and 93643 (DN 355, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1464 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456544 | Pipes 56544 (DN 300, distribution) and 56545 (DN 200, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1465 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456548 | Pipes 56548 (DN 150, distribution) and 77106 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1466 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456568 | Pipes 56568 (DN 63, distribution) and 89714 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1467 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456576 | Pipes 56576 (DN 63, distribution) and 89714 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1468 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0489379 | Pipes 89379 (DN 110, transmission) and 89381-1 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1469 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0489481 | Pipes 89481 (DN 90, distribution) and 95580 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1470 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0489481 | Pipes 89481 (DN 90, distribution) and 95579 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1471 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0489481 | Pipes 89481 (DN 90, distribution) and 95578 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1472 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0489613 | Pipes 89613 (DN 110, distribution) and 95582 (DN 160, transmission) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1473 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0489713 | Pipes 89713 (DN 160, transmission) and 99701 (DN 63, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1474 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0493643 | Pipes 93643 (DN 355, transmission) and 95548 (DN 355, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1475 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0495581 | Pipes 95581 (DN 160, transmission) and 56366-1 (DN 90, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1476 | WARNING P48 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0495582 | Pipes 95582 (DN 160, transmission) and 56366-1 (DN 90, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1477 | WARNING P48 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev043 pipes near 65715 | 3 pipe(s), 26 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1478 | WARNING P47 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 63872 | 2 pipe(s), 19 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1479 | WARNING P47 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 63886 | 2 pipe(s), 20 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1480 | WARNING P47 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 63928 | 2 pipe(s), 18 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1481 | WARNING P47 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 64695 | 2 pipe(s), 19 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1482 | WARNING P47 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 64697 | 2 pipe(s), 11 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1483 | WARNING P47 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 65128 | 2 pipe(s), 14 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1484 | WARNING P47 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 65254 | 2 pipe(s), 12 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1485 | WARNING P47 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev042 pipes near 65256 | 2 pipe(s), 13 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1486 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453737 | Pipes 53737 (DN 110, distribution) and 56633-42 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1487 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453737 | Pipes 53737 (DN 110, distribution) and 56633-40 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1488 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453737 | Pipes 53737 (DN 110, distribution) and 56633-38 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1489 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453737 | Pipes 53737 (DN 110, distribution) and 56633-29 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1490 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453737 | Pipes 53737 (DN 110, distribution) and 56633-27 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1491 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453737 | Pipes 53737 (DN 110, distribution) and 56633-25 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1492 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453737 | Pipes 53737 (DN 110, distribution) and 56633-24 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1493 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453748 | Pipes 53748 (DN 110, distribution) and 56527 (DN 63, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1494 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453748 | Pipes 53748 (DN 110, distribution) and 56549 (distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1495 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453748 | Pipes 53748 (DN 110, distribution) and 56550 (distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1496 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453748 | Pipes 53748 (DN 110, distribution) and 56543 (DN 150, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1497 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453748 | Pipes 53748 (DN 110, distribution) and 56548 (DN 150, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1498 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453748 | Pipes 53748 (DN 110, distribution) and 56542 (DN 200, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1499 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0453748 | Pipes 53748 (DN 110, distribution) and 95548 (DN 355, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1500 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456371 | Pipes 56371 (DN 63, distribution) and 89472-4 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1501 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456380 | Pipes 56380 (DN 90, distribution) and 89613 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1502 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456384 | Pipes 56384 (DN 150, distribution) and 89472-4 (DN 110, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1503 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456527 | Pipes 56527 (DN 63, distribution) and 56544 (DN 300, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1504 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456539 | Pipes 56539 (distribution) and 56549 (distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1505 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456539 | Pipes 56539 (distribution) and 95548 (DN 355, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1506 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456542 | Pipes 56542 (DN 200, distribution) and 95548 (DN 355, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1507 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456543 | Pipes 56543 (DN 150, distribution) and 56549 (distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1508 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456543 | Pipes 56543 (DN 150, distribution) and 95548 (DN 355, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1509 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456549 | Pipes 56549 (distribution) and 95548 (DN 355, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1510 | WARNING P46 | Pipes cross without a junctionTOPO_CROSSINGTopology | Pipe_Functional_Rev0456550 | Pipes 56550 (distribution) and 95548 (DN 355, distribution) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. | Open |
| 1511 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 59281 | 1 pipe(s), 2 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1512 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 59291 | 1 pipe(s), 21 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1513 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63832 | 1 pipe(s), 11 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1514 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63858 | 1 pipe(s), 4 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1515 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63884 | 1 pipe(s), 9 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1516 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63923 | 1 pipe(s), 7 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1517 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63924 | 1 pipe(s), 16 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1518 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63925 | 1 pipe(s), 12 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1519 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63926 | 1 pipe(s), 9 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1520 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63929 | 1 pipe(s), 6 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1521 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63930 | 1 pipe(s), 14 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1522 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63931 | 1 pipe(s), 8 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1523 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63932 | 1 pipe(s), 12 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1524 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63933 | 1 pipe(s), 11 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1525 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63934 | 1 pipe(s), 18 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1526 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63935 | 1 pipe(s), 16 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1527 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63936 | 1 pipe(s), 14 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1528 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63937 | 1 pipe(s), 17 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1529 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63938 | 1 pipe(s), 13 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1530 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63939 | 1 pipe(s), 13 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1531 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63940 | 1 pipe(s), 14 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1532 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63941 | 1 pipe(s), 15 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1533 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63942 | 1 pipe(s), 15 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1534 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63943 | 1 pipe(s), 13 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1535 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63944 | 1 pipe(s), 18 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1536 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63945 | 1 pipe(s), 17 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1537 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63946 | 1 pipe(s), 19 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1538 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63947 | 1 pipe(s), 15 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1539 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63948 | 1 pipe(s), 13 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1540 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 63949 | 1 pipe(s), 13 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1541 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64077 | 1 pipe(s), 9 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1542 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64692 | 1 pipe(s), 8 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1543 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64693 | 1 pipe(s), 6 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1544 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64694 | 1 pipe(s), 6 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1545 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64696 | 1 pipe(s), 5 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1546 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64698 | 1 pipe(s), 12 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1547 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64699 | 1 pipe(s), 6 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1548 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64700 | 1 pipe(s), 5 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1549 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64701 | 1 pipe(s), 3 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1550 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64702 | 1 pipe(s), 4 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1551 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64704 | 1 pipe(s), 5 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1552 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64706 | 1 pipe(s), 7 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1553 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64707 | 1 pipe(s), 5 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1554 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64709 | 1 pipe(s), 5 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1555 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 64710 | 1 pipe(s), 4 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1556 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 65137 | 1 pipe(s), 7 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1557 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 65253 | 1 pipe(s), 7 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1558 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 65255 | 1 pipe(s), 23 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1559 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 65257 | 1 pipe(s), 4 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1560 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 65386 | 1 pipe(s), 10 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1561 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 65485 | 1 pipe(s), 71 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1562 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 65514 | 1 pipe(s), 59 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1563 | WARNING P44 | Network part not connected to supplyTOPO_DISCONNECTEDTopology | Pipe_Functional_Rev041 pipes near 65515 | 1 pipe(s), 83 m in total, are not connected to the main network. → Find the missing connection (unsnapped end, missing pipe or junction); if this is a separate system, add its source. | Open |
| 1564 | WARNING P42 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0367601 | Junction 67601 (degree 2) lies on pipe 65660 (DN 40, service) but is not connected to it. → Split pipe 65660 at junction 67601 so both are connected. | Open |
| 1565 | WARNING P42 | Junction touches a pipe but is not connectedTOPO_NODE_ON_PIPETopology | Junction_Rev0378644 | Junction 78644 (degree 1) lies on pipe 59248 (DN 25, service) but is not connected to it. → Split pipe 59248 at junction 78644 so both are connected. | Open |
| 1566 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0318656 | Junction 18656 (degree 1) is 0.11 m from pipe 93172 (DN 25, service) but is not connected to it. → Extend/snap to pipe 93172 and split it there, or confirm the gap is real. | Open |
| 1567 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0332082 | Junction 32082 (degree 1) is 0.85 m from pipe 59215 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59215 and split it there, or confirm the gap is real. | Open |
| 1568 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0332084 | Junction 32084 (degree 1) is 0.86 m from pipe 59214 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59214 and split it there, or confirm the gap is real. | Open |
| 1569 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0358454 | Junction 58454 (degree 1) is 0.71 m from pipe 59324 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59324 and split it there, or confirm the gap is real. | Open |
| 1570 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0377487 | Junction 77487 (degree 1) is 0.59 m from pipe 58674 (DN 25, service) but is not connected to it. → Extend/snap to pipe 58674 and split it there, or confirm the gap is real. | Open |
| 1571 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0377511 | Junction 77511 (degree 1) is 0.59 m from pipe 58662 (DN 25, service) but is not connected to it. → Extend/snap to pipe 58662 and split it there, or confirm the gap is real. | Open |
| 1572 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0377900 | Junction 77900 (degree 1) is 0.93 m from pipe 58871 (DN 25, service) but is not connected to it. → Extend/snap to pipe 58871 and split it there, or confirm the gap is real. | Open |
| 1573 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0377903 | Junction 77903 (degree 1) is 0.93 m from pipe 58870 (DN 25, service) but is not connected to it. → Extend/snap to pipe 58870 and split it there, or confirm the gap is real. | Open |
| 1574 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0377966 | Junction 77966 (degree 1) is 0.70 m from pipe 59244 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59244 and split it there, or confirm the gap is real. | Open |
| 1575 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0377982 | Junction 77982 (degree 1) is 0.55 m from pipe 59222 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59222 and split it there, or confirm the gap is real. | Open |
| 1576 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378132 | Junction 78132 (degree 1) is 0.88 m from pipe 60592 (DN 50, service) but is not connected to it. → Extend/snap to pipe 60592 and split it there, or confirm the gap is real. | Open |
| 1577 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378176 | Junction 78176 (degree 1) is 0.59 m from pipe 59009 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59009 and split it there, or confirm the gap is real. | Open |
| 1578 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378178 | Junction 78178 (degree 1) is 0.85 m from pipe 59008 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59008 and split it there, or confirm the gap is real. | Open |
| 1579 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378206 | Junction 78206 (degree 1) is 0.92 m from pipe 59024 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59024 and split it there, or confirm the gap is real. | Open |
| 1580 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378208 | Junction 78208 (degree 1) is 0.92 m from pipe 59023 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59023 and split it there, or confirm the gap is real. | Open |
| 1581 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378599 | Junction 78599 (degree 1) is 0.67 m from pipe 58911 (DN 25, service) but is not connected to it. → Extend/snap to pipe 58911 and split it there, or confirm the gap is real. | Open |
| 1582 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378607 | Junction 78607 (degree 1) is 0.72 m from pipe 59244 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59244 and split it there, or confirm the gap is real. | Open |
| 1583 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378627 | Junction 78627 (degree 1) is 0.96 m from pipe 89504 (DN 25, service) but is not connected to it. → Extend/snap to pipe 89504 and split it there, or confirm the gap is real. | Open |
| 1584 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378635 | Junction 78635 (degree 1) is 0.69 m from pipe 59226 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59226 and split it there, or confirm the gap is real. | Open |
| 1585 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378726 | Junction 78726 (degree 1) is 0.81 m from pipe 65740 (DN 25, service) but is not connected to it. → Extend/snap to pipe 65740 and split it there, or confirm the gap is real. | Open |
| 1586 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378732 | Junction 78732 (degree 1) is 0.80 m from pipe 59300 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59300 and split it there, or confirm the gap is real. | Open |
| 1587 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0378734 | Junction 78734 (degree 1) is 0.80 m from pipe 59299 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59299 and split it there, or confirm the gap is real. | Open |
| 1588 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381353 | Junction 81353 (degree 1) is 0.24 m from pipe 65667 (DN 16, service) but is not connected to it. → Extend/snap to pipe 65667 and split it there, or confirm the gap is real. | Open |
| 1589 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381355 | Junction 81355 (degree 1) is 0.21 m from pipe 60692 (DN 25, service) but is not connected to it. → Extend/snap to pipe 60692 and split it there, or confirm the gap is real. | Open |
| 1590 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381356 | Junction 81356 (degree 1) is 0.20 m from pipe 60691 (DN 25, service) but is not connected to it. → Extend/snap to pipe 60691 and split it there, or confirm the gap is real. | Open |
| 1591 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381379 | Junction 81379 (degree 1) is 0.39 m from pipe 60726 (DN 25, service) but is not connected to it. → Extend/snap to pipe 60726 and split it there, or confirm the gap is real. | Open |
| 1592 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381380 | Junction 81380 (degree 1) is 0.39 m from pipe 60723 (DN 25, service) but is not connected to it. → Extend/snap to pipe 60723 and split it there, or confirm the gap is real. | Open |
| 1593 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381381 | Junction 81381 (degree 1) is 0.41 m from pipe 60724 (DN 25, service) but is not connected to it. → Extend/snap to pipe 60724 and split it there, or confirm the gap is real. | Open |
| 1594 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381382 | Junction 81382 (degree 1) is 0.34 m from pipe 60727 (DN 25, service) but is not connected to it. → Extend/snap to pipe 60727 and split it there, or confirm the gap is real. | Open |
| 1595 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0381383 | Junction 81383 (degree 1) is 0.34 m from pipe 60726 (DN 25, service) but is not connected to it. → Extend/snap to pipe 60726 and split it there, or confirm the gap is real. | Open |
| 1596 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0386470 | Junction 86470 (degree 1) is 0.30 m from pipe 65450 (service) but is not connected to it. → Extend/snap to pipe 65450 and split it there, or confirm the gap is real. | Open |
| 1597 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389037 | Junction 89037 (degree 1) is 0.72 m from pipe 65169 (service) but is not connected to it. → Extend/snap to pipe 65169 and split it there, or confirm the gap is real. | Open |
| 1598 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389955 | Junction 89955 (degree 1) is 0.67 m from pipe 65654 (DN 25, service) but is not connected to it. → Extend/snap to pipe 65654 and split it there, or confirm the gap is real. | Open |
| 1599 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389956 | Junction 89956 (degree 1) is 0.67 m from pipe 65653 (DN 25, service) but is not connected to it. → Extend/snap to pipe 65653 and split it there, or confirm the gap is real. | Open |
| 1600 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389957 | Junction 89957 (degree 1) is 0.35 m from pipe 65660 (DN 40, service) but is not connected to it. → Extend/snap to pipe 65660 and split it there, or confirm the gap is real. | Open |
| 1601 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389962 | Junction 89962 (degree 1) is 0.35 m from pipe 65655 (DN 25, service) but is not connected to it. → Extend/snap to pipe 65655 and split it there, or confirm the gap is real. | Open |
| 1602 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389969 | Junction 89969 (degree 1) is 0.23 m from pipe 60689 (DN 40, service) but is not connected to it. → Extend/snap to pipe 60689 and split it there, or confirm the gap is real. | Open |
| 1603 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0389970 | Junction 89970 (degree 1) is 0.27 m from pipe 65667 (DN 16, service) but is not connected to it. → Extend/snap to pipe 65667 and split it there, or confirm the gap is real. | Open |
| 1604 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0390022 | Junction 90022 (degree 1) is 0.74 m from pipe 65736 (DN 25, service) but is not connected to it. → Extend/snap to pipe 65736 and split it there, or confirm the gap is real. | Open |
| 1605 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0390024 | Junction 90024 (degree 1) is 0.74 m from pipe 65735 (DN 25, service) but is not connected to it. → Extend/snap to pipe 65735 and split it there, or confirm the gap is real. | Open |
| 1606 | WARNING P42 | Pipe end not connected (snapping gap)TOPO_UNCONNECTED_ENDTopology | Junction_Rev0390032 | Junction 90032 (degree 1) is 0.77 m from pipe 59296 (DN 25, service) but is not connected to it. → Extend/snap to pipe 59296 and split it there, or confirm the gap is real. | Open |
| 1607 | WARNING P40 | Missing elevationATTR_ELEVATION_MISSINGCompleteness | Junction_Rev0320333 | Junction 20333 elevation is empty. → Enter the surveyed elevation or interpolate from a DEM. | Open |
| 1608 | WARNING P40 | Missing elevationATTR_ELEVATION_MISSINGCompleteness | Junction_Rev0320350 | Junction 20350 elevation is empty. → Enter the surveyed elevation or interpolate from a DEM. | Open |
| 1609 | WARNING P40 | Missing elevationATTR_ELEVATION_MISSINGCompleteness | Junction_Rev0320351 | Junction 20351 elevation is empty. → Enter the surveyed elevation or interpolate from a DEM. | Open |
| 1610 | WARNING P40 | Missing elevationATTR_ELEVATION_MISSINGCompleteness | Junction_Rev0320352 | Junction 20352 elevation is empty. → Enter the surveyed elevation or interpolate from a DEM. | Open |
| 1611 | WARNING P40 | Missing elevationATTR_ELEVATION_MISSINGCompleteness | Junction_Rev0320353 | Junction 20353 elevation is empty. → Enter the surveyed elevation or interpolate from a DEM. | Open |
| 1612 | WARNING P40 | Missing elevationATTR_ELEVATION_MISSINGCompleteness | Junction_Rev0320354 | Junction 20354 elevation is empty. → Enter the surveyed elevation or interpolate from a DEM. | Open |
| 1613 | WARNING P40 | Missing elevationATTR_ELEVATION_MISSINGCompleteness | Junction_Rev0320356 | Junction 20356 elevation is empty. → Enter the surveyed elevation or interpolate from a DEM. | Open |
| 1614 | WARNING P40 | Elevation outlierATTR_ELEVATION_OUTLIERPlausibility | Junction_Rev039411 | Junction 9411 is at 198.2 m while its 2 neighbours are around 178.4 m (+19.8 m). → Check for a typo or wrong datum; correct the elevation if it is not a real step. | Open |
| 1615 | INFO P26 | Missing installation year · 2119 featuresATTR_YEAR_MISSINGCompleteness | Pipe_Functional_Rev042,119 Pipe_Functional_Rev04 features | 2,119 of 3,754 Pipe_Functional_Rev04 features (56%): missing installation year. Example: Pipe 52740 has no installation year. → Record the installation year (needed for asset-age and renewal planning). This is a systematic data gap: fix it in bulk in the source system. | Open |
| 1616 | INFO P21 | Pipes cross without a junction · 883 featuresTOPO_CROSSINGTopology | Pipe_Functional_Rev04883 Pipe_Functional_Rev04 features | 883 cases involving 556 of 3,754 Pipe_Functional_Rev04 features (15%): pipes cross without a junction. Example: Pipes 52817 (DN 150, distribution) and 64434 (service) cross without a shared junction. → Confirm it is a crossing at different depths; otherwise split both pipes and add a junction. This is a systematic data gap: fix it in bulk in the source system. | Open |